HomeMy WebLinkAboutUNION PARK - FDP240004 - SUBMITTAL DOCUMENTS - ROUND 2 - Electrical PlansT
F
600S4
M
600F4
1
2
MDP
DAYCARE
PANEL
"A"
PANEL
"B"
225F4
225F4
3 4
208/120V, 3PH, 4W, UTILITY
TRANSFORMER
TO UTILITY PRIMARY
DISCONNECT/CT
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:NOT FOR CONSTRUCTIONCOPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/17/2024 9:44:56 AM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - DAYCARE
E512
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - DAYCARE
428 MIN. FEEDER AMPS
154020 TOTAL VA (W/ CONTINUOUS)
61884 29% SPARE AVAILABLE
154020 TOTAL VA
LMOTOR 0 1.25 0
MOTOR 0 1 0
NONCONC. 0 0 0
MISC 112040 1 112040
KITCHEN 0 0.65 0
EQUIP 41980 1 41980
LIGHTING 0 1.25 0
RECEPT 0 NEC 0
LOAD TYPE LOAD IN VA FACTOR DIVERSIFIED LOAD
30/3 SPD
12 4660 E-CU-10
11 4000 E-CU-9
10 4660 E-CU-8
9 4660 E-CU-7
8 4000 E-CU-6
7 4000 E-CU-5
6 4000 E-CU-4
5 4000 E-CU-3
4 4000 E-CU-2
3 4000 E-CU-1
2 225/3 66400 PANEL B
1 225/3 45640 PANEL A
CKT # O/C REMARKS LOAD VA DESCRIPTION
BREAKER DISTRIBUTION 100% NEUTRAL
XXXXX MINIMUM AIC RATING FULLY RATED
600 AMP MCB INTEGRAL SPD
208/120V 3 PHASE 4 WIRE W/ GND BAR 80% MAIN
DISTRIBUTION PANEL MDP-DAYCARE
LMOTOR 0 1.25 0
MOTOR 0 1 0
NONCONC. 0 0 0 14353 C-PHASE LOAD
MISC 0 1 0 15634 B-PHASE LOAD
KITCHEN 0 0.65 0 12938 A-PHASE LOAD
EQUIP 13795 1 13795 106 MIN. FEEDER AMPS
LIGHTING 8560 1.25 10700 38311 VA (W/ CONTINUOUS)
RECEPT 20570 NEC 15285 42653 52.7% SPARE
LOAD TYPE LOAD IN VA FACTOR DIV LOAD 37640 TOTAL VA
SECURITY PANEL 250 20/1 59 C 60
* 600 *
INTERCOM SYSTEM 250 20/1 57 B 58
15/2 600 E-ERV-4
E-RECEPTION FRIDGE 750 GFCI 20/1 55 A 56
SPARE
R-RECEPTION 1080 20/1 53 C 54
20/1 GFCI 1200 E-COMMERCIAL DISHWASHER
R-POFFICE 900 20/1 51 B 52
* 2300 *
E-ELECTRIC WATER COOLER 500 GFCI 20/1 49 A 50
30/2 GFCI 2300 E-COMMERCIAL OVEN
R-RESOURCE 540 20/1 47 C 48
20/1 360 R-SECURITY RACK
R-TELEPHONE BOARD 360 20/1 45 B 46
20/1 540 R-KITCHEN RECEPTS
E-IRRIGATION CONTROLLER 100 20/1 43 A 44
20/1 540 R-KITCHEN RECEPTS
R-LAUNDRY/SPRINKLER RM 540 20/1 41 C 42
20/1 1150 L-SITE LIGHTING
E-FRIDGE 775 GFCI 20/1 39 B 40
20/1 481 L-CLASSROOM/TOILET
L-CLASSROOM LTG 750 20/1 37 A 38
20/1 316 L-GALLEY/STOR.
E-FRIDGE 770 GFCI 20/1 35 C 36
20/1 738 L-CLASSRM/OFFICE/TOILET
R-CLASSROOM RECEPT 775 20/1 33 B 34
20/1 720 R-CLASSROOM RECEPT
R-GALLERY/ELEC. 1080 20/1 31 A 32
20/1 540 R-CLASSROOM RECEPT
R-CLASSROOM RECEPT 1125 20/1 29 C 30
20/1 900 R-CLASSROOM RECEPT
SPARE 720 20/1 27 B 28
20/1 720 R-OFFICE
L-CLASSROOM LTG 950 20/1 25 A 26
20/1 500 E-ELECTRIC WATER COOLER
L-CLASSROOM LTG 950 20/1 23 C 24
20/1 540 R-CLASSROOM RECEPT
L-CLASSROOM LTG 468 20/1 21 B 22
20/1 720 R-CLASSROOM RECEPT
L-CLASSROOM LTG 525 20/1 19 A 20
20/1 540 R-STAFF 205
L-CLASSROOM LTG 682 20/1 17 C 18
20/1 900 R-CLASSROOM RECEPT
L-CLASSROOM LTG 986 20/1 15 B 16
20/1 720 R-CLASSROOM RECEPT
SPARE 20/1 13 A 14
20/1 720 R-CLASSROOM RECEPT
L-CLASSROOM LTG 772 20/1 11 C 12
20/1 540 R-CLASSROOM RECEPT
L-CLASSROOM LTG 784 20/1 9 B 10
20/1 GFCI 1080 R-VESTABULE RECEPTS
L-GALLERY/VESTIBULE LTG 490 20/1 7 A 8
20/1 720 R-CLASSROOM RECEPT
L-CONF RM/MECH/ELEC/STAIR 216 20/1 5 C 6
20/1 GFCI 500 E-ICE MAKER
L-CLASSROOM LTG 535 20/1 3 B 4
20/1 GFCI 1200 E-FREEZER
L-CLASSROOM LTG 417 20/1 1 A 2
20/1 GFCI 1200 E- FRIDGE
DESCRIPTION LOAD VA REMARKS O/C CKT # PH CKT # O/C REMARKS LOAD VA DESCRIPTION
60 POLES ONE SECTION
10000 MINIMUM AIC RATING FULLY RATED
225 AMP MLO 100% NEUTRAL
208/120V 3 PHASE 4 WIRE W/ GND BAR SURFACE MOUNTED
PANELA
LMOTOR 0 1.25 0
MOTOR 0 1 0
NONCONC. 0 0 0 13010 C-PHASE LOAD
MISC 0 1 0 12960 B-PHASE LOAD
KITCHEN 0 0.65 0 16665 A-PHASE LOAD
EQUIP 42635 1 42635 118 MIN. FEEDER AMPS
LIGHTING 0 1.25 0 42635 VA (W/ CONTINUOUS)
RECEPT 0 NEC 0 38329 47.3% SPARE
LOAD TYPE LOAD IN VA FACTOR DIV LOAD 42635 TOTAL VA
E-CP-2 60 20/1 41 C 42
20/1 SPARE
E-CP-1 60 20/1 39 B 40
* 600 *
E-SP-1 500 20/1 37 A 38
15/2 600 E-ERV-3
E-WH-2 600 20/1 35 C 36
* 600 *
E-WH-1 600 20/1 33 B 34
15/2 600 E-ERV-2
E-EF-2 165 20/1 31 A 32
* 600 *
E-EF-1 250 20/1 29 C 30
15/2 600 E-ERV-1
*1100 *27 B 28
15/1 SPARE
E-EUH-2 1100 GFCI 30/2 25 A 26
15/1 SPARE
*1500 *23 C 24
15/1 SPARE
E-EUH-1 1500 GFCI 30/2 21 B 22
15/1 SPARE
*1600 *19 A 20
15/1 1700 E-FURN-10
E-DRYER 1600 GFCI 30/2 17 C 18
15/1 1300 E-FURN-9
E-WASHER 1000 GFCI 20/1 15 B 16
15/1 1700 E-FURN-8
*1600 *13 A 14
15/1 1700 E-FURN-7
E-DRYER 1600 GFCI 30/2 11 C 12
15/1 1300 E-FURN-6
E-WASHER 1000 GFCI 20/1 9 B 10
15/1 1300 E-FURN-5
*2300 *7 A 8
15/1 1300 E-FURN-4
E-COMMERCIAL OVEN 2300 GFCI 30/2 5 C 6
15/1 1300 E-FURN-3
*2200 *3 B 4
15/1 1300 E-FURN-2
E-COMMERCIAL MICROWAVE 2200 GFCI 30/2 1 A 2
15/1 1300 E-FURN-1
DESCRIPTION LOAD VA REMARKS O/C CKT # PH CKT # O/C REMARKS LOAD VA DESCRIPTION
42 POLES ONE SECTION
10000 MINIMUM AIC RATING FULLY RATED
225 AMP MLO 100% NEUTRAL
208/120V 3 PHASE 4 WIRE W/ GND BAR SURFACE MOUNTED
PANELB
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
600A 2/0BJ 8BJ 6GEC 2/0GEC 4GEC 2/0GEC 2/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
3. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
2. FEEDER CALLOUTS DENOTED WITH AN 'S4' RATHER THAN AN 'F4' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16
NOTES:
600 600S4 2 2 1/2" (4)350 KCM N/A 600 600S4 2 3 1/2" (4)500 KCM N/A
600 600F4 2 2 1/2" (4)350 KCM (1)#1 600 600F4 2 3 1/2" (4)500 KCM (1)#2/0 AL
225 225F4 1 2 1/2" (4)#4/0 (1)#4 225 225F4 1 2" (4)300 KCM (1)#2 AL
100 100F4 1 1 1/2" (4)#1 (1)#6 100 100F4 1 1 1/2" (4)#1/0 (1)#4 AL
OCPD
RATING
FEEDER
TYPE SETS CONDUIT
PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
TYPE SETS CONDUIT
PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
4-WIRE FEEDER SCHEDULE
PANEL
"HPL1"
PANEL
"TENANT
A"
M M
T
F
400/3
30
/
3
60
/
3
10
0
/
3
10
0
/
3
10
0
/
3
400S4
60F4
60F4
SPD
1
2
3 4
M
5
M
6
PANEL
"TENANT
B"
PANEL
"TENANT
C"
100F4
100F4
100F4
100F4
100F4
100F4
10
0
/
3
M
7
PANEL
"TENANT
C"
100F4
100F4
10
0
/
3
10
0
/
3
M
208/120V, 3PH, 4W, UTILITY
TRANSFORMER
"MSB" 400A, 208/120V, 3PH, 4W,
65KAIC, NEMA 3R
1 2 3 4
TO UTILITY PRIMARY
5 6 7
SOLAR KEY NOTES:
2. CIRCUIT BREAKER FOR PV SYSTEM, PROVIDED BY EC. COORDINATE REQUIREMENTS WITH PV
CONTRACTOR.
3. PV CONNECTION BY PV CONTRACTOR.
4. PROVIDE (2)2"C TO ROOF. FEEDERS BY SOLAR CONTRACTOR. FOR FUTURE USE.
5. NON-FUSED, UTILITY DISCONNECT AND PV PRODUCTION METER BY PV CONTRACTOR.
#
PV PANEL
/ ARRAY
2
PV STORAGE
3
4 3
5
ROOF
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:NOT FOR CONSTRUCTIONCOPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/17/2024 9:44:56 AM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - MIXED-USE
E513
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - MIXED-USE
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
400A 1/0BJ 8BJ 6GEC 1/0GEC 4GEC 1/0GEC 1/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
295 MIN. FEEDER AMPS
106140 TOTAL VA (W/ CONTINUOUS)
37796 26% SPARE AVAILABLE
106140 TOTAL VA
LMOTOR 0 1.25 0
MOTOR 0 1 0
NONCONC. 0 0 0
MISC 106140 1 106140
KITCHEN 0 0.65 0
EQUIP 0 1 0
LIGHTING 0 1.25 0
RECEPT 0 NEC 0
LOAD TYPE LOAD IN VA FACTOR DIVERSIFIED LOAD
30/3 SPD
6 FUTURE SOLAR
5 100/3 24660 TENANT 4
4 100/3 24660 TENANT 3
3 100/3 24660 TENANT 2
2 100/3 24660 TENANT 1
1 60/3 7500 HOUSE PANEL
CKT # O/C REMARKS LOAD VA DESCRIPTION
BREAKER DISTRIBUTION 100% NEUTRAL
XXXXX MINIMUM AIC RATING FULLY RATED
400 AMP MCB INTEGRAL SPD
208/120V 3 PHASE 4 WIRE W/ GND BAR 80% MAIN
DISTRIBUTION PANEL MDP-MIXED USE
3. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
2. FEEDER CALLOUTS DENOTED WITH AN 'S4' RATHER THAN AN 'F4' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16
NOTES:
400 400S4 2 2" (4)#3/0 N/A 400 400S4 2 2 1/2" (4)250 KCM N/A
400 400F4 2 2" (4)#3/0 (1)#3 400 400F4 2 2 1/2" (4)250 KCM (1)#1 AL
100 100F4 1 1 1/2" (4)#1 (1)#6 100 100F4 1 1 1/2" (4)#1/0 (1)#4 AL
OCPD
RATING
FEEDER
TYPE SETS CONDUIT
PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
TYPE SETS CONDUIT
PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
4-WIRE FEEDER SCHEDULE
PANEL
"HPL1"
PANEL
"TENANT
A"
M M
T
F
800/3
30
/
3
60
/
3
20
0
/
3
20
0
/
3
20
0
/
3
800S4
60F4 200F4
60F4 200F4
SPD
1
2
3 4
M
200F4
200F4
5
M
200F4
200F4
6
PANEL
"TENANT
B"
PANEL
"TENANT
C"
20
0
/
3
M
200F4
200F4
7
PANEL
"TENANT
D"
208/120V, 3PH, 4W, UTILITY
TRANSFORMER
"MSB" 800A, 208/120V, 3PH, 4W,
65KAIC, NEMA 3R
1 2 3 4
TO UTILITY PRIMARY
5
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:NOT FOR CONSTRUCTIONCOPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/17/2024 9:44:57 AM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - SMALL
OFFICE
E514
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - SMALL OFFICE
3. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
2. FEEDER CALLOUTS DENOTED WITH AN 'S4' RATHER THAN AN 'F4' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16
NOTES:
800 800S4 3 2 1/2" (4)300 KCM N/A 800 800S4 3 3" (4)400 KCM N/A
800 800F4 3 2 1/2" (4)300 KCM (1)#1/0 800 800F4 3 3" (4)400 KCM (1)#3/0 AL
200 200F4 1 2" (4)#3/0 (1)#6 200 200F4 1 2" (4)250 KCM (1)#4 AL
60 60F4 1 1 1/4" (4)#6 (1)#8
OCPD
RATING
FEEDER
TYPE SETS CONDUIT
PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
TYPE SETS CONDUIT
PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
4-WIRE FEEDER SCHEDULE
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
800A 2/0BJ 8BJ 6GEC 2/0GEC 4GEC 2/0GEC 2/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE
538 MIN. FEEDER AMPS
193520 TOTAL VA (W/ CONTINUOUS)
94352 33% SPARE AVAILABLE
193520 TOTAL VA
LMOTOR 0 1.25 0
MOTOR 0 1 0
NONCONC. 0 0 0
MISC 193520 1 193520
KITCHEN 0 0.65 0
EQUIP 0 1 0
LIGHTING 0 1.25 0
RECEPT 0 NEC 0
LOAD TYPE LOAD IN VA FACTOR DIVERSIFIED LOAD
30/3 SPD
5 200/3 45700 TENANT D
4 200/3 46420 TENANT C
3 200/3 45700 TENANT B
2 200/3 45700 TENANT A
1 60/3 10000 HOUSE PANEL
CKT # O/C REMARKS LOAD VA DESCRIPTION
BREAKER DISTRIBUTION 100% NEUTRAL
XXXXX MINIMUM AIC RATING FULLY RATED
800 AMP MCB INTEGRAL SPD
208/120V 3 PHASE 4 WIRE W/ GND BAR 80% MAIN
DISTRIBUTION PANEL MDP-OFFICESM
PANEL
"HPL1"
PANEL
"TENANT
A"
M M
T
F
1200/3
30
/
3
10
0
/
3
20
0
/
3
20
0
/
3
20
0
/
3
20
0
/
3
20
0
/
3
20
0
/
3
1200S4
100F4 200F4
100F4 200F4
SPD
1
2
3 4
M
200F4
200F4
5
M
200F4
200F4
6
M
200F4
200F4
7
M
200F4
200F4
8
M
200F4
200F4
9
PANEL
"TENANT
B"
PANEL
"TENANT
C"
PANEL
"TENANT
D"
PANEL
"TENANT
E"
PANEL
"TENANT
F"
208/120V, 3PH, 4W, UTILITY
TRANSFORMER
"MSB" 1200A, 208/120V, 3PH, 4W,
65KAIC, NEMA 3R
1 2 3 4 5 6 7
TO UTILITY PRIMARY
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:NOT FOR CONSTRUCTIONCOPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/17/2024 9:44:58 AM
Au
t
o
d
e
s
k
D
o
c
s
:
/
/
L
M
H
1
0
.
3
1
-
O
n
e
-
l
i
n
e
s
/
L
M
H
1
0
.
3
1
-
E
l
e
c
t
ri
c
a
l
O
n
e
-
L
i
n
e
s
_
R
2
3
.
r
v
t
ONE-LINE DIAGRAM - LARGE
OFFICE
E515
LMH000010.31
JTH
RMR
FO
R
T
C
O
L
L
I
N
S
,
C
O
UN
I
O
N
P
A
R
K
O
N
E
-
L
I
N
E
S
LA
N
D
M
A
R
K
H
O
M
E
S
SCALE: NO SCALE1ELECTRICAL ONE-LINE - LARGE OFFICE
3. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
2. FEEDER CALLOUTS DENOTED WITH AN 'S4' RATHER THAN AN 'F4' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
1. AMPACITY BASED UPON NEC, TABLE 310.15.B.16
NOTES:
1200 1200S4 4 2 1/2" (4)350 KCM N/A 1200 1200S4 4 3 1/2" (4)500 KCM N/A
1200 1200F4 4 2 1/2" (4)350 KCM (1)#3/0 1200 1200F4 4 3 1/2"(4)500 KCM (1)250 KCM AL
200 200F4 1 2" (4)#3/0 (1)#6 200 200F4 1 2" (4)250 KCM (1)#4 AL
100 100F4 1 1 1/2" (4)#1 (1)#6 100 100F4 1 1 1/2" (4)#1/0 (1)#4 AL
OCPD
RATING
FEEDER
TYPE SETS CONDUIT
PHASE AND/
OR NEUTRAL GND OCPD
RATING
FEEDER
TYPE SETS CONDUIT
PHASE AND/
OR NEUTRAL GND
COPPER ALUMINUM
4-WIRE FEEDER SCHEDULE
950 MIN. FEEDER AMPS
341680 TOTAL VA (W/ CONTINUOUS)
90128 21% SPARE AVAILABLE
341680 TOTAL VA
LMOTOR 0 1.25 0
MOTOR 0 1 0
NONCONC. 0 0 0
MISC 341680 1 341680
KITCHEN 0 0.65 0
EQUIP 0 1 0
LIGHTING 0 1.25 0
RECEPT 0 NEC 0
LOAD TYPE LOAD IN VA FACTOR DIVERSIFIED LOAD
30/3 SPD
7 200/3 46300 TENANT F
6 200/3 66400 TENANT E
5 200/3 45640 TENANT D
4 200/3 46300 TENANT C
3 200/3 66400 TENANT B
2 200/3 45640 TENANT A
1 100/3 25000 HOUSE PANEL
CKT # O/C REMARKS LOAD VA DESCRIPTION
BREAKER DISTRIBUTION 100% NEUTRAL
XXXXX MINIMUM AIC RATING FULLY RATED
1200 AMP MCB INTEGRAL SPD
208/120V 3 PHASE 4 WIRE W/ GND BAR 80% MAIN
DISTRIBUTION PANEL MDP-OFFICELG
ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT CONSTITUTE NORMALLY DRY CONDITIONS.
RESISTANCE SHALL BE ACHIEVED UNDER NORMALLY DRY CONDITIONS UNLESS OTHERWISE APPROVED BY
TO GROUND WHEN TESTED ACCORDING TO IEEE 81 USING "FALL-OF-POTENTIAL" METHOD. SPECIFIED SYSTEM'S
d. THE RESISTANCE OF THE GROUNDING ELECTRODE SYSTEM SHALL NOT BE GREATER THAN TWENTY FIVE OHMS
COPPER, COPPERCLAD STEEL, OR OTHER UL LISTED GROUND ROD.
c. WHERE NONE OF THE ABOVE ARE AVAILABLE, PROVIDE GEC FROM EQUIPMENT GROUND TO 8' LONG X 5/8" DIAMETER
b. OTHER METAL BUILDING COMPONENTS, MINIMUM LISTED, MATCH EQUIPMENT GROUND OF ASSOCIATED SYSTEM.
a. GROUNDING AND BONDING JUMPER CONDUCTORS ARE COPPER.
GENERAL NOTES:
1200A 4/0BJ 8BJ 6GEC 3/0GEC 4GEC 3/0GEC 3/0GEC -
MAIN
BONDING
JUMPER (BJ)
OTHER METAL
COMPONENTS
MAIN
ELECTRODE
MAIN METAL
WATER PIPE
CONCRETE
ENCASED
GROUND
RING
BUILDING
STEEL
WHRE PRESENT, BONDING GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTED TO
SERVICE
RATING
BONDING/JUMPER DESIGNATION
REMARKS
GROUNDING AND BONDING JUMPER SCHEDULE