HomeMy WebLinkAboutFORT COLLINS RESCUE MISSION - FDP230022 - SUBMITTAL DOCUMENTS - ROUND 2 - Supporting Documentation (2)TOTAL
FIXTURE FIXTURE
NO. VALUE VALUE
OF AT AT
FIXTURE DESCRIPTION FIXTURES 60 PSI 60 PSI
WATER CLOSET (PUBLIC, GENERAL USE, FLUSH VALVE) 41 24 984
LAVATORY (PUBLIC, GENERAL USE) 44 0.5 22
DRINKING FOUNTAIN (PUBLIC, GENERAL USE) 9 2 18
SHOWER (PUBLIC, GENERAL USE)33 2.5 82.5
KITCHEN SINK/DISPOSAL/DISHWASHER (PUBLIC, GENERAL USE) 6 3.1 18.6
BAR SINK (PUBLIC, GENERAL USE)9 1.8 16.2
CLOTHESWASHER (PUBLIC, GENERAL USE, MORE THAN 3 UNITS TOTAL) 18 3 54
MOP SINK (PUBLIC, GENERAL USE)4 4 16
HOSE BIBB (PUBLIC, GENERAL USE, FIRST UNIT) 1 12 12
HOSE BIBB (PUBLIC, GENERAL USE, EACH ADDITIONAL UNIT) 13 12 156
COMBINED FIXTURE VALUE TOTAL 1379.3
CUSTOMER PEAK DEMAND FROM FIGURE 4-2 OR 4-3 RESIDENTIAL APARTMENTS, MOTELS, CONDOS (GPM)66
CUSTOMER PEAK DEMAND FROM FIGURE 4-2 OR 4-3 COMMERCIAL HOTELS, RETAIL, RESTAURANTS, PUBLIC BUILDINGS (GPM)136
TAP AND METER SERVICE SIZE (INCHES)3
FORT COLLINS RESCUE MISSION
DOMESTIC WATER SERVICE SIZING
2014 AWWA M22 CRITERIA