HomeMy WebLinkAboutWORTHINGTON STORAGE - FDP220016 - SUBMITTAL DOCUMENTS - ROUND 6 - Supporting Documentation (4)Worthington Storage
Water Service Sizing
April 3, 2024
Reference: 2014 AWWA M22
Fixture Description
Nu
m
b
e
r
o
f
F
i
x
t
u
r
e
s
Fi
x
t
u
r
e
V
a
l
u
e
a
t
6
0
p
s
i
To
t
a
l
F
i
x
t
u
r
e
V
a
l
u
e
a
t
6
0
p
s
i
Pr
e
s
s
u
r
e
A
d
j
u
s
t
m
e
n
t
F
a
c
t
o
r
To
t
a
l
F
i
x
t
u
r
e
V
a
l
u
e
Water Closet (Public, General Use, Flush Valve)2 24 48 0.67 32.16
Lavatory (Public, General Use)2 0.5 1 0.67 0.67
Drinking Fountain (Public, General Use)1 2 2 0.67 1.34
Combined Fixture Value Total 51 34.17
Water Flow Demand from Fig. 4-2, upper curve (gpm)41
Water Flow Demand from Fig. 4-2, lower curve (gpm)20
Service Line and Meter Size (inches)1