Loading...
HomeMy WebLinkAboutWORTHINGTON STORAGE - FDP220016 - SUBMITTAL DOCUMENTS - ROUND 6 - Supporting Documentation (4)Worthington Storage Water Service Sizing April 3, 2024 Reference: 2014 AWWA M22 Fixture Description Nu m b e r o f F i x t u r e s Fi x t u r e V a l u e a t 6 0 p s i To t a l F i x t u r e V a l u e a t 6 0 p s i Pr e s s u r e A d j u s t m e n t F a c t o r To t a l F i x t u r e V a l u e Water Closet (Public, General Use, Flush Valve)2 24 48 0.67 32.16 Lavatory (Public, General Use)2 0.5 1 0.67 0.67 Drinking Fountain (Public, General Use)1 2 2 0.67 1.34 Combined Fixture Value Total 51 34.17 Water Flow Demand from Fig. 4-2, upper curve (gpm)41 Water Flow Demand from Fig. 4-2, lower curve (gpm)20 Service Line and Meter Size (inches)1