HomeMy WebLinkAboutUNION PARK - FDP240004 - SUBMITTAL DOCUMENTS - ROUND 3 - Supporting Documentation (2)M M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
PANEL
"UNIT"
200/2
PANEL
"UNIT"
200/2
PANEL
"HPL1"
T
F
800/3
800A
1000/3
1000A
200F3 200F3
400F4
1600S4
1
2
3
44
10
0
/
3
M
M
N
G
120/208V, 3PH, 4W
PAD MOUNTED
TRANSFORMER
"MSB" 1200A, 120/208V, 3PH, 4W, NEMA 3R, 100kAIC
TYPICAL UNIT
PANEL (QTY 16)
TYPICAL UNIT
PANEL (QTY 16)
ONE-LINE KEY NOTES:
1. "MSB" SHALL BE THREE TIER SERIES RATED AT 100 kAIC. BASIS OF DESIGN IS SCHNEIDER ELECTRIC
(SQUARE D) EZM METER CENTER WITH THREE TIER SERIES RATING, CONSISTING OF TYPE L MAIN FUSE
QOH TENANT CIRCUIT BREAKER, AND TYPE QOY TENANT PANEL CIRCUIT BREAKERS.
2. CIRCUIT BREAKER FOR PV SYSTEM, PROVIDED BY EC. COORDINATE REQUIREMENTS WITH PV
CONTRACTOR.
3. PV CONNECTION BY PV CONTRACTOR.
4. PROVIDE (2)2"C TO ROOF. FEEDERS BY SOLAR CONTRACTOR. FOR FUTURE USE.
5. NON-FUSED, UTILITY DISCONNECT AND PV PRODUCTION METER BY PV CONTRACTOR.
#
1 1
TO UTILITY PRIMARY
PV PANEL
/ ARRAY
2
3
4
5
1600A, 120/208V, 3PH,
4W, SECONDARY
CONNECTION CABINET
BY UTILITY
320A IN-LINE METER FOR HOUSE PANEL RATED AT 80%, 400A
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:17 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - 32 UNIT
E500
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - U.P. APARTMENTS - 32 UNIT
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
1600A 250BJ 8BJ 6GEC 3/0GEC 4GEC 3/0GEC 3/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S3' RATHER THAN AN 'F3' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
FROM AHJ TO DOWNSIZE CONDUCTORS.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR PER THE ABOVE. CONTRACTOR TO PROVIDE WRITTEN APPROVAL
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC, ARTICLE 310.15.B.3.a. UNLESS NOTED OTHERWISE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16. (100% OF 75 DEGREE THWN OR THHN).
NOTES:
200 200F3 1 2" (3)#3/0 (1)#6 200 200F3 1 2" (3)250 KCM (1)#4 AL
OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
3-WIRE FEEDER SCHEDULE
60 60F2 1 1" (2#)6 (1)#10
50 50F2 1 1" (2#)8 (1)#10
40 40F2 1 1" (2)#8 (1)#10
30 30F2 1 3/4" (2)#10 (1)#10
20 20F2 1 1/2" (2)#12 (1)#12
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER
2-WIRE FEEDER SCHEDULE
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S4' RATHER THAN AN 'F4' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
FROM AHJ TO DOWNSIZE CONDUCTORS.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR PER THE ABOVE. CONTRACTOR TO PROVIDE WRITTEN APPROVAL
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC, ARTICLE 310.15.B.3.a. UNLESS NOTED OTHERWISE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16
NOTES:
1600 1600S4 5 3" (4)400 KCM N/A 1600 1600S4 6 3" (4)400 KCM N/A
1600 1600F4 5 3" (4)400 KCM (1)#4/0 1600 1600F4 6 3" (4)400 KCM (1)350 KCM AL
1000 1000F4 3 3" (4)400 KCM (1)#2/0 1000 1000F4 4 3" (4)350 KCM (1)#4/0 AL
800 800F4 3 2 1/2" (4)300 KCM (1)#1/0 800 800F4 3 3" (4)400 KCM (1)#3/0 AL
400 400F4 2 2 1/2" (4)250 KCM (1)#3 400 400F4 2 3" (4)350 KCM (1)#1 AL
90 90F4 1 1 1/2" (4)#1/0 (1)#8
80 80F4 1 1 1/4" (4)#1 (1)#8
70 70F4 1 1 1/4" (4)#2 (1)#8
60 60F4 1 1 1/4" (4)#3 (1)#10
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
4-WIRE FEEDER SCHEDULE
MINIMUM SERVICE SIZE 512112 1422
HOUSE LOAD (VA) 115520 115520 321
DWELLING UNIT DEMAND 396592 1101
DEMAND FACTOR 0.31
TOTAL DWELLING UNIT LOAD 1279328
VA AMPS
TOTAL 32 1119584 159744
UNIT C1 2 34156 68312 4992 9984
UNIT C 2 36655 73310 4992 9984
UNIT B2 6 35692 214152 4992 29952
UNIT B1 2 34156 68312 4992 9984
UNIT B 2 36073 72146 4992 9984
UNIT A3 2 34156 68312 4992 9984
UNIT A2 6 34456 206736 4992 29952
UNIT A1 6 34480 206880 4992 29952
UNIT A 4 35356 141424 4992 19968
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 208Y/120, 3PH
SERVICE CALCULATION FOR 32 UNIT
MINIMUM SERVICE SIZE 330793 918
HOUSE LOAD (VA) 115520 115520 321
DWELLING UNIT DEMAND 215273 598
DEMAND FACTOR 0.41
TOTAL DWELLING UNIT LOAD 525055
VA AMPS
TOTAL 13 460159 64896
UNIT C1 2 34156 68312 4992 9984
UNIT C 2 36655 73310 4992 9984
UNIT B2 6 35692 214152 4992 29952
UNIT B1 2 34156 68312 4992 9984
UNIT B 1 36073 36073 4992 4992
UNIT A3
UNIT A2
UNIT A1
UNIT A
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE 208Y/120, 3PH
FEEDER CALCULATION FOR RIGHT METERS
MINIMUM SERVICE SIZE 286624 796
HOUSE LOAD (VA)
DWELLING UNIT DEMAND 286624 796
DEMAND FACTOR 0.38
TOTAL DWELLING UNIT LOAD 754273
VA AMPS
TOTAL 19 659425 94848
UNIT C1
UNIT C
UNIT B2
UNIT B1
UNIT B 1 36073 36073 4992 4992
UNIT A3 2 34156 68312 4992 9984
UNIT A2 6 34456 206736 4992 29952
UNIT A1 6 34480 206880 4992 29952
UNIT A 4 35356 141424 4992 19968
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE 208Y/120, 3PH
FEEDER CALCULATION FOR LEFT METERS
M
M
M
M
M
M M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
PANEL
"UNIT"
200/2
PANEL
"UNIT"
200/2
PANEL
"HPL1"
T
F
1000/3
1000A
1000/3
1000A
400F4
2000S4
1
2
3
44
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
200F3 M
M
M
M
M
200F3
10
0
/
3
M
1000/3
1000A
1000F4
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
PANEL
"UNIT"
200/2
N
G
120/208V, 3PH, 4W
PAD MOUNTED
TRANSFORMER
"MSB" 2000A, 120/208V, 3PH, 4W,
NEMA 3R, 100kAIC
TYPICAL UNIT
PANEL (QTY 19)
TYPICAL UNIT
PANEL (QTY 21)
ONE-LINE KEY NOTES:
1. "MSB" SHALL BE THREE TIER SERIES RATED AT 100 kAIC. BASIS OF DESIGN IS SCHNEIDER ELECTRIC
(SQUARE D) EZM METER CENTER WITH THREE TIER SERIES RATING, CONSISTING OF TYPE L MAIN FUSE
QOH TENANT CIRCUIT BREAKER, AND TYPE QOY TENANT PANEL CIRCUIT BREAKERS OR EQUAL.
2. CIRCUIT BREAKER FOR PV SYSTEM, PROVIDED BY EC. COORDINATE REQUIREMENTS WITH PV
CONTRACTOR.
3. PV CONNECTION BY PV CONTRACTOR.
4. PROVIDE (2)2"C TO ROOF. FEEDERS BY SOLAR CONTRACTOR. FOR FUTURE USE.
5. NON-FUSED, UTILITY DISCONNECT AND PV PRODUCTION METER BY PV CONTRACTOR.
#
1 1
TO UTILITY PRIMARY
PV PANEL
/ ARRAY
2
3
4
5
2000A, 120/208V, 3PH,
4W, SECONDARY
CONNECTION CABINET
BY UTILITY
1
TYPICAL UNIT
PANEL (QTY 22)
320A IN-LINE METER FOR HOUSE PANEL
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:18 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - 49 UNIT
E501
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - U.P. APARTMENTS - 49 UNIT
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
2000A 300BJ 8BJ 6GEC 3/0GEC 4GEC 3/0GEC 3/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S3' RATHER THAN AN 'F3' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
FROM AHJ TO DOWNSIZE CONDUCTORS.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR PER THE ABOVE. CONTRACTOR TO PROVIDE WRITTEN APPROVAL
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC, ARTICLE 310.15.B.3.a. UNLESS NOTED OTHERWISE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16. (100% OF 75 DEGREE THWN OR THHN).
NOTES:
200 200F3 1 2" (3)#3/0 (1)#6 200 200F3 1 2" (3)250 KCM (1)#4 AL
OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
3-WIRE FEEDER SCHEDULE
60 60F2 1 1" (2#)6 (1)#10
50 50F2 1 1" (2#)8 (1)#10
40 40F2 1 1" (2)#8 (1)#10
30 30F2 1 3/4" (2)#10 (1)#10
20 20F2 1 1/2" (2)#12 (1)#12
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER
2-WIRE FEEDER SCHEDULE
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S4' RATHER THAN AN 'F4' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
FROM AHJ TO DOWNSIZE CONDUCTORS.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR PER THE ABOVE. CONTRACTOR TO PROVIDE WRITTEN APPROVAL
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC, ARTICLE 310.15.B.3.a. UNLESS NOTED OTHERWISE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16
NOTES:
2000 2000S4 6 3" (4)400 KCM N/A 2000 2000S4 8 3" (4)350 KCM N/A
2000 2000F4 6 3" (4)400 KCM (1)250 KCM 2000 2000F4 8 3" (4)350 KCM (1)400 KCM AL
1000 1000F4 4 3" (4)400 KCM (1)#2/0 1000 1000F4 5 3" (4)350 KCM (1)#4/0 AL
400 400F4 2 2 1/2" (4)250 KCM (1)#3 400 400F4 2 3" (4)350 KCM (1)#1 AL
100 100F4 1 1 1/2" (4)#1/0 (1)#8 100 100F4 1 1 1/2" (4)#3/0 (1)#4 AL
90 90F4 1 1 1/2" (4)#1/0 (1)#8
80 80F4 1 1 1/4" (4)#1 (1)#8
70 70F4 1 1 1/4" (4)#2 (1)#8
60 60F4 1 1 1/4" (4)#3 (1)#10
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
4-WIRE FEEDER SCHEDULE
MINIMUM SERVICE SIZE 633525 1759
HOUSE LOAD (VA) 115520 115520 321
DWELLING UNIT DEMAND 518005 1438
DEMAND FACTOR 0.26
TOTAL DWELLING UNIT LOAD 1992328
VA AMPS
TOTAL 49 1747720 244608
UNIT D1 6 36613 219678 4992 29952
UNIT C3 3 36289 108867 4992 14976
UNIT C2 10 36130 361300 4992 49920
UNIT C1 6 36037 216222 4992 29952
UNIT A2 2 34864 69728 4992 9984
UNIT A1 19 35182 668458 4992 94848
UNIT S1 3 34489 103467 4992 14976
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 208Y/120, 3PH
SERVICE CALCULATION FOR 49 UNIT BUILDING
MINIMUM SERVICE SIZE 292345 812
HOUSE LOAD (VA) 115520 115520 321
DWELLING UNIT DEMAND 176825 491
DEMAND FACTOR 0.43
TOTAL DWELLING UNIT LOAD 411220
VA AMPS
TOTAL 10 361300 49920
UNIT D1
UNIT C3
UNIT C2 10 36130 361300 4992 49920
UNIT C1
UNIT A2
UNIT A1
UNIT S1
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE 208Y/120, 3PH
FEEDER CALCULATION FOR RIGHT METERS
MINIMUM SERVICE SIZE 311917 866
HOUSE LOAD (VA)
DWELLING UNIT DEMAND 311917 866
DEMAND FACTOR 0.37
TOTAL DWELLING UNIT LOAD 843018
VA AMPS
TOTAL 21 738186 104832
UNIT D1
UNIT C3
UNIT C2
UNIT C1
UNIT A2 2 34864 69728 4992 9984
UNIT A1 19 35182 668458 4992 94848
UNIT S1
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE 208Y/120, 3PH
FEEDER CALCULATION FOR LEFT METERS
MINIMUM SERVICE SIZE 280474 779
HOUSE LOAD (VA)
DWELLING UNIT DEMAND 280474 779
DEMAND FACTOR 0.38
TOTAL DWELLING UNIT LOAD 738090
VA AMPS
TOTAL 18 648234 89856
UNIT D1 6 36613 219678 4992 29952
UNIT C3 3 36289 108867 4992 14976
UNIT C2
UNIT C1 6 36037 216222 4992 29952
UNIT A2
UNIT A1
UNIT S1 3 34489 103467 4992 14976
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE 208Y/120, 3PH
FEEDER CALCULATION FOR CENTER METERS
M
M
M
M
M
PANEL
"UNIT"
150/2
T
F
150F3
1
2
3
4
600S3
600/2
600A
10
0
/
3
M
PANEL
"HPL1"
225F3
N
G
TYPICAL UNIT
PANEL (QTY 4)
ONE-LINE KEY NOTES:
1. "MSB" SHALL BE THREE TIER SERIES RATED AT 100 kAIC. BASIS OF DESIGN IS SCHNEIDER ELECTRIC
(SQUARE D) EZM METER CENTER WITH THREE TIER SERIES RATING, CONSISTING OF TYPE L MAIN FUSE
QOH TENANT CIRCUIT BREAKER, AND TYPE QOY TENANT PANEL CIRCUIT BREAKERS OR EQUIVALENT.
2. HOUSE PANEL IS OPTIONAL DEPENDING ON LOCATION AND REQUIREMENTS FOR LIGHTING OR
IRRIGATION LOADS. SITE PLANS TO BE PROVIDED TO COORDINATE REQUIRED LOCATIONS. MAIN FUSES
SHALL ALSO BE REDUCED TO 400A WITHOUT A HOUSE PANEL.
#
TO UTILITY PRIMARY
1
2
120/240V, 1PH, 3W
PAD MOUNTED
TRANSFORMER
"ZIEGLER, 4-UNIT METER
STACK" 600A, 120/240V, 1PH, 3W,
NEMA 3R, 100kAIC
PV PANEL
/ ARRAY
3
4
5
6
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:18 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - ZIEGLER
E502
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - ZIEGLER - 4 UNIT
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
600A 2/0BJ 8BJ 6GEC 2/0GEC 4GEC 2/0GEC 2/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S3' RATHER THAN AN 'F3' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
FROM AHJ TO DOWNSIZE CONDUCTORS.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR PER THE ABOVE. CONTRACTOR TO PROVIDE WRITTEN APPROVAL
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC, ARTICLE 310.15.B.3.a. UNLESS NOTED OTHERWISE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16. (100% OF 75 DEGREE THWN OR THHN).
NOTES:
600 600S3 2 2 1/2" (3)350 KCM N/A 600 600S3 3 2 1/2" (3)250 KCM N/A
600 600F3 2 2 1/2" (3)350 KCM (1)#1 600 600F3 3 2 1/2" (3)250 KCM (1)#2/0 AL
200 200F3 1 2" (3)#3/0 (1)#6 200 200F3 1 2" (3)250 KCM (1)#4 AL
OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
3-WIRE FEEDER SCHEDULE
60 60F2 1 1" (2#)6 (1)#10
50 50F2 1 1" (2#)8 (1)#10
40 40F2 1 1" (2)#8 (1)#10
30 30F2 1 3/4" (2)#10 (1)#10
20 20F2 1 1/2" (2)#12 (1)#12
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER
2-WIRE FEEDER SCHEDULE
REQUIRED FEEDER AMPACITY 133 104
TOTAL DEMAND (W)31991 24891
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 19898.8
REMAINDER AT 40% 24747 9898.8
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 34747
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 11742
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 0.75
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4256.85
REMAINDER AT 25%
3001 - 120000 VA 35% 3591 1256.85
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 6591
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 2091 2091
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/240 UNIT AREA: 697 SQFT
UNIT ONE BED
DWELLING UNIT LOAD CALCULATION
MINIMUM SERVICE SIZE 114730 478
HOUSE LOAD (VA) 43200 43200 180
DWELLING UNIT DEMAND 71530 298
DEMAND FACTOR 0.45
TOTAL DWELLING UNIT LOAD 158956
VA AMPS
TOTAL 4 138988 19968
UNIT ONE BED 4 34747 138988 4992 19968
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE 120/240, 1PH
FEEDER CALCULATION FOR ZIEGLER 4 UNIT
M
M
M
PANEL
"UNIT"
T
F
400/2
400A
400S3
1
2
4 200/2
200F3
10
0
/
3
M
N
G
120/240V, 1PH, 3W
PAD MOUNTED
TRANSFORMER
"BROWN 3-UNIT METER STACK"
400A, 120/240V, 1PH, 3W,
NEMA 3R, 100kAIC
TYPICAL UNIT
PANEL (QTY 3)
ONE-LINE KEY NOTES:
1. "MSB" SHALL BE THREE TIER SERIES RATED AT 100 kAIC. BASIS OF DESIGN IS SCHNEIDER ELECTRIC
(SQUARE D) EZM METER CENTER WITH THREE TIER SERIES RATING, CONSISTING OF TYPE L MAIN FUSE
QOH TENANT CIRCUIT BREAKER, AND TYPE QOY TENANT PANEL CIRCUIT BREAKERS.
2. HOUSE PANEL IS OPTIONAL DEPENDING ON LOCATION AND REQUIREMENTS FOR LIGHTING OR
IRRIGATION LOADS. SITE PLANS TO BE PROVIDED TO COORDINATE REQUIRED LOCATIONS.
3. CIRCUIT BREAKER FOR PV SYSTEM, PROVIDED BY EC. COORDINATE REQUIREMENTS WITH PV
CONTRACTOR.
4. PV CONNECTION BY PV CONTRACTOR.
5. PROVIDE (2)2"C TO ROOF. FEEDERS BY SOLAR CONTRACTOR. FOR FUTURE USE.
6. NON-FUSED, UTILITY DISCONNECT AND PV PRODUCTION METER BY PV CONTRACTOR.
#
1
TO UTILITY PRIMARY
PV PANEL
/ ARRAY
3
4
5
6
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:18 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - BROWN -
3-UNIT
E503
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - BROWN - 3 UNIT
MINIMUM SERVICE SIZE 58946 246
HOUSE LOAD (VA)
DWELLING UNIT DEMAND 58946 246
DEMAND FACTOR 0.45
TOTAL DWELLING UNIT LOAD 130992
VA AMPS
TOTAL 3 116016 14976
UNIT C 1 37882 37882 4992 4992
UNIT B 1 39298 39298 4992 4992
UNIT A 1 38836 38836 4992 4992
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
SERVICE CALCULATION FOR 3-UNIT NO HOUSE PANEL
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
400A 1/0BJ 8BJ 6GEC 1/0GEC 4GEC 1/0GEC 1/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S3' RATHER THAN AN 'F3' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
FROM AHJ TO DOWNSIZE CONDUCTORS.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR PER THE ABOVE. CONTRACTOR TO PROVIDE WRITTEN APPROVAL
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC, ARTICLE 310.15.B.3.a. UNLESS NOTED OTHERWISE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16. (100% OF 75 DEGREE THWN OR THHN).
NOTES:
400 400S3 2 2" (3)#3/0 N/A 400 400S3 2 2 1/2" (3)250 KCM N/A
400 400F3 2 2" (3)#3/0 (1)#3 400 400F3 2 2 1/2" (3)250 KCM (1)#1 AL
200 200F3 1 2" (3)#3/0 (1)#6 200 200F3 1 2" (3)250 KCM (1)#4 AL
OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
3-WIRE FEEDER SCHEDULE
60 60F2 1 1" (2#)6 (1)#10
50 50F2 1 1" (2#)8 (1)#10
40 40F2 1 1" (2)#8 (1)#10
30 30F2 1 3/4" (2)#10 (1)#10
20 20F2 1 1/2" (2)#12 (1)#12
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER
2-WIRE FEEDER SCHEDULE
M
M
M
PANEL
"UNIT"
T
F
600/2
600A
600S3
1
2
4
M
200/2
200F3
PANEL
"HPL1"
60F3
3
M
10
0
/
3
M
N
G
120/240V, 1PH, 3W
PAD MOUNTED
TRANSFORMER
"BROWN 4-UNIT METER STACK"
600A, 120/240V, 1PH, 3W,
NEMA 3R, 100kAIC
TYPICAL UNIT
PANEL (QTY 4)
ONE-LINE KEY NOTES:
1. "MSB" SHALL BE THREE TIER SERIES RATED AT 100 kAIC. BASIS OF DESIGN IS SCHNEIDER ELECTRIC
(SQUARE D) EZM METER CENTER WITH THREE TIER SERIES RATING, CONSISTING OF TYPE L MAIN FUSE
QOH TENANT CIRCUIT BREAKER, AND TYPE QOY TENANT PANEL CIRCUIT BREAKERS.
2. HOUSE PANEL IS OPTIONAL DEPENDING ON LOCATION AND REQUIREMENTS FOR LIGHTING OR
IRRIGATION LOADS. SITE PLANS TO BE PROVIDED TO COORDINATE REQUIRED LOCATIONS.
3. CIRCUIT BREAKER FOR PV SYSTEM, PROVIDED BY EC. COORDINATE REQUIREMENTS WITH PV
CONTRACTOR.
4. PV CONNECTION BY PV CONTRACTOR.
5. PROVIDE (2)2"C TO ROOF. FEEDERS BY SOLAR CONTRACTOR. FOR FUTURE USE.
6. NON-FUSED, UTILITY DISCONNECT AND PV PRODUCTION METER BY PV CONTRACTOR.
#
1
TO UTILITY PRIMARY
2
PV PANEL
/ ARRAY
3
4
5
6
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:19 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - BROWN - 4
UNIT
E504
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - BROWN - 4 UNIT
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
600A 2/0BJ 8BJ 6GEC 2/0GEC 4GEC 2/0GEC 2/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S3' RATHER THAN AN 'F3' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
FROM AHJ TO DOWNSIZE CONDUCTORS.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR PER THE ABOVE. CONTRACTOR TO PROVIDE WRITTEN APPROVAL
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC, ARTICLE 310.15.B.3.a. UNLESS NOTED OTHERWISE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16. (100% OF 75 DEGREE THWN OR THHN).
NOTES:
600 600S3 2 2 1/2" (3)350 KCM N/A 600 600S3 3 2 1/2" (3)250 KCM N/A
600 600F3 2 2 1/2" (3)350 KCM (1)#1 600 600F3 3 2 1/2" (3)250 KCM (1)#2/0 AL
200 200F3 1 2" (3)#3/0 (1)#6 200 200F3 1 2" (3)250 KCM (1)#4 AL
OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
3-WIRE FEEDER SCHEDULE
60 60F2 1 1" (2#)6 (1)#10
50 50F2 1 1" (2#)8 (1)#10
40 40F2 1 1" (2)#8 (1)#10
30 30F2 1 3/4" (2)#10 (1)#10
20 20F2 1 1/2" (2)#12 (1)#12
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER
2-WIRE FEEDER SCHEDULE
MINIMUM SERVICE SIZE 90189 376
HOUSE LOAD (VA) 11520 11520 48
DWELLING UNIT DEMAND 78669 328
DEMAND FACTOR 0.45
TOTAL DWELLING UNIT LOAD 174820
VA AMPS
TOTAL 4 154852 19968
UNIT C 1 37882 37882 4992 4992
UNIT B 1 39298 39298 4992 4992
UNIT A 2 38836 77672 4992 9984
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
SERVICE CALCULATION FOR 4-UNIT
MINIMUM SERVICE SIZE 78669 328
HOUSE LOAD (VA)
DWELLING UNIT DEMAND 78669 328
DEMAND FACTOR 0.45
TOTAL DWELLING UNIT LOAD 174820
VA AMPS
TOTAL 4 154852 19968
UNIT C 1 37882 37882 4992 4992
UNIT B 1 39298 39298 4992 4992
UNIT A 2 38836 77672 4992 9984
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
SERVICE CALCULATION FOR 4-UNIT NO HOUSE PANEL
M
M
M
PANEL
"UNIT"
200/2
T
F
200F3
600S3
1
2
4
M
M
600/2
600A
PANEL
"HPL1"
60F3
3
M
10
0
/
3
M
N
G
TYPICAL UNIT
PANEL (QTY 5)
ONE-LINE KEY NOTES:
1. "MSB" SHALL BE THREE TIER SERIES RATED AT 100 kAIC. BASIS OF DESIGN IS SCHNEIDER ELECTRIC
(SQUARE D) EZM METER CENTER WITH THREE TIER SERIES RATING, CONSISTING OF TYPE L MAIN FUSE
QOH TENANT CIRCUIT BREAKER, AND TYPE QOY TENANT PANEL CIRCUIT BREAKERS.
2. HOUSE PANEL IS OPTIONAL DEPENDING ON LOCATION AND REQUIREMENTS FOR LIGHTING OR
IRRIGATION LOADS. SITE PLANS TO BE PROVIDED TO COORDINATE REQUIRED LOCATIONS.
3. CIRCUIT BREAKER FOR PV SYSTEM, PROVIDED BY EC. COORDINATE REQUIREMENTS WITH PV
CONTRACTOR.
4. PV CONNECTION BY PV CONTRACTOR.
5. PROVIDE (2)2"C TO ROOF. FEEDERS BY SOLAR CONTRACTOR. FOR FUTURE USE.
6. NON-FUSED, UTILITY DISCONNECT AND PV PRODUCTION METER BY PV CONTRACTOR.
#
1
TO UTILITY PRIMARY
120/240V, 1PH, 3W
PAD MOUNTED
TRANSFORMER
"BROWN 5-UNIT METER STACK"
600A, 120/240V, 1PH, 3W,
NEMA 3R, 100kAIC 2
PV PANEL
/ ARRAY
3
4
5
6
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:19 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - BROWN - 5
UNIT
E505
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
600A 2/0BJ 8BJ 6GEC 2/0GEC 4GEC 2/0GEC 2/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S3' RATHER THAN AN 'F3' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
FROM AHJ TO DOWNSIZE CONDUCTORS.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR PER THE ABOVE. CONTRACTOR TO PROVIDE WRITTEN APPROVAL
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC, ARTICLE 310.15.B.3.a. UNLESS NOTED OTHERWISE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16. (100% OF 75 DEGREE THWN OR THHN).
NOTES:
600 600S3 2 2 1/2" (3)350 KCM N/A 600 600S3 3 2 1/2" (3)250 KCM N/A
600 600F3 2 2 1/2" (3)350 KCM (1)#1 600 600F3 3 2 1/2" (3)250 KCM (1)#2/0 AL
200 200F3 1 2" (3)#3/0 (1)#6 200 200F3 1 2" (3)250 KCM (1)#4 AL
OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
3-WIRE FEEDER SCHEDULE
60 60F2 1 1" (2#)6 (1)#10
50 50F2 1 1" (2#)8 (1)#10
40 40F2 1 1" (2)#8 (1)#10
30 30F2 1 3/4" (2)#10 (1)#10
20 20F2 1 1/2" (2)#12 (1)#12
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER
2-WIRE FEEDER SCHEDULE
SCALE: NO SCALE1ELECTRICAL ONE-LINE - BROWN - 5 UNIT
MINIMUM SERVICE SIZE 110120 459
HOUSE LOAD (VA) 11520 11520 48
DWELLING UNIT DEMAND 98600 411
DEMAND FACTOR 0.45
TOTAL DWELLING UNIT LOAD 219110
VA AMPS
TOTAL 5 194150 24960
UNIT C 1 37882 37882 4992 4992
UNIT B 2 39298 78596 4992 9984
UNIT A 2 38836 77672 4992 9984
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
SERVICE CALCULATION FOR 5-UNIT
MINIMUM SERVICE SIZE 98600 411
HOUSE LOAD (VA)
DWELLING UNIT DEMAND 98600 411
DEMAND FACTOR 0.45
TOTAL DWELLING UNIT LOAD 219110
VA AMPS
TOTAL 5 194150 24960
UNIT C 1 37882 37882 4992 4992
UNIT B 2 39298 78596 4992 9984
UNIT A 2 38836 77672 4992 9984
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
SERVICE CALCULATION FOR 5-UNIT NO HOUSE PANEL
M
M
M
PANEL
"UNIT"
T
F
800S3
1
2
4
M
M
M
800/2
800A
200/2
200F3
PANEL
"HPL1"
60F3
3
M
600S3
10
0
/
3
M
N
G
TYPICAL UNIT
PANEL (QTY 6)
ONE-LINE KEY NOTES:
1. "MSB" SHALL BE THREE TIER SERIES RATED AT 100 kAIC. BASIS OF DESIGN IS SCHNEIDER ELECTRIC
(SQUARE D) EZM METER CENTER WITH THREE TIER SERIES RATING, CONSISTING OF TYPE L MAIN FUSE
QOH TENANT CIRCUIT BREAKER, AND TYPE QOY TENANT PANEL CIRCUIT BREAKERS.
2. HOUSE PANEL IS OPTIONAL DEPENDING ON LOCATION AND REQUIREMENTS FOR LIGHTING OR
IRRIGATION LOADS. SITE PLANS TO BE PROVIDED TO COORDINATE REQUIRED LOCATIONS. MAIN FUSES
SHALL ALSO BE REDUCED TO 600A WITHOUT A HOUSE PANEL.
3. CIRCUIT BREAKER FOR PV SYSTEM, PROVIDED BY EC. COORDINATE REQUIREMENTS WITH PV
CONTRACTOR.
4. PV CONNECTION BY PV CONTRACTOR.
5. PROVIDE (2)2"C TO ROOF. FEEDERS BY SOLAR CONTRACTOR. FOR FUTURE USE.
6. NON-FUSED, UTILITY DISCONNECT AND PV PRODUCTION METER BY PV CONTRACTOR.
#
TO UTILITY PRIMARY
1
120/240V, 1PH, 3W
PAD MOUNTED
TRANSFORMER
"BROWN 6-UNIT METER STACK"
800A, 120/240V, 1PH, 3W,
NEMA 3R, 100kAIC 2
IF NO HOUSE PANEL
PV PANEL
/ ARRAY
3
4
5
6
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:20 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - BROWN - 6
UNIT
E506
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - BROWN - 6 UNIT
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
800A 2/0BJ 8BJ 6GEC 2/0GEC 4GEC 2/0GEC 2/0GEC -
600A 2/0BJ 8BJ 6GEC 2/0GEC 4GEC 2/0GEC 2/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S3' RATHER THAN AN 'F3' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
FROM AHJ TO DOWNSIZE CONDUCTORS.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR PER THE ABOVE. CONTRACTOR TO PROVIDE WRITTEN APPROVAL
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC, ARTICLE 310.15.B.3.a. UNLESS NOTED OTHERWISE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16. (100% OF 75 DEGREE THWN OR THHN).
NOTES:
800 800S3 3 2 1/2" (3)300 KCM N/A 800 800S3 4 2 1/2" (3)250 KCM N/A
800 800F3 3 2 1/2" (3)300 KCM (1)#1/0 800 800F3 4 2 1/2" (3)250 KCM (1)#3/0 AL
600 600S3 2 2 1/2" (3)350 KCM N/A 600 600S3 3 2 1/2" (3)250 KCM N/A
600 600F3 2 2 1/2" (3)350 KCM (1)#1 600 600F3 3 2 1/2" (3)250 KCM (1)#2/0 AL
200 200F3 1 2" (3)#3/0 (1)#6 200 200F3 1 2" (3)250 KCM (1)#4 AL
OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
3-WIRE FEEDER SCHEDULE
60 60F2 1 1" (2#)6 (1)#10
50 50F2 1 1" (2#)8 (1)#10
40 40F2 1 1" (2)#8 (1)#10
30 30F2 1 3/4" (2)#10 (1)#10
20 20F2 1 1/2" (2)#12 (1)#12
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER
2-WIRE FEEDER SCHEDULE
MINIMUM SERVICE SIZE 126793 528
HOUSE LOAD (VA) 11520 11520 48
DWELLING UNIT DEMAND 115273 480
DEMAND FACTOR 0.44
TOTAL DWELLING UNIT LOAD 261984
VA AMPS
TOTAL 6 232032 29952
UNIT C 2 37882 75764 4992 9984
UNIT B 2 39298 78596 4992 9984
UNIT A 2 38836 77672 4992 9984
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
SERVICE CALCULATION FOR 6-UNIT
MINIMUM SERVICE SIZE 115273 480
HOUSE LOAD (VA)
DWELLING UNIT DEMAND 115273 480
DEMAND FACTOR 0.44
TOTAL DWELLING UNIT LOAD 261984
VA AMPS
TOTAL 6 232032 29952
UNIT C 2 37882 75764 4992 9984
UNIT B 2 39298 78596 4992 9984
UNIT A 2 38836 77672 4992 9984
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
SERVICE CALCULATION FOR 6-UNIT NO HOUSE PANEL
M
M
M
PANEL
"UNIT"
PANEL
"HPL1"
T
F
60F3
600S3
1
2
3
4
M
M
M
200/2
200F3
600/2
600A
10
0
/
3
M
N
G
TYPICAL UNIT
PANEL (QTY 5)
ONE-LINE KEY NOTES:
1. "MSB" SHALL BE THREE TIER SERIES RATED AT 100 kAIC. BASIS OF DESIGN IS SCHNEIDER ELECTRIC
(SQUARE D) EZM METER CENTER WITH THREE TIER SERIES RATING, CONSISTING OF TYPE L MAIN FUSE
QOH TENANT CIRCUIT BREAKER, AND TYPE QOY TENANT PANEL CIRCUIT BREAKERS.
2. HOUSE PANEL IS OPTIONAL DEPENDING ON LOCATION AND REQUIREMENTS FOR LIGHTING OR
IRRIGATION LOADS. SITE PLANS TO BE PROVIDED TO COORDINATE REQUIRED LOCATIONS.
3. CIRCUIT BREAKER FOR PV SYSTEM, PROVIDED BY EC. COORDINATE REQUIREMENTS WITH PV
CONTRACTOR.
4. PV CONNECTION BY PV CONTRACTOR.
5. PROVIDE (2)2"C TO ROOF. FEEDERS BY SOLAR CONTRACTOR. FOR FUTURE USE.
6. NON-FUSED, UTILITY DISCONNECT AND PV PRODUCTION METER BY PV CONTRACTOR.
#
TO UTILITY PRIMARY
1
2
120/240V, 1PH, 3W
PAD MOUNTED
TRANSFORMER
"3STRY, 5-UNIT METER STACK"
600A, 120/240V, 1PH, 3W,
NEMA 3R, 100kAIC
PV PANEL
/ ARRAY
3
4
5
6
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:20 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - 3 STORY
WALK-UP - 5 UNIT
E507
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
600A 2/0BJ 8BJ 6GEC 2/0GEC 4GEC 2/0GEC 2/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S3' RATHER THAN AN 'F3' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
FROM AHJ TO DOWNSIZE CONDUCTORS.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR PER THE ABOVE. CONTRACTOR TO PROVIDE WRITTEN APPROVAL
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC, ARTICLE 310.15.B.3.a. UNLESS NOTED OTHERWISE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16. (100% OF 75 DEGREE THWN OR THHN).
NOTES:
600 600S3 2 2 1/2" (3)350 KCM N/A 600 600S3 3 2 1/2" (3)250 KCM N/A
600 600F3 2 2 1/2" (3)350 KCM (1)#1 600 600F3 3 2 1/2" (3)250 KCM (1)#2/0 AL
200 200F3 1 2" (3)#3/0 (1)#6 200 200F3 1 2" (3)250 KCM (1)#4 AL
OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
3-WIRE FEEDER SCHEDULE
60 60F2 1 1" (2#)6 (1)#10
50 50F2 1 1" (2#)8 (1)#10
40 40F2 1 1" (2)#8 (1)#10
30 30F2 1 3/4" (2)#10 (1)#10
20 20F2 1 1/2" (2)#12 (1)#12
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER
2-WIRE FEEDER SCHEDULE
SCALE: NO SCALE1ELECTRICAL ONE-LINE - 3 STORY TOWNHOME - 5 UNIT
MINIMUM SERVICE SIZE 109064 454
HOUSE LOAD (VA) 11520 11520 48
DWELLING UNIT DEMAND 97544 406
DEMAND FACTOR 0.45
TOTAL DWELLING UNIT LOAD 216764
VA AMPS
TOTAL 5 191804 24960
UNIT D 1 38584 38584 4992 4992
UNIT C 1 38140 38140 4992 4992
UNIT B 2 38140 76280 4992 9984
UNIT A 1 38800 38800 4992 4992
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
FEEDER CALCULATION FOR 5 UNIT
MINIMUM SERVICE SIZE 97544 406
HOUSE LOAD (VA)
DWELLING UNIT DEMAND 97544 406
DEMAND FACTOR 0.45
TOTAL DWELLING UNIT LOAD 216764
VA AMPS
TOTAL 5 191804 24960
UNIT D 1 38584 38584 4992 4992
UNIT C 1 38140 38140 4992 4992
UNIT B 2 38140 76280 4992 9984
UNIT A 1 38800 38800 4992 4992
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
FEEDER CALCULATION FOR 5 UNIT NO HOUSE PANEL
M
M
M
PANEL
"UNIT"
PANEL
"HPL1"
T
F
60F4
1
2
3
4
M
M
M
M
60F3
800S3
200/2
200F3
800/2
800A
600S3
10
0
/
3
M
N
G
TYPICAL UNIT
PANEL (QTY 6)
ONE-LINE KEY NOTES:
1. "MSB" SHALL BE THREE TIER SERIES RATED AT 100 kAIC. BASIS OF DESIGN IS SCHNEIDER ELECTRIC
(SQUARE D) EZM METER CENTER WITH THREE TIER SERIES RATING, CONSISTING OF TYPE L MAIN FUSE
QOH TENANT CIRCUIT BREAKER, AND TYPE QOY TENANT PANEL CIRCUIT BREAKERS.
2. HOUSE PANEL IS OPTIONAL DEPENDING ON LOCATION AND REQUIREMENTS FOR LIGHTING OR
IRRIGATION LOADS. SITE PLANS TO BE PROVIDED TO COORDINATE REQUIRED LOCATIONS. MAIN
FUSES SHALL ALSO BE REDUCED TO 600A WITHOUT A HOUSE PANEL.
3. CIRCUIT BREAKER FOR PV SYSTEM, PROVIDED BY EC. COORDINATE REQUIREMENTS WITH PV
CONTRACTOR.
4. PV CONNECTION BY PV CONTRACTOR.
5. PROVIDE (2)2"C TO ROOF. FEEDERS BY SOLAR CONTRACTOR. FOR FUTURE USE.
6. NON-FUSED, UTILITY DISCONNECT AND PV PRODUCTION METER BY PV CONTRACTOR.
#
TO UTILITY PRIMARY
1
2
120/240V, 1PH, 3W
PAD MOUNTED
TRANSFORMER
"3STRY, 6-UNIT METER STACK"
800A, 120/240V, 1PH, 3W,
NEMA 3R, 100kAIC
IF NO HOUSE PANEL
PV PANEL
/ ARRAY
3
4
5
6
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:21 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - 3 STORY
WALK-UP - 6 UNIT
E508
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
MINIMUM SERVICE SIZE 125874 524
HOUSE LOAD (VA) 11520 11520 48
DWELLING UNIT DEMAND 114354 476
DEMAND FACTOR 0.44
TOTAL DWELLING UNIT LOAD 259896
VA AMPS
TOTAL 6 229944 29952
UNIT D 1 38584 38584 4992 4992
UNIT C 2 38140 76280 4992 9984
UNIT B 2 38140 76280 4992 9984
UNIT A 1 38800 38800 4992 4992
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
FEEDER CALCULATION FOR 6 UNIT
SCALE: NO SCALE1ELECTRICAL ONE-LINE - 3 STORY TOWNHOME - 6 UNIT
MINIMUM SERVICE SIZE 114354 476
HOUSE LOAD (VA)
DWELLING UNIT DEMAND 114354 476
DEMAND FACTOR 0.44
TOTAL DWELLING UNIT LOAD 259896
VA AMPS
TOTAL 6 229944 29952
UNIT D 1 38584 38584 4992 4992
UNIT C 2 38140 76280 4992 9984
UNIT B 2 38140 76280 4992 9984
UNIT A 1 38800 38800 4992 4992
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
FEEDER CALCULATION FOR 6 UNIT NO HOUSE PANEL
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
800A 2/0BJ 8BJ 6GEC 2/0GEC 4GEC 2/0GEC 2/0GEC -
600A 2/0BJ 8BJ 6GEC 2/0GEC 4GEC 2/0GEC 2/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S3' RATHER THAN AN 'F3' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
FROM AHJ TO DOWNSIZE CONDUCTORS.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR PER THE ABOVE. CONTRACTOR TO PROVIDE WRITTEN APPROVAL
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC, ARTICLE 310.15.B.3.a. UNLESS NOTED OTHERWISE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16. (100% OF 75 DEGREE THWN OR THHN).
NOTES:
800 800S3 3 2 1/2" (3)300 KCM N/A 800 800S3 4 2 1/2" (3)250 KCM N/A
800 800F3 3 2 1/2" (3)300 KCM (1)#1/0 800 800F3 4 2 1/2" (3)250 KCM (1)#3/0 AL
600 600S3 2 2 1/2" (3)350 KCM N/A 600 600S3 3 2 1/2" (3)250 KCM N/A
600 600F3 2 2 1/2" (3)350 KCM (1)#1 600 600F3 3 2 1/2" (3)250 KCM (1)#2/0 AL
200 200F3 1 2" (3)#3/0 (1)#6 200 200F3 1 2" (3)250 KCM (1)#4 AL
OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
3-WIRE FEEDER SCHEDULE
60 60F2 1 1" (2#)6 (1)#10
50 50F2 1 1" (2#)8 (1)#10
40 40F2 1 1" (2)#8 (1)#10
30 30F2 1 3/4" (2)#10 (1)#10
20 20F2 1 1/2" (2)#12 (1)#12
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER
2-WIRE FEEDER SCHEDULE
M
M
M
PANEL
"UNIT"
PANEL
"HPL1"
T
F
1
2
3
4
M
M
M
M
M
M 60F3
800S3
200/2
200F3
800/2
800A
10
0
/
3
M
N
G
TYPICAL UNIT
PANEL (QTY 8)
ONE-LINE KEY NOTES:
1. "MSB" SHALL BE THREE TIER SERIES RATED AT 100 kAIC. BASIS OF DESIGN IS SCHNEIDER ELECTRIC
(SQUARE D) EZM METER CENTER WITH THREE TIER SERIES RATING, CONSISTING OF TYPE L MAIN FUSE
QOH TENANT CIRCUIT BREAKER, AND TYPE QOY TENANT PANEL CIRCUIT BREAKERS.
2. HOUSE PANEL IS OPTIONAL DEPENDING ON LOCATION AND REQUIREMENTS FOR LIGHTING OR
IRRIGATION LOADS. SITE PLANS TO BE PROVIDED TO COORDINATE REQUIRED LOCATIONS.
3. CIRCUIT BREAKER FOR PV SYSTEM, PROVIDED BY EC. COORDINATE REQUIREMENTS WITH PV
CONTRACTOR.
4. PV CONNECTION BY PV CONTRACTOR.
5. PROVIDE (2)2"C TO ROOF. FEEDERS BY SOLAR CONTRACTOR. FOR FUTURE USE.
6. NON-FUSED, UTILITY DISCONNECT AND PV PRODUCTION METER BY PV CONTRACTOR.
#
TO UTILITY PRIMARY
1
2
120/240V, 1PH, 3W
PAD MOUNTED
TRANSFORMER
"3STRY, 8-UNIT METER STACK"
800A, 100% RATED,
120/240V, 1PH, 3W,
NEMA 3R, 100kAIC
PV PANEL
/ ARRAY
3
4
5
6
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:21 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - 3 STORY
WALK-UP - 8 UNIT
E509
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S3' RATHER THAN AN 'F3' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
FROM AHJ TO DOWNSIZE CONDUCTORS.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR PER THE ABOVE. CONTRACTOR TO PROVIDE WRITTEN APPROVAL
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC, ARTICLE 310.15.B.3.a. UNLESS NOTED OTHERWISE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16. (100% OF 75 DEGREE THWN OR THHN).
NOTES:
800 800S3 3 2 1/2" (3)300 KCM N/A 800 800S3 4 2 1/2" (3)250 KCM N/A
800 800F3 3 2 1/2" (3)300 KCM (1)#1/0 800 800F3 4 2 1/2" (3)250 KCM (1)#3/0 AL
200 200F3 1 2" (3)#3/0 (1)#6 200 200F3 1 2" (3)250 KCM (1)#4 AL
OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
3-WIRE FEEDER SCHEDULE
60 60F2 1 1" (2#)6 (1)#10
50 50F2 1 1" (2#)8 (1)#10
40 40F2 1 1" (2)#8 (1)#10
30 30F2 1 3/4" (2)#10 (1)#10
20 20F2 1 1/2" (2)#12 (1)#12
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER
2-WIRE FEEDER SCHEDULE
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
800A 2/0BJ 8BJ 6GEC 2/0GEC 4GEC 2/0GEC 2/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
SCALE: NO SCALE1ELECTRICAL ONE-LINE - 3 STORY TOWNHOME - 8 UNIT
MINIMUM SERVICE SIZE 160844 670
HOUSE LOAD (VA) 11520 11520 48
DWELLING UNIT DEMAND 149324 622
DEMAND FACTOR 0.43
TOTAL DWELLING UNIT LOAD 347264
VA AMPS
TOTAL 8 307328 39936
UNIT D 2 38584 77168 4992 9984
UNIT C 2 38140 76280 4992 9984
UNIT B 2 38140 76280 4992 9984
UNIT A 2 38800 77600 4992 9984
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
FEEDER CALCULATION FOR 8 UNIT
MINIMUM SERVICE SIZE 149324 622
HOUSE LOAD (VA)
DWELLING UNIT DEMAND 149324 622
DEMAND FACTOR 0.43
TOTAL DWELLING UNIT LOAD 347264
VA AMPS
TOTAL 8 307328 39936
UNIT D 2 38584 77168 4992 9984
UNIT C 2 38140 76280 4992 9984
UNIT B 2 38140 76280 4992 9984
UNIT A 2 38800 77600 4992 9984
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
FEEDER CALCULATION FOR 8 UNIT NO HOUSE PANEL
M
M
M
M
PANEL
"UNIT"
125/2
PANEL
"HPL1"
T
F
1
2
3
4
M
M
M
M
M
M
60F3
200/2
200F3
800S3
800/2
800A
10
0
/
3
M
N
G
TYPICAL UNIT
PANEL (QTY 9)
ONE-LINE KEY NOTES:
1. "MSB" SHALL BE THREE TIER SERIES RATED AT 100 kAIC. BASIS OF DESIGN IS SCHNEIDER ELECTRIC
(SQUARE D) EZM METER CENTER WITH THREE TIER SERIES RATING, CONSISTING OF TYPE L MAIN FUSE
QOH TENANT CIRCUIT BREAKER, AND TYPE QOY TENANT PANEL CIRCUIT BREAKERS.
2. HOUSE PANEL IS OPTIONAL DEPENDING ON LOCATION AND REQUIREMENTS FOR LIGHTING OR
IRRIGATION LOADS. SITE PLANS TO BE PROVIDED TO COORDINATE REQUIRED LOCATIONS.
3. CIRCUIT BREAKER FOR PV SYSTEM, PROVIDED BY EC. COORDINATE REQUIREMENTS WITH PV
CONTRACTOR.
4. PV CONNECTION BY PV CONTRACTOR.
5. PROVIDE (2)2"C TO ROOF. FEEDERS BY SOLAR CONTRACTOR. FOR FUTURE USE.
6. NON-FUSED, UTILITY DISCONNECT AND PV PRODUCTION METER BY PV CONTRACTOR.
#
TO UTILITY PRIMARY
1
2
120/240V, 1PH, 3W
PAD MOUNTED
TRANSFORMER
"3STRY, 9-UNIT METER STACK"
800A, 100% RATED,
120/240V, 1PH, 3W,
NEMA 3R, 100kAIC
PV PANEL
/ ARRAY
3
4
5
6
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:22 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - 3 STORY
WALK-UP - 9 UNIT
E510
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S3' RATHER THAN AN 'F3' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
FROM AHJ TO DOWNSIZE CONDUCTORS.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR PER THE ABOVE. CONTRACTOR TO PROVIDE WRITTEN APPROVAL
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC, ARTICLE 310.15.B.3.a. UNLESS NOTED OTHERWISE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16. (100% OF 75 DEGREE THWN OR THHN).
NOTES:
800 800S3 3 2 1/2" (3)300 KCM N/A 800 800S3 4 2 1/2" (3)250 KCM N/A
800 800F3 3 2 1/2" (3)300 KCM (1)#1/0 800 800F3 4 2 1/2" (3)250 KCM (1)#3/0 AL
200 200F3 1 2" (3)#3/0 (1)#6 200 200F3 1 2" (3)250 KCM (1)#4 AL
OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
3-WIRE FEEDER SCHEDULE
60 60F2 1 1" (2#)6 (1)#10
50 50F2 1 1" (2#)8 (1)#10
40 40F2 1 1" (2)#8 (1)#10
30 30F2 1 3/4" (2)#10 (1)#10
20 20F2 1 1/2" (2)#12 (1)#12
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER
2-WIRE FEEDER SCHEDULE
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
800A 2/0BJ 8BJ 6GEC 2/0GEC 4GEC 2/0GEC 2/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
SCALE: NO SCALE1ELECTRICAL ONE-LINE - 3 STORY TOWNHOME - 9 UNIT
MINIMUM SERVICE SIZE 179390 747
HOUSE LOAD (VA) 11520 11520 48
DWELLING UNIT DEMAND 167870 699
DEMAND FACTOR 0.43
TOTAL DWELLING UNIT LOAD 390396
VA AMPS
TOTAL 9 345468 44928
UNIT D 2 38584 77168 4992 9984
UNIT C 3 38140 114420 4992 14976
UNIT B 2 38140 76280 4992 9984
UNIT A 2 38800 77600 4992 9984
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
FEEDER CALCULATION FOR 9 UNIT
MINIMUM SERVICE SIZE 167870 699
HOUSE LOAD (VA)
DWELLING UNIT DEMAND 167870 699
DEMAND FACTOR 0.43
TOTAL DWELLING UNIT LOAD 390396
VA AMPS
TOTAL 9 345468 44928
UNIT D 2 38584 77168 4992 9984
UNIT C 3 38140 114420 4992 14976
UNIT B 2 38140 76280 4992 9984
UNIT A 2 38800 77600 4992 9984
QTY PER UNIT TOTAL PER UNIT TOTAL
GENERAL LOAD HEATING AND A/C
SYSTEM VOLTAGE: 120/240, 1PH
FEEDER CALCULATION FOR 9 UNIT NO HOUSE PANEL
PANEL
"LPL1"
T
F
400S4
M
400/3
300AF
400F4
1
2
208/120V, 3PH, 4W, UTILITY
TRANSFORMER
TO UTILITY PRIMARY
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:22 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - CLUBHOUSE
E511
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - CLUBHOUSE
LMOTOR 0 1.25 0
MOTOR 0 1 0
NONCONC. 0 0 0 13572 C-PHASE LOAD
MISC 0 1 0 17007 B-PHASE LOAD
KITCHEN 11900 0.65 7735 13513 A-PHASE LOAD
EQUIP 23526 1 23526 112 MIN. FEEDER AMPS
LIGHTING 826 1.25 1033 40134 VA (W/ CONTINUOUS)
RECEPT 7840 NEC 7840 40831 50.4% SPARE
LOAD TYPE LOAD IN VA FACTOR DIV LOAD 39927 TOTAL VA
SPARE 20/1 59 C 60 20/1 SPARE
SPARE 20/1 57 B 58 20/1 SPARE
SPARE 20/1 55 A 56 20/1 SPARE
SPARE 20/1 53 C 54 20/1 SPARE
SPARE 20/1 51 B 52 20/1 SPARE
SPARE 20/1 49 A 50 20/1 SPARE
SPARE 20/1 47 C 48 20/1 SPARE
SPARE 20/1 45 B 46 20/1 SPARE
SPARE 20/1 43 A 44 20/1 SPARE
SPARE 20/1 41 C 42 20/1 SPARE
SPARE 20/1 39 B 40 20/1 1200 R-FITNESS EQUIPMENT
SPARE 20/1 37 A 38 20/1 1200 R-FITNESS EQUIPMENT
SPARE 20/1 35 C 36 20/1 1200 R-FITNESS EQUIPMENT
R-FITNESS FANS 1080 20/1 33 B 34 20/1 1200 R-FITNESS EQUIPMENT
R-FITNESS RECEPT. 900 20/1 31 A 32 20/1 1200 R-FITNESS EQUIPMENT
E-FIREPLACE 500 20/1 29 C 30 20/1 1200 R-FITNESS EQUIPMENT
E-FIREPLACE 500 20/1 27 B 28 * 4008 *
R-EXTERIOR RECEPT. 900 20/1 25 A 26 50/2 4008 E-CU-1
R-HALLWAY RECEPT. 1260 20/1 23 C 24 20/1 400 E-CP-1
R-CORNER COUNTER 540 20/1 21 B 22 20/1 1524 E-FUR-1
K-REFRIGERATOR 1000 GFCI 20/1 19 A 20 20/1 372 E-GWH-1
* 4000 * *17 C 18 20/1 1500 *
K-RANGE 4000 GFCI 50/2 15 B 16 20/1 1500 E-EWH-2
K-MICROWAVE 1200 GFCI 20/1 13 A 14 20/1 1500 *
K-DISHWASHER 1200 GFCI 20/1 11 C 12 20/1 1500 E-EWH-1
K-DISPOSAL 500 GFCI 20/1 9 B 10 20/1 7 E-EF-2
R-ISLAND COUNTER 540 20/1 7 A 8 20/1 7 E-EF-1
R-ISLAND COUNTER 720 20/1 5 C 6 20/1 92 L-EXTERIOR LIGHTING
R-KITCHEN COUNTER 360 20/1 3 B 4 20/1 588 L-FIT. & KITCH. & GREAT ROOM
R-MECH & RR 540 20/1 1 A 2 20/1 146 L-BACK OF HOUSE & RR
DESCRIPTION LOAD VA REMARKS O/C CKT # PH CKT # O/C REMARKS LOAD VA DESCRIPTION
60 POLES ONE SECTION
18000 MINIMUM AIC RATING FULLY RATED
225 AMP MLO 100% NEUTRAL
208/120V 3 PHASE 4 WIRE W/ GND BAR SURFACE MOUNTED
PANELCH
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S3' RATHER THAN AN 'F3' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
FROM AHJ TO DOWNSIZE CONDUCTORS.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR PER THE ABOVE. CONTRACTOR TO PROVIDE WRITTEN APPROVAL
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC, ARTICLE 310.15.B.3.a. UNLESS NOTED OTHERWISE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16. (100% OF 75 DEGREE THWN OR THHN).
NOTES:
400 400S3 2 2" (3)#3/0 N/A 400 400S3 2 2 1/2" (3)250 KCM N/A
400 400F3 2 2" (3)#3/0 (1)#3 400 400F3 2 2 1/2" (3)250 KCM (1)#1 AL
100 100F3 1 1 1/2" (3)#1 (1)#6 100 100F3 1 1 1/2" (3)#1/0 (1)#4 AL
90 90F3 1 1 1/4" (3)#2 (1)#8
80 80F3 1 1 1/4" (3)#3 (1)#8
70 70F3 1 1 1/4" (3)#4 (1)#8
60 60S3 1 1 1/4" (3)#6 N/A
60 60F3 1 1 1/4" (3)#6 (1)#8
50 50F3 1 1" (3)#8 (1)#10
40 40F3 1 1" (3#)8 (1)#10
30 30F3 1 3/4" (3)#10 (1)#10
20 20F3 1 1/2" (3)#12 (1)#12
OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
CALLOUT SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
3-WIRE FEEDER SCHEDULE
60 60F2 1 1" (2#)6 (1)#10
50 50F2 1 1" (2#)8 (1)#10
40 40F2 1 1" (2)#8 (1)#10
30 30F2 1 3/4" (2)#10 (1)#10
20 20F2 1 1/2" (2)#12 (1)#12
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER
2-WIRE FEEDER SCHEDULE
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
225A 2BJ 8BJ 6GEC 2GEC 4GEC 2GEC 2GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
T
F
600S4
M
600F4
1
2
MDP
DAYCARE
PANEL
"A"
PANEL
"B"
225F4
225F4
3 4
208/120V, 3PH, 4W, UTILITY
TRANSFORMER
TO UTILITY PRIMARY
DISCONNECT/CT
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:23 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - DAYCARE
E512
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - DAYCARE
428 MIN. FEEDER AMPS
154020 TOTAL VA (W/ CONTINUOUS)
61884 29% SPARE AVAILABLE
154020 TOTAL VA
LMOTOR 0 1.25 0
MOTOR 0 1 0
NONCONC. 0 0 0
MISC 112040 1 112040
KITCHEN 0 0.65 0
EQUIP 41980 1 41980
LIGHTING 0 1.25 0
RECEPT 0 NEC 0
LOAD TYPE LOAD IN VA FACTOR DIVERSIFIED LOAD
30/3 SPD
12 4660 E-CU-10
11 4000 E-CU-9
10 4660 E-CU-8
9 4660 E-CU-7
8 4000 E-CU-6
7 4000 E-CU-5
6 4000 E-CU-4
5 4000 E-CU-3
4 4000 E-CU-2
3 4000 E-CU-1
2 225/3 66400 PANEL B
1 225/3 45640 PANEL A
CKT # O/C REMARKS LOAD VA DESCRIPTION
BREAKER DISTRIBUTION 100% NEUTRAL
XXXXX MINIMUM AIC RATING FULLY RATED
600 AMP MCB INTEGRAL SPD
208/120V 3 PHASE 4 WIRE W/ GND BAR 80% MAIN
DISTRIBUTION PANEL MDP-DAYCARE
LMOTOR 0 1.25 0
MOTOR 0 1 0
NONCONC. 0 0 0 14353 C-PHASE LOAD
MISC 0 1 0 15634 B-PHASE LOAD
KITCHEN 0 0.65 0 12938 A-PHASE LOAD
EQUIP 13795 1 13795 106 MIN. FEEDER AMPS
LIGHTING 8560 1.25 10700 38311 VA (W/ CONTINUOUS)
RECEPT 20570 NEC 15285 42653 52.7% SPARE
LOAD TYPE LOAD IN VA FACTOR DIV LOAD 37640 TOTAL VA
SECURITY PANEL 250 20/1 59 C 60 * 600 *
INTERCOM SYSTEM 250 20/1 57 B 58 15/2 600 E-ERV-4
E-RECEPTION FRIDGE 750 GFCI 20/1 55 A 56 SPARE
R-RECEPTION 1080 20/1 53 C 54 20/1 GFCI 1200 E-COMMERCIAL DISHWASHER
R-POFFICE 900 20/1 51 B 52 * 2300 *
E-ELECTRIC WATER COOLER 500 GFCI 20/1 49 A 50 30/2 GFCI 2300 E-COMMERCIAL OVEN
R-RESOURCE 540 20/1 47 C 48 20/1 360 R-SECURITY RACK
R-TELEPHONE BOARD 360 20/1 45 B 46 20/1 540 R-KITCHEN RECEPTS
E-IRRIGATION CONTROLLER 100 20/1 43 A 44 20/1 540 R-KITCHEN RECEPTS
R-LAUNDRY/SPRINKLER RM 540 20/1 41 C 42 20/1 1150 L-SITE LIGHTING
E-FRIDGE 775 GFCI 20/1 39 B 40 20/1 481 L-CLASSROOM/TOILET
L-CLASSROOM LTG 750 20/1 37 A 38 20/1 316 L-GALLEY/STOR.
E-FRIDGE 770 GFCI 20/1 35 C 36 20/1 738 L-CLASSRM/OFFICE/TOILET
R-CLASSROOM RECEPT 775 20/1 33 B 34 20/1 720 R-CLASSROOM RECEPT
R-GALLERY/ELEC. 1080 20/1 31 A 32 20/1 540 R-CLASSROOM RECEPT
R-CLASSROOM RECEPT 1125 20/1 29 C 30 20/1 900 R-CLASSROOM RECEPT
SPARE 720 20/1 27 B 28 20/1 720 R-OFFICE
L-CLASSROOM LTG 950 20/1 25 A 26 20/1 500 E-ELECTRIC WATER COOLER
L-CLASSROOM LTG 950 20/1 23 C 24 20/1 540 R-CLASSROOM RECEPT
L-CLASSROOM LTG 468 20/1 21 B 22 20/1 720 R-CLASSROOM RECEPT
L-CLASSROOM LTG 525 20/1 19 A 20 20/1 540 R-STAFF 205
L-CLASSROOM LTG 682 20/1 17 C 18 20/1 900 R-CLASSROOM RECEPT
L-CLASSROOM LTG 986 20/1 15 B 16 20/1 720 R-CLASSROOM RECEPT
SPARE 20/1 13 A 14 20/1 720 R-CLASSROOM RECEPT
L-CLASSROOM LTG 772 20/1 11 C 12 20/1 540 R-CLASSROOM RECEPT
L-CLASSROOM LTG 784 20/1 9 B 10 20/1 GFCI 1080 R-VESTABULE RECEPTS
L-GALLERY/VESTIBULE LTG 490 20/1 7 A 8 20/1 720 R-CLASSROOM RECEPT
L-CONF RM/MECH/ELEC/STAIR 216 20/1 5 C 6 20/1 GFCI 500 E-ICE MAKER
L-CLASSROOM LTG 535 20/1 3 B 4 20/1 GFCI 1200 E-FREEZER
L-CLASSROOM LTG 417 20/1 1 A 2 20/1 GFCI 1200 E- FRIDGE
DESCRIPTION LOAD VA REMARKS O/C CKT # PH CKT # O/C REMARKS LOAD VA DESCRIPTION
60 POLES ONE SECTION
10000 MINIMUM AIC RATING FULLY RATED
225 AMP MLO 100% NEUTRAL
208/120V 3 PHASE 4 WIRE W/ GND BAR SURFACE MOUNTED
PANEL A
LMOTOR 0 1.25 0
MOTOR 0 1 0
NONCONC. 0 0 0 13010 C-PHASE LOAD
MISC 0 1 0 12960 B-PHASE LOAD
KITCHEN 0 0.65 0 16665 A-PHASE LOAD
EQUIP 42635 1 42635 118 MIN. FEEDER AMPS
LIGHTING 0 1.25 0 42635 VA (W/ CONTINUOUS)
RECEPT 0 NEC 0 38329 47.3% SPARE
LOAD TYPE LOAD IN VA FACTOR DIV LOAD 42635 TOTAL VA
E-CP-2 60 20/1 41 C 42 20/1 SPARE
E-CP-1 60 20/1 39 B 40 * 600 *
E-SP-1 500 20/1 37 A 38 15/2 600 E-ERV-3
E-WH-2 600 20/1 35 C 36 * 600 *
E-WH-1 600 20/1 33 B 34 15/2 600 E-ERV-2
E-EF-2 165 20/1 31 A 32 * 600 *
E-EF-1 250 20/1 29 C 30 15/2 600 E-ERV-1
* 1100 *27 B 28 15/1 SPARE
E-EUH-2 1100 GFCI 30/2 25 A 26 15/1 SPARE
* 1500 *23 C 24 15/1 SPARE
E-EUH-1 1500 GFCI 30/2 21 B 22 15/1 SPARE
* 1600 *19 A 20 15/1 1700 E-FURN-10
E-DRYER 1600 GFCI 30/2 17 C 18 15/1 1300 E-FURN-9
E-WASHER 1000 GFCI 20/1 15 B 16 15/1 1700 E-FURN-8
* 1600 *13 A 14 15/1 1700 E-FURN-7
E-DRYER 1600 GFCI 30/2 11 C 12 15/1 1300 E-FURN-6
E-WASHER 1000 GFCI 20/1 9 B 10 15/1 1300 E-FURN-5
* 2300 *7 A 8 15/1 1300 E-FURN-4
E-COMMERCIAL OVEN 2300 GFCI 30/2 5 C 6 15/1 1300 E-FURN-3
* 2200 *3 B 4 15/1 1300 E-FURN-2
E-COMMERCIAL MICROWAVE 2200 GFCI 30/2 1 A 2 15/1 1300 E-FURN-1
DESCRIPTION LOAD VA REMARKS O/C CKT # PH CKT # O/C REMARKS LOAD VA DESCRIPTION
42 POLES ONE SECTION
10000 MINIMUM AIC RATING FULLY RATED
225 AMP MLO 100% NEUTRAL
208/120V 3 PHASE 4 WIRE W/ GND BAR SURFACE MOUNTED
PANEL B
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
600A 2/0BJ 8BJ 6GEC 2/0GEC 4GEC 2/0GEC 2/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
3. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
2. FEEDER CALLOUTS DENOTED WITH AN 'S4' RATHER THAN AN 'F4' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16
NOTES:
600 600S4 2 2 1/2" (4)350 KCM N/A 600 600S4 2 3 1/2" (4)500 KCM N/A
600 600F4 2 2 1/2" (4)350 KCM (1)#1 600 600F4 2 3 1/2" (4)500 KCM (1)#2/0 AL
225 225F4 1 2 1/2" (4)#4/0 (1)#4 225 225F4 1 2" (4)300 KCM (1)#2 AL
100 100F4 1 1 1/2" (4)#1 (1)#6 100 100F4 1 1 1/2" (4)#1/0 (1)#4 AL
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
4-WIRE FEEDER SCHEDULE
PANEL
"HPL1"
PANEL
"TENANT
A"
M M
T
F
400/3
30
/
3
60
/
3
10
0
/
3
10
0
/
3
10
0
/
3
400S4
60F4
60F4
SPD
1
2
3 4
M
5
M
6
PANEL
"TENANT
B"
PANEL
"TENANT
C"
100F4
100F4
100F4
100F4
100F4
100F4
10
0
/
3
M
7
PANEL
"TENANT
C"
100F4
100F4
10
0
/
3
10
0
/
3
M
208/120V, 3PH, 4W, UTILITY
TRANSFORMER
"MSB" 400A, 208/120V, 3PH, 4W,
65KAIC, NEMA 3R
1 2 3 4
TO UTILITY PRIMARY
5 6 7
SOLAR KEY NOTES:
2. CIRCUIT BREAKER FOR PV SYSTEM, PROVIDED BY EC. COORDINATE REQUIREMENTS WITH PV
CONTRACTOR.
3. PV CONNECTION BY PV CONTRACTOR.
4. PROVIDE (2)2"C TO ROOF. FEEDERS BY SOLAR CONTRACTOR. FOR FUTURE USE.
5. NON-FUSED, UTILITY DISCONNECT AND PV PRODUCTION METER BY PV CONTRACTOR.
#
PV PANEL
/ ARRAY
2
PV STORAGE
3
4 3
5
ROOF
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:24 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - MIXED-USE
E513
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - MIXED-USE
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
400A 1/0BJ 8BJ 6GEC 1/0GEC 4GEC 1/0GEC 1/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
295 MIN. FEEDER AMPS
106140 TOTAL VA (W/ CONTINUOUS)
37796 26% SPARE AVAILABLE
106140 TOTAL VA
LMOTOR 0 1.25 0
MOTOR 0 1 0
NONCONC. 0 0 0
MISC 106140 1 106140
KITCHEN 0 0.65 0
EQUIP 0 1 0
LIGHTING 0 1.25 0
RECEPT 0 NEC 0
LOAD TYPE LOAD IN VA FACTOR DIVERSIFIED LOAD
30/3 SPD
6 FUTURE SOLAR
5 100/3 24660 TENANT 4
4 100/3 24660 TENANT 3
3 100/3 24660 TENANT 2
2 100/3 24660 TENANT 1
1 60/3 7500 HOUSE PANEL
CKT # O/C REMARKS LOAD VA DESCRIPTION
BREAKER DISTRIBUTION 100% NEUTRAL
XXXXX MINIMUM AIC RATING FULLY RATED
400 AMP MCB INTEGRAL SPD
208/120V 3 PHASE 4 WIRE W/ GND BAR 80% MAIN
DISTRIBUTION PANEL MDP-MIXED USE
3. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
2. FEEDER CALLOUTS DENOTED WITH AN 'S4' RATHER THAN AN 'F4' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16
NOTES:
400 400S4 2 2" (4)#3/0 N/A 400 400S4 2 2 1/2" (4)250 KCM N/A
400 400F4 2 2" (4)#3/0 (1)#3 400 400F4 2 2 1/2" (4)250 KCM (1)#1 AL
100 100F4 1 1 1/2" (4)#1 (1)#6 100 100F4 1 1 1/2" (4)#1/0 (1)#4 AL
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
4-WIRE FEEDER SCHEDULE
PANEL
"HPL1"
PANEL
"TENANT
A"
M M
T
F
800/3
30
/
3
60
/
3
20
0
/
3
20
0
/
3
20
0
/
3
800S4
60F4 200F4
60F4 200F4
SPD
1
2
3 4
M
200F4
200F4
5
M
200F4
200F4
6
PANEL
"TENANT
B"
PANEL
"TENANT
C"
20
0
/
3
M
200F4
200F4
7
PANEL
"TENANT
D"
208/120V, 3PH, 4W, UTILITY
TRANSFORMER
"MSB" 800A, 208/120V, 3PH, 4W,
65KAIC, NEMA 3R
1 2 3 4
TO UTILITY PRIMARY
5
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:24 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - SMALL
OFFICE
E514
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - SMALL OFFICE
3. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
2. FEEDER CALLOUTS DENOTED WITH AN 'S4' RATHER THAN AN 'F4' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16
NOTES:
800 800S4 3 2 1/2" (4)300 KCM N/A 800 800S4 3 3" (4)400 KCM N/A
800 800F4 3 2 1/2" (4)300 KCM (1)#1/0 800 800F4 3 3" (4)400 KCM (1)#3/0 AL
200 200F4 1 2" (4)#3/0 (1)#6 200 200F4 1 2" (4)250 KCM (1)#4 AL
60 60F4 1 1 1/4" (4)#6 (1)#8
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
4-WIRE FEEDER SCHEDULE
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
800A 2/0BJ 8BJ 6GEC 2/0GEC 4GEC 2/0GEC 2/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
538 MIN. FEEDER AMPS
193520 TOTAL VA (W/ CONTINUOUS)
94352 33% SPARE AVAILABLE
193520 TOTAL VA
LMOTOR 0 1.25 0
MOTOR 0 1 0
NONCONC. 0 0 0
MISC 193520 1 193520
KITCHEN 0 0.65 0
EQUIP 0 1 0
LIGHTING 0 1.25 0
RECEPT 0 NEC 0
LOAD TYPE LOAD IN VA FACTOR DIVERSIFIED LOAD
30/3 SPD
5 200/3 45700 TENANT D
4 200/3 46420 TENANT C
3 200/3 45700 TENANT B
2 200/3 45700 TENANT A
1 60/3 10000 HOUSE PANEL
CKT # O/C REMARKS LOAD VA DESCRIPTION
BREAKER DISTRIBUTION 100% NEUTRAL
XXXXX MINIMUM AIC RATING FULLY RATED
800 AMP MCB INTEGRAL SPD
208/120V 3 PHASE 4 WIRE W/ GND BAR 80% MAIN
DISTRIBUTION PANEL MDP-OFFICESM
PANEL
"HPL1"
PANEL
"TENANT
A"
M M
T
F
1200/3
30
/
3
10
0
/
3
20
0
/
3
20
0
/
3
20
0
/
3
20
0
/
3
20
0
/
3
20
0
/
3
1200S4
100F4 200F4
100F4 200F4
SPD
1
2
3 4
M
200F4
200F4
5
M
200F4
200F4
6
M
200F4
200F4
7
M
200F4
200F4
8
M
200F4
200F4
9
PANEL
"TENANT
B"
PANEL
"TENANT
C"
PANEL
"TENANT
D"
PANEL
"TENANT
E"
PANEL
"TENANT
F"
208/120V, 3PH, 4W, UTILITY
TRANSFORMER
"MSB" 1200A, 208/120V, 3PH, 4W,
65KAIC, NEMA 3R
1 2 3 4 5 6 7
TO UTILITY PRIMARY
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:25 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - LARGE
OFFICE
E515
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - LARGE OFFICE
3. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
2. FEEDER CALLOUTS DENOTED WITH AN 'S4' RATHER THAN AN 'F4' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16
NOTES:
1200 1200S4 4 2 1/2" (4)350 KCM N/A 1200 1200S4 4 3 1/2" (4)500 KCM N/A
1200 1200F4 4 2 1/2" (4)350 KCM (1)#3/0 1200 1200F4 4 3 1/2"(4)500 KCM (1)250 KCM AL
200 200F4 1 2" (4)#3/0 (1)#6 200 200F4 1 2" (4)250 KCM (1)#4 AL
100 100F4 1 1 1/2" (4)#1 (1)#6 100 100F4 1 1 1/2" (4)#1/0 (1)#4 AL
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
4-WIRE FEEDER SCHEDULE
950 MIN. FEEDER AMPS
341680 TOTAL VA (W/ CONTINUOUS)
90128 21% SPARE AVAILABLE
341680 TOTAL VA
LMOTOR 0 1.25 0
MOTOR 0 1 0
NONCONC. 0 0 0
MISC 341680 1 341680
KITCHEN 0 0.65 0
EQUIP 0 1 0
LIGHTING 0 1.25 0
RECEPT 0 NEC 0
LOAD TYPE LOAD IN VA FACTOR DIVERSIFIED LOAD
30/3 SPD
7 200/3 46300 TENANT F
6 200/3 66400 TENANT E
5 200/3 45640 TENANT D
4 200/3 46300 TENANT C
3 200/3 66400 TENANT B
2 200/3 45640 TENANT A
1 100/3 25000 HOUSE PANEL
CKT # O/C REMARKS LOAD VA DESCRIPTION
BREAKER DISTRIBUTION 100% NEUTRAL
XXXXX MINIMUM AIC RATING FULLY RATED
1200 AMP MCB INTEGRAL SPD
208/120V 3 PHASE 4 WIRE W/ GND BAR 80% MAIN
DISTRIBUTION PANEL MDP-OFFICELG
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
1200A 4/0BJ 8BJ 6GEC 3/0GEC 4GEC 3/0GEC 3/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:26 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ELECTRICAL CALCULATIONS - 32
UNIT
E800A
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
REQUIRED FEEDER AMPACITY 174 121
TOTAL DEMAND (W)36118 25134
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 20142.4
REMAINDER AT 40% 25356 10142.4
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 35356
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 15656
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 1
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4470
REMAINDER AT 25%
3001 - 120000 VA 35% 4200 1470
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 7200
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 2700 2700
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 900 SQFT
UNIT A
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 172 119
TOTAL DEMAND (W)35811 24784
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 19792
REMAINDER AT 40% 24480 9792
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 34480
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 15656
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 1
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4163.4
REMAINDER AT 25%
3001 - 120000 VA 35% 3324 1163.4
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 6324
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 1824 1824
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 608 SQFT
UNIT A1
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 172 119
TOTAL DEMAND (W)35803 24774
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 19782.4
REMAINDER AT 40% 24456 9782.4
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 34456
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 15656
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 1
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4155
REMAINDER AT 25%
3001 - 120000 VA 35% 3300 1155
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 6300
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 1800 1800
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 600 SQFT
UNIT A2
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 172 119
TOTAL DEMAND (W)35698 24654
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 19662.4
REMAINDER AT 40% 24156 9662.4
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 34156
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 15656
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 1
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4050
REMAINDER AT 25%
3001 - 120000 VA 35% 3000 1050
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 6000
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 1500 1500
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 500 SQFT
UNIT A3
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 175 122
TOTAL DEMAND (W)36369 25421
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 20429.2
REMAINDER AT 40% 26073 10429.2
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 36073
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 15656
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 1
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4720.95
REMAINDER AT 25%
3001 - 120000 VA 35% 4917 1720.95
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 7917
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 3417 3417
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 1139 SQFT
UNIT B
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 172 119
TOTAL DEMAND (W)35698 24654
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 19662.4
REMAINDER AT 40% 24156 9662.4
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 34156
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 15656
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 1
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4050
REMAINDER AT 25%
3001 - 120000 VA 35% 3000 1050
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 6000
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 1500 1500
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 500 SQFT
UNIT B1
DWELLING UNIT LOAD CALCULATION
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:27 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ELECTRICAL CALCULATIONS - 32
UNIT
E800B
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
REQUIRED FEEDER AMPACITY 174 121
TOTAL DEMAND (W)36236 25269
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 20276.8
REMAINDER AT 40% 25692 10276.8
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 35692
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 15656
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 1
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4587.6
REMAINDER AT 25%
3001 - 120000 VA 35% 4536 1587.6
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 7536
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 3036 3036
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 1012 SQFT
UNIT B2
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 176 123
TOTAL DEMAND (W)36573 25654
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 20662
REMAINDER AT 40% 26655 10662
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 36655
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 15656
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 1
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4924.65
REMAINDER AT 25%
3001 - 120000 VA 35% 5499 1924.65
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 8499
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 3999 3999
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 1333 SQFT
UNIT C
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 172 119
TOTAL DEMAND (W)35698 24654
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 19662.4
REMAINDER AT 40% 24156 9662.4
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 34156
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 15656
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 1
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4050
REMAINDER AT 25%
3001 - 120000 VA 35% 3000 1050
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 6000
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 1500 1500
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 500 SQFT
UNIT C1
DWELLING UNIT LOAD CALCULATION
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:28 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ELECTRICAL CALCULATIONS - 49
UNIT
E801A
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
REQUIRED FEEDER AMPACITY 153 119
TOTAL DEMAND (W)31901 24788
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 19795.6
REMAINDER AT 40% 24489 9795.6
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 34489
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 11742
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 0.75
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4166.55
REMAINDER AT 25%
3001 - 120000 VA 35% 3333 1166.55
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 6333
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 1833 1833
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 611 SQFT
UNIT S1
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 173 121
TOTAL DEMAND (W)36057 25065
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 20072.8
REMAINDER AT 40% 25182 10072.8
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 35182
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 15656
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 1
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4409.1
REMAINDER AT 25%
3001 - 120000 VA 35% 4026 1409.1
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 7026
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 2526 2526
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 842 SQFT
UNIT A1
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 154 120
TOTAL DEMAND (W)32032 24938
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 19945.6
REMAINDER AT 40% 24864 9945.6
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 34864
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 11742
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 0.75
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4297.8
REMAINDER AT 25%
3001 - 120000 VA 35% 3708 1297.8
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 6708
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 2208 2208
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 736 SQFT
UNIT A2
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 156 122
TOTAL DEMAND (W)32442 25407
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 20414.8
REMAINDER AT 40% 26037 10414.8
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 36037
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 11742
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 0.75
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4708.35
REMAINDER AT 25%
3001 - 120000 VA 35% 4881 1708.35
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 7881
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 3381 3381
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 1127 SQFT
UNIT C1
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 156 122
TOTAL DEMAND (W)32475 25444
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 20452
REMAINDER AT 40% 26130 10452
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 36130
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 11742
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 0.75
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4740.9
REMAINDER AT 25%
3001 - 120000 VA 35% 4974 1740.9
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 7974
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 3474 3474
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 1158 SQFT
UNIT C2
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 156 123
TOTAL DEMAND (W)32531 25508
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 20515.6
REMAINDER AT 40% 26289 10515.6
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 36289
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 11742
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 0.75
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4796.55
REMAINDER AT 25%
3001 - 120000 VA 35% 5133 1796.55
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 8133
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 3633 3633
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 1211 SQFT
UNIT C3
DWELLING UNIT LOAD CALCULATION
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:29 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ELECTRICAL CALCULATIONS - 49
UNIT
E801B
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
REQUIRED FEEDER AMPACITY 157 123
TOTAL DEMAND (W)32644 25637
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 20645.2
REMAINDER AT 40% 26613 10645.2
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 36613
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 11742
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 0.75
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 4909.95
REMAINDER AT 25%
3001 - 120000 VA 35% 5457 1909.95
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 8457
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 3957 3957
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/208 UNIT AREA: 1319 SQFT
UNIT D1
DWELLING UNIT LOAD CALCULATION
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:29 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ELECTRICAL CALCULATIONS -
BROWN
E802
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
REQUIRED FEEDER AMPACITY 139 111
TOTAL DEMAND (W)33422 26526
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 21534.4
REMAINDER AT 40% 28836 11534.4
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 38836
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 11742
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 0.75
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 5688
REMAINDER AT 25%
3001 - 120000 VA 35% 7680 2688
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 10680
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 6180 6180
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/240 UNIT AREA: 2060 SQFT
UNIT A
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 156 111
TOTAL DEMAND (W)37498 26711
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 21719.2
REMAINDER AT 40% 29298 11719.2
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 39298
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 15656
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 1
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 5849.7
REMAINDER AT 25%
3001 - 120000 VA 35% 8142 2849.7
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 11142
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 6642 6642
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/240 UNIT AREA: 2214 SQFT
UNIT B
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 138 109
TOTAL DEMAND (W)33088 26145
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 21152.8
REMAINDER AT 40% 27882 11152.8
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 37882
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 11742
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 0.75
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 5354.1
REMAINDER AT 25%
3001 - 120000 VA 35% 6726 2354.1
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 9726
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 5226 5226
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/240 UNIT AREA: 1742 SQFT
UNIT C
DWELLING UNIT LOAD CALCULATION
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
NOT F
O
R
CON
S
T
R
U
C
TION
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
8/21/2024 2:36:30 PM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ELECTRICAL CALCULATIONS - 3
STORY
E803
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
REQUIRED FEEDER AMPACITY 139 110
TOTAL DEMAND (W)33409 26512
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 21520
REMAINDER AT 40% 28800 11520
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 38800
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 11742
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 0.75
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 5675.4
REMAINDER AT 25%
3001 - 120000 VA 35% 7644 2675.4
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 10644
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 6144 6144
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/240 UNIT AREA: 2048 SQFT
UNIT A
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 155 109
TOTAL DEMAND (W)37092 26248
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 21256
REMAINDER AT 40% 28140 11256
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 38140
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 15656
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 1
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 5444.4
REMAINDER AT 25%
3001 - 120000 VA 35% 6984 2444.4
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 9984
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 5484 5484
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/240 UNIT AREA: 1828 SQFT
UNIT B
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 138 109
TOTAL DEMAND (W)33178 26248
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 21256
REMAINDER AT 40% 28140 11256
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 38140
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 11742
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 0.75
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 5444.4
REMAINDER AT 25%
3001 - 120000 VA 35% 6984 2444.4
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 9984
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 5484 5484
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/240 UNIT AREA: 1828 SQFT
UNIT C
DWELLING UNIT LOAD CALCULATION
REQUIRED FEEDER AMPACITY 139 110
TOTAL DEMAND (W)33334 26426
OPTIONAL CALCULATION HEATING AND A/C DEMAND 4992
HEATING AND AIR CONDITIONING DEMAND 4992
ELECTRIC HEAT NAMEPLATE RATING (W): 4992
AIR CONDITIONING NAMEPLATE RATING (W): 4992
HEATING AND AIR CONDITIONING
OPTIONAL CALCULATION GENERAL LOAD DEMAND 21433.6
REMAINDER AT 40% 28584 11433.6
10000 W AT 100% 10000 10000
DEMAND FACTORS
OPTIONAL CALCULATION GENERAL LOAD TOTAL 38584
DRYER NAMEPLATE RATING (W): 5000 5000 5000
COOKING EQUIPMENT DEMAND 6000
TABLE 220.55 FACTOR 0.8
OVEN NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
COOKTOP NAMEPLATE RATING (W):
TABLE 220.55 FACTOR 0.8
RANGE NAMEPLATE RATING (W): 7500 6000 7500
COOKING EQUIPMENT (1-3/4KW TO 8-3/4KW ONLY)
PERMANENTLY CONNECTED APPLIANCE DEMAND 11742
DEMAND FACTOR FOR 4 OR MORE APPLIANCES: 0.75
APPLIANCE TOTAL 15656
EV CHARGER NAMEPLATE RATING (W): 6500 6500 6500
WATER HEATER NAMEPLATE RATING (W): 3000 3000 3000
FURNACE FAN NAMEPLATE RATING (W): 1956 1956 1956
MICROWAVE NAMEPLATE RATING (W): 1100 1100 1100
DISHWASHER NAMEPLATE RATING (W): 1100 1100 1100
DISPOSAL NAMEPLATE RATING (W): 1200 1200 1200
REFRIGERATOR NAMEPLATE RATING (W): 800 800 800
PERMANENTLY CONNECTED APPLIANCES
LIGHTING AND SMALL APPLIANCE DEMAND 5599.8
REMAINDER AT 25%
3001 - 120000 VA 35% 7428 2599.8
3000 VA AT 100% 3000 3000
DEMAND FACTORS
LIGHTING TOTAL 10428
LAUNDRY CIRCUIT 1 1500 VA 1500 1500
SMALL APPLIANCE CIRCUITS 2 1500 VA 3000 3000
LIGHTING 3 VA/SF 5928 5928
STANDARD OPTIONAL
SYSTEM VOLTAGE (1PH) 120/240 UNIT AREA: 1976 SQFT
UNIT D
DWELLING UNIT LOAD CALCULATION