July 21, 2023
Russ Lee
Ripley Design Inc
419 Canyon Ave Suite 200
Fort Collins, CO 80521
RE: Sit and Stay Dog Bar, FDP230005, Round Number 2
Please see the following summary of comments from City staff and outside reviewing
agencies for your submittal of Sit and Stay Dog Bar. If you have questions about any
comments, you may contact the individual commenter or direct your questions through your
Development Review Coordinator, Tenae Beane via phone at 970 -224-6119 or via email
at tbeane@fcgov.com.
RIPLEY DESIGN RESPONSE:
VFLA RESPONSE:
OLSSON RESPONSE:
PATRICK DUNCAN RESPONSE:
Comment Summary:
Department: Development Review Coordinator
Contact: Tenae Beane tbeane@fcgov.com 970-224-6119
Topic: General
Comment Number: 1
INFORMATION:
I will be your primary point of contact throughout the development review and
permitting process. If you have any questions, need additional meetings with the
project reviewers, or need assistance throughout the process, please let me
know and I can assist you and your team. Please include me in all email
correspondence with other reviewers and keep me informed of any phone
conversations. Thank you!
RIPLEY DESIGN RESPONSE: Thank you.
2
Comment Number: 2
03/14/2023: SUBMITTAL:
As part of your resubmittal, you will respond to the comments provided in this
letter. This letter is provided to you in Microsoft Word format. Please use this
document to insert responses to each comment for your submittal, using a
different font color.
When replying to the comment letter please be detailed in your responses, as
all comments should be thoroughly addressed. Comments requiring action
should NOT have a response such as noted or acknowledged. You will need to
provide references to specific project plans, pages, reports, or explanations of
why comments have not been addressed [when applicable].
RIPLEY DESIGN RESPONSE: Below comments provieded have been addressed and responded to.
Comment Number: 3
03/14/2023: SUBMITTAL:
Please follow the Electronic Submittal Requirements and File Naming
Standards found at https://www.fcgov.com/developmentreview/files/electronic
submittal requirements and file naming standards_v1_8 1 19.pdf?1566857888.
File names should begin with the file type, followed by the project information,
and round number.
Example: UTILITY PLANS_PROJECT NAME_PDP_Rd2.pdf
File type acronyms maybe appropriate to avoid extremely long file names.
Example: TIS for Traffic Impact Study, ECS for Ecological Characterization
Study.
Reach out to me if you would like a list of suggested names.
*Please disregard any references to paper copies, flash drives, or CDs.
RIPLEY DESIGN RESPONSE: The documents in this submittal follow the above format and naming convention.
Comment Number: 4
03/14/2023: SUBMITTAL:
All plans should be saved as optimized/flattened PDFs to reduce file size and
remove layers.
Per the Electronic Submittal Requirements AutoCAD SHX attributes need to be
removed from the PDF’s.
AutoCAD turns drawing text into comments that appear in the PDF plan set,
and these must be removed prior to submittal as they can cause issues with the
PDF file.
The default setting is "1" ("on") in AutoCAD. To change the setting and remove
this feature, type "EPDFSHX" (version 2016.1) or “PDFSHX (version 2017 and
newer) in the command line and enter "0".
Read this article at Autodesk.com for more on this topic:
https://knowledge.autodesk.com/support/autocad/troubleshooting/caas/sfdcarti
cles/sfdcarticles/Drawing-text-appears-as-Comments-in-a-PDF-created-by-AutoCAD.html
RIPLEY DESIGN RESPONSE: The documents in this submittal follow the above optimization and flattening for size reduction.
Comment Number: 5
03/14/2023: SUBMITTAL:
Resubmittals are accepted any day of the week, with Wednesday at noon being
the cut-off for routing the same week. When you are preparing to resubmit your
3
plans, please notify me with an expected submittal date with as much advanced
notice as possible.
RIPLEY DESIGN RESPONSE: We will be submitting FDP Rd 3 on 05/01/2024.
Comment Number: 6
03/14/2023: INFORMATION:
Please resubmit within 180 days, approximately 6 months, to avoid the
expiration of your project.
RIPLEY DESIGN RESPONSE: We had requested an extension to be better address comments from city staff. The new expiration
date is 06/08/2024.
Comment Number: 7
03/14/2023: INFORMATION:
ANY project that requires four or more rounds of review would be subject to an
additional fee of $3,000.00.
RIPLEY DESIGN RESPONSE: Understood, thank you.
Comment Number: 8
03/14/2023: FOR FINAL APPROVAL:
All "For Final Approval / For Approval" comments need to be addressed and
resolved prior to moving forward with the final documents and recording of this
project. I will provide a recording checklist and process information when we
are closer to this step.
RIPLEY DESIGN RESPONSE: All “For Fianl Approval/ For Approval” comments have been addressed in this comment response
letter.
Comment Number: 9
03/14/2023: INFORMATION:
LUC 2.211 Lapse, Term of Vested Right: Within a maximum of three (3) years
following the approval of a final plan or other site-specific development plan, the
applicant must undertake, install and complete all engineering improvements
(water, sewer, streets, curb, gutter, streetlights, fire hydrants and storm
drainage) in accordance with city codes, rules and regulations. The period of
time shall constitute the "term of the vested property right." Failure to undertake
and complete such engineering improvements within the term of the vested
property right shall cause a forfeiture of the vested property right and shall
require resubmission of all materials and reapproval of the same to be
processed as required by this Code. All dedications as contained on the final
plat shall remain valid unless vacated in accordance with law.
RIPLEY DESIGN RESPONSE: Understood, thank you.
Department: Engineering Development Review
Contact: Sophie Buckingham sbuckingham@fcgov.com
Topic: General
Comment Number: 2
07/07/2023: FOR FINAL APPROVAL - UPDATE:
(Updated by John Gerwel) Thank you for providing the easement legal
4
descriptions and exhibits. The deeds of dedication will also need to be filled out
and signed. The templates can be found here:
https://www.fcgov.com/engineering/devrev.php#cb -38308-6601 - the General
Deed should work just fine for these easements. I'd recommend avoiding
changes to the language provided unless it's necessary. Any changes will need
to be reviewed by our City Attorney's Office.
OLSSON RESPONSE: A General Deed has been filled out, signed, and has been provided.
03/03/2023: FOR FINAL APPROVAL:
Based on discussions with the applicant team, it sounds like there will be two
separate drainage easement dedications. Please submit these easements with
the next round. See instructions for easement dedication in the previous
comment, and contact me with any questions.
Comment Number: 3
07/07/2023: FOR FINAL APPROVAL - UPDATE:
(Updated by John Gerwel) Thank you for providing the easement legal
descriptions and exhibits. The deeds of dedication will also need to be filled out
and signed. The templates can be found here:
https://www.fcgov.com/engineering/devrev.php#cb -38308-6601 - the General
Deed should work just fine for these easements. I'd recommend avoiding
changes to the language provided unless it's necessary. Any changes will need
to be reviewed by our City Attorney's Office.
OLSSON RESPONSE: A General Deed has been filled out, signed, and has been provided.
03/03/2023: FOR FINAL APPROVAL:
This project will be required to dedicate a utility easement for the proposed
transformer and primary wire. Please submit this easement with the next round.
See instructions for easement dedication in the previous comment, and contact
me with any questions.
Comment Number: 4
07/07/2023: FOR FINAL APPROVAL - UNRESOLVED:
(Updated by John Gerwel) A few redlines were unresolved and I added a couple
more.
OLSSON RESPONSE: All redlines have been resolved.
03/13/2023: FOR FINAL APPROVAL:
Please see my redlines for items that need to be cleaned up before the plans
can be recorded.
Comment Number: 5
03/13/2023: INFORMATION:
Please check the plans and make any necessary quality control changes before
the next round of review. Keep in mind that if changes are made between the
final round of review and the submittal of your recording documents, the City will
not be able to accept the recording documents and will require an additional
round of review to address the changes.
5
OLSSON RESPONSE: Acknowledged, thank you.
Department: Traffic Operation
Contact: Steve Gilchrist sgilchrist@fcgov.com 970-224-6175
Topic: General
Comment Number: 3
07/18/2023: FOR FINAL APPROVAL: With the removal of the parking lot on
the south side of the site we would like an east/west sidewalk added that
creates a pedestrian connection along the parking lot to south.
RIPLEY DESIGN RESPONSE: A pedestrian walk connecting the east and west private drives has been included in the new site
design. See sheet “L2 - Site Plan.”
Department: Erosion Control
Contact: Basil Hamdan bhamdan@fcgov.com 970-222-1801
Topic: Erosion Control
Comment Number: 7
07/18/2023: all Erosion and Sediment Control comments have been
addressed.
OLSSON RESPONSE: Acknowledged, thank you.
03/10/2023: FOR FINAL APPROVAL:
Please address all redlined comments provided on the Erosion Control Plans.
Department: Stormwater Engineering
Contact: Wes Lamarque wlamarque@fcgov.com 970-416-2418
Topic: General
Comment Number: 1
07/19/2023: FOR APPROVAL - UPDATED:
Please make more clear the WQ weirs on Sheet 28 in the " Flow Control
Structure Parameters" Detail.
OLSSON RESPONSE: Details have been revised for additional clarity.
03/10/2023: FOR APPROVAL:
Please include all needed Stormtech details in the Utility Plan set. This needs
to include the manifold system as well.
Comment Number: 2
07/19/2023: FOR APPROVAL - UNRESOLVED:
Sanitary sewer connection still needed for washing operations.
OLSSON RESPONSE: Per discussions and coordination with the COFC, the following resolution has been agreed upon:
“To accommodate these concerns, we are going to implement a permeable turf section for part of the site in order to infiltrat e the low
flow sprinklers that arise. For the hard power washed areas, we will drain the flows to the storm sewer system trench dra in and area
inlet in the parking areas. This will require a vault and two valves to open the sanitary system and close the storm system d uring the
washes and vice versa for the remaining time.”
6
03/10/2023: FOR APPROVAL:
Discussions need to take place on dog waste maintenance and what is being
planned for cleanup. Primary waste areas can not drain into the storm sewer
system until cleaning is performed. Is there a proposed method? The City
suggests an area that can be cleaned and rinsed into the sanitary sewer
system. Since the area is outside, a weather proof system would need to be
proposed. This could include a sewer cleanout (intake) that is capped to
prevent storm drainage from entering. The cap could then be removed during
cleaning periods.
Comment Number: 5
07/19/2023: FOR APPROVAL - UPDATED:
The easements need to be labeled "Drainage Easement" not "Storm Utility".
Please revise.
OLSSON RESPONSE: Easement for the Underground detention facility is labeled Drainage Easement.
RIPLEY DESIGN RESPONSE: ESMTS label has been updated to “Drainage Easement” on Site plan.
03/11/2023: FOR APPROVAL:
Drainage easements are required for both Stormtech systems and outlet pipes.
Comment Number: 8
07/19/2023: FOR APPROVAL:
The southeast storm sewer, from the inlet to the Stormtech chambers, is too
close to the proposed shade tree. Please provide 10 feet of separation.
RIPLEY DESIGN RESPONSE: The proposed tree in conflict with the storm sewer has been adjusted to provide greater than 10’
clearance. See sheet “L4 - Landscape & Tree Mitigation” for new location.
Department: Water-Wastewater Engineering
Contact: Wes Lamarque wlamarque@fcgov.com 970-416-2418
Topic: General
Comment Number: 1
07/19/2023: FOR APPROVAL - UNRESOLVED:
03/10/2023: FOR APPROVAL:
Please provide 6 feet of separation from the sewer service and the gas line.
OLSSON RESPONSE: The gas line has been update to show 6 feet of separation from the sanitary sewer grease trap service as
far as possible until it needs to connect into the building.
Comment Number: 3
07/19/2023: FOR APPROVAL - UPDATED:
Please also add water Detail 11.
OLSSON RESPONSE: Water Detail 11 has been added to the first detail sheet.
03/10/2023: FOR APPROVAL:
Please update the water service to the correct details. Water Details 16A &
16B need to be added to the plans and please remove the current detail in the
plan set.
7
Comment Number: 9
07/19/2023: FOR APPROVAL:
Water Details 31 and 2 on Sheet 26 can be removed as well unless there is
some reason they are needed.
OLSSON RESPONSE: Water Details 31 and 2 on Sheet 26 were added for the 6” fire service line and will remain on the plans.
Department: Light And Power
Contact: Austin Kreager akreager@fcgov.com 970-224-6152
Topic: General
Comment Number: 3
03/14/2023: FOR RECORDING: Light & Power will need AutoCAD files of the
site plan, utility plans, and landscape drawings once plans are approved.
OLSSON RESPONSE: CAD files shall be provided once plans are approved.
RIPLEY DESIGN RESPONSE: CAD files shall be provided upon request from Light and Power.
Comment Number: 4
03/14/2023: FOR INFORMATION: Electric capacity fees, development fees,
building site charges and any system modification charges necessary to feed
the site will apply to this development. Please contact me to discuss
development fees or visit the following website for an estimate of charges and
fees related to this project:
http://www.fcgov.com/utilities/business/builders-and-developers/plant-investmen
T-development-fees
Comment Number: 5
03/14/2023: FOR INFORMATION: You may contact Austin Kreager with project
engineering if you have questions. (970) 224-6152. You may reference Light &
Power’s Electric Service Standards at:
https://www.fcgov.com/utilities/img/site_specific/uploads/electricservicestandar
ds.pdf?1645038437
You may reference our policies, development charge processes, and use our
fee estimator at
http://www.fcgov.com/utilities/business/builders-and-developers.
Department: Environmental Planning
Contact: Scott Benton sbenton@fcgov.com (970)416-4290
Topic: General
Comment Number: 2
8
07/17/2023: (UPDATED) FOR FINAL APPROVAL: The old language was
used for Native Seed Mix Note #7, please use the correct language below:
7. AFTER SEEDING THE AREA SHALL BE COVERED WITH CRIMPED
STRAW, JUTE MESH, OR OTHER APPROPRIATE METHODS.
PLASTIC -BASED EROSION CONTROL MATERIALS (I.E.,
PLASTIC-WELDED BLANKETS) SHALL NOT BE USED WITHOUT
EXPRESS PERMISSION FROM THE ENVIRONMENTAL PLANNER AS
THESE MATERIALS HAVE PROVEN TO CAUSE WILDLIFE ENTRAPMENT
ISSUES.
RIPLEY DESIGN RESPONSE: The above note has been updated in the native seed mix notes.
Department: Forestry
Contact: Christine Holtz choltz@fcgov.com
Topic: General
Comment Number: 1
07/17/2023: FOR FINAL APROVAL
Please see forestry redlines for one tree/utility conflict. Please shift the
ornamental tree, and do not remove it from the landscape plan.
RIPLEY DESIGN RESPONSE: As we were not able to open the expired Bluebeam session documents, the landscape plan has
been vetted to adjust the ornamental tree to avoid utility conflicts.
Contact: Russell Hovland rhovland@fcgov.com 970-416-2341
Topic: Building Insp Plan Review
Comment Number: 1
03/13/2023: Construction shall comply with adopted codes as amended.
Current adopted codes are:
2021 International Building Code (IBC) with local amendments
2021 International Existing Building Code (IEBC) with local amendments
2021 International Energy Conservation Code (IECC) with local amendments
2021 International Mechanical Code (IMC) with local amendments
2021 International Fuel Gas Code (IFGC) with local amendments
2021 International Swimming Pool and Spa Code (ISPSC) with local
amendments
Colorado Plumbing Code & state amendments (currently 2018 IPC)
2020 National Electrical Code (NEC) as amended by the State of Colorado
Copies of current City of Fort Collins code amendments can be found at
fcgov.com/building.
· Accessibility: State Law CRS 9-5 & ICC/ANSI A117.1-2017.
· Snow Live Load: Ground Snow Load 35 PSF.
· Frost Depth: 30 inches.
· Wind Loads: Risk Category II (most structures):
· 140mph (Ultimate) exposure B or Front Range Gust Map published by The
Structural Engineer's Association of Colorado
· Seismic Design: Category B.
· Climate Zone: Zone 5
· Energy Code: 2021 IECC commercial chapter.
9
INFORMATIONAL ITEMS:
· Commercial occupancies must provide 10ft to 30ft of fire separation (setback)
from property lines and 20 feet between other buildings or provide fire rated
walls and openings per chapter 6 and 7 of the IBC.
· City of Fort Collins adopted International Fire Code (IFC) and amendments to
the 2018/2021 IFC require a full NFPA-13 sprinkler system per IBC chapter 9 or
when building exceeds 5000 sq.ft. (or meet fire containment requirements).
· Buildings using electric heat, must use heat pump equipment.
· A City licensed commercial general contractor is required to construct any new
commercial structure.
· Plans must be signed and stamped by a Colorado licensed architect or
engineer and must be included in the permit application.
· Electric vehicle parking spaces are now required per local amendment to the
IBC. See section 3604.
· For projects located in Metro Districts, there are special additional code
requirements for new buildings. Please contact the plan review team to obtain
the requirements for each district.
Building Permit Pre-Submittal Meeting:
For new buildings, please schedule a pre-submittal meeting for any new
commercial or multi-family building with Building Services for this project.
Pre-Submittal meetings assist the designer/builder by assuring, early on in the
design, that the new projects are on track to complying with all of the adopted
City codes and Standards.
Department: Outside Agencies
Contact: Marcus Petty, Comcast, marcus_petty@comcast.com
Topic: General
Comment Number: 1
06/30/2023: Comcast will be able to provide service to this location.
Department: Water Conservation
Contact: Eric Olson eolson@fcgov.com 970-221-6704
Topic: General
Comment Number: 1
03/14/2023: FOR INFORMATION: Irrigation plans are required no later than at
the time of building permit. The irrigation plans must comply with the provisions
outlined in Section 3.2.1(J) of the Land Use Code. Direct questions concerning
irrigation requirements to Eric Olson, at 221-6704 or eolson@fcgov.com
RIPLEY DESIGN RESPONSE: Final Irrigation plans shall be provided at time of Building Permit.