HomeMy WebLinkAboutFORT COLLINS RESCUE MISSION - FDP230022 - SUBMITTAL DOCUMENTS - ROUND 2 - Electrical PlansDETAIL NOTE DESIGNATION
MECHANICAL EQUIPMENT DESIGNATION
CONDUIT DOWN
CONDUIT UP
CONDUIT CAP
ELECTRICAL WIRE SIZE
DELTA REVISION NOTE
HOMERUN ARROWS
CONDUIT CONTINUATION
.
.
.
.
WEATHER PROOF/GROUND FAULT INTERRUPTING
PARTIAL CIRCUIT USED IN MULTIPLE LOCATIONS
EXISTING TO BE REMOVED
EXISTING TO BE RELOCATED
INSTA HOT
HOUSE PHONE
SAME AS (P)
UNLESS OTHERWISE NOTED
GROUND FAULT INTERRUPTING
ELECTRICAL WATER COOLER
TELEPHONE TERMINAL BOARD
WEATHER PROOF
UON
WG
WP
HP
(PART)
TTB
(P)
IH
ER
EX
GFCI
EWC
GROUNDED SINGLE RECEPTACLE
GROUNDED SWITCHED DUPLEX/QUAD RECEPTACLE
GROUNDED DUPLEX RECEPTACLE
SUBSCRIPT = AMPACITY.
GROUNDED SPLIT-WIRED RECEPTACLE
FLOOR MOUNTED FOUR PLEX RECEPTACLE
FLOOR MOUNTED SPECIAL PURPOSE RECEPTACLE
SPECIAL PURPOSE RECEPTACLE
FOUR PLEX RECEPTACLE
FLOOR MOUNTED RECEPTACLE
TELEPHONE/DATA OUTLET
FLOOR MOUNTED TELEPHONE/DATA OUTLET
FLOOR MOUNTED TELEPHONE OUTLET
ELECTRICAL LEGEND
ELECTRICAL PANELBOARD RECESSED MOUNTING
ELECTRICAL PANELBOARD SURFACE MOUNTING
EQUIPMENT NON-FUSED DISCONNECT SWITCH
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
TELEPHONE TERMINAL BOARD
MAGNETIC CONTROLLER (STARTER)
EQUIPMENT FUSED DISCONNECT SWITCH
COMBINATION STARTER/DISCONNECT SWITCH
FLOOR MOUNTED JUNCTION BOX
SWITCH & RECEPTACLE COMBINATION
FLOOR MOUNTED DATA OUTLET
SPEAKER - PAGING AND OR SOUND SYSTEM
CURRENT TRANSFORMER
NORMALLY CLOSED CONTACT
NORMALLY OPEN CONTACT
BREAKER WITH DRAWOUT FEATURE
PHOTOCELL
FUSED SWITCH
GROUND
POWER TRANSFORMER
CIRCUIT BREAKER
P
METER
CONTACTOR
RELAY
TRANSFORMER
THERMOSTAT
BATTERY
SOLENOID VALVE
C
S
B
T
SV
T
R
MCC
M
PULL BOXPB
DATA OUTLET
JUNCTION BOX
WALL MOUNTED J-BOX
1, 2, OR 3 BUTTON STATION
J
J
J
MOTOR
PLUG MOLD
CLOCK RECEPTACLE
TELEPHONE OUTLET
HP
PM
ABOVE COUNTER/GROUND FAULT INTERRUPTING
BATTERY PACK EMERGENCY LIGHT
EXIT LIGHT - SHADED INDICATES FACE
3-WAY SWITCH
4-WAY SWITCH
DIMMER SWITCH
SINGLE POLE SWITCH
DOUBLE POLE SWITCH
WALL MOUNTED VACANCY SENSOR SWITCH
KEY OPERATED SWITCH
THERMAL OVERLOAD SWITCH
ABOVE FINISH FLOOR
CIRCUIT
EXHAUST FAN
ARC-FAULT CIRCUIT INTERRUPTER
ABOVE COUNTER - VERIFY HEIGHT
EXISTING TO REMAIN
ELECTRICAL CONTRACTOR
AG
CCT
EC
EF
E
TO
AFF
AC
AFCI
3
4
K
D
P
2
DUCT FIRE DETECTOR (SUPPLY)
REMOTE INDICATING LIGHT
VOLUME CONTROL
CEILING FIXTURE
120V. MOTORIZED SMOKE DAMPER
FIRE / SMOKE DAMPER
WALL MOUNTED FIXTURE
RECESSED LIGHT FIXTURE
SURFACE MOUNTED LIGHT FIXTURE
STRIP LIGHT FIXTURE
WALL WASHER
PORCELAIN LAMP HOLDER
SURFACE CEILING FIXTURE
POLE MOUNTED FIXTURE
WALL PACK FIXTURE
EMERGENCY FIXTURE - SHADED
TRACK HEAD FIXTURE
K
V
M
S
FIRE ALARM HORN
FIRE STROBE
FIRE ALARM HORN & LIGHT
FIRE HORN OR SPEAKER WITH STROBE
MANUAL PULL STATION
FIRE ALARM ANNUNCIATOR
FIRE ALARM PANEL
TAMPER SWITCH
I = IONIZATION
SMOKE DETECTOR
FIRE ALARM FLOW SWITCH
MAGNETIC DOOR HOLDER
FIRE THERMAL DETECTOR
P = PHOTOELECTRIC
DUCT FIRE DETECTOR (RETURN)
FIRE ALARM ANNUNCIATOR CONTROL PANEL
TS
S
R
T
FS
MH
FAP
FAA
S
FACP
CEILING MOUNTED OCCUPANCY SENSOR
WALL MOUNTED OCCUPANCY SENSOR
SWITCH WITH INTEGRATED OCCUPANCY SENSOROS
M
SWITCH & PILOT LAMP
VS
CEILING MOUNTED VACANCY SENSORVS
POWER/DATA POKE-THRU
POWER ONLY POKE-THRU
KITCHEN EQUIPMENT DESIGNATIONK-XXX
POWER/TELEPHONE POLETP
TELEVISION OUTLET
BUZZER
CHIME
B
FLOOR MOUNTED TELEVISION OUTLET
RESIDENTIAL COMMUNICATION CENTER
CARD READERCR
TRACK WITH TRACK HEAD FIXTURE
COMBO GROUNDED DUPLEX RECEPTACLE AND
USB / USB-C CHARGING PORTUSB
TWO WAY COMMUNICATIONTWC
WIRELESS ACCESS POINTWAP
COMBINATION CO/SMOKE DETECTOR
S/CO
CC
NOTE: NOT ALL SYMBOLS ARE
NECESSARILY USED ON THIS PROJECT.
SURFACE MOUNTED DEVICE(S)
XXXX/W
CEILING MOUNTED DAYLIGHT SENSORDS
DETAIL NOTES
1 PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED PER 2023
NEC 250, INCLUDING METAL UNDERGROUND WATER PIPE, METAL
FRAME OF THE BUILDING, CONCRETE-ENCASED ELECTRODE, AND
ROD AND PIPE ELECTRODES.
2 SURGE PROTECTION DEVICE. PROVIDE CIRCUIT BREAKER AND
WIRE AS SIZED BY MANUFACTURER.
3 PANEL SHALL BE PROVIDED WITH METERING BREAKERS AS
REQUIRED TO COMPLY WITH 2021 IECC C405.12. HVAC LOADS,
INTERIOR LIGHTING, EXTERIOR LIGHTING, PLUG LOADS, PROCESS
LOADS, AND REMAINING LOADS SHALL BE SEPARATELY METERED
AND METER DATA SHALL BE ACQUIRED AND STORED IN
COMPLIANCE WITH IECC C405.12.5. BASIS OF DESIGN IS SIEMENS
SEM3 SERIES METERING SYSTEM. ALTERNATE APPROVED EQUALS
ARE ACCEPTABLE. PROVIDE THROUGH- WIRING AND
COMMUNICATION LINES AS REQUIRED. COORDINATE WITH
MANUFACTURER.
4 CIRCUIT BREAKER MOUNTING SPACE FOR FUTURE PV SYSTEM. PER
2023 NEC 705.12(B)(2)(3)(B) PV SYSTEM CIRCUIT BREAKER SHALL BE
INSTALLED AT THE END OF THE BUS. PROVIDE PERMANENT
WARNING LABEL.
5 LIGHTING CONTROL PANEL (LCP). PROVIDE A FEED THROUGH
LIGHTING CONTROL PANEL. PANEL SHALL HAVE DIMMING MODULES
FOR CONTROL OF EXTERIOR LIGHT FIXTURES. MODULES SHALL BE
SUITABLE FOR LED, 0-10V, ELV, MLV AND FLUORESCENT LIGHT
FIXTURES. LCP SHALL HAVE PHOTOCELL AND ASTRONOMIC
TIMECLOCK CONTROL.
6 ROUTE CONDUIT TO SOLAR READY ZONE AT ROOF. BENDS NOT TO
EXCEED 270° WITHOUT ACCESSIBLE PULL BOX. FIELD COORDINATE
ROUTING WITH ARCHITECT PRIOR TO ROUGH-IN.
7 PROVIDE A REMOTE GENERATOR ANNUCIATOR/CONTROLLER.
CONFIRM LOCATION WITH FIRE DEPARTMENT PRIOR TO ROUGH-IN.
PROVIDE CONTROL PANEL IN GENERATOR WITH TCP/IP INTERFACE
FOR MONITORING AND CONTROL.
GENERAL NOTES
1.PROVIDE INCREASED FEEDER CONDUCTOR SIZES AS REQUIRED TO
ACCOMMODATE VOLTAGE DROP. MAXIMUM VOLTAGE DROP
ALLOWED AT PANELS IS 3%. PROVIDE ALL NECESSARY JUNCTION
BOXES AND SPLICES AS REQUIRED TO REDUCE OVERSIZED
CONDUCTORS IN ORDER TO TERMINATE ON PANELBOARD LUGS.
2.PROVIDE SLEEVES AS REQUIRED FOR VERTICAL ROUTING OF
FEEDERS. RACEWAYS ON LEVELS ABOVE THE PARKING GARAGE
SHALL BE CONCEALED. ROUTE THROUGH WALLS AS REQUIRED.
COORDINATE SLEEVE LOCATIONS AND RACEWAY ROUTING WITH
STRUCTURAL ENGINEER AND GENERAL CONTRACTOR PRIOR TO
ROUGH-IN.
3.MAINTAIN FIRE RATING OF ALL PENETRATIONS.
4.ELECTRICAL EQUIPMENT MUST FIT IN THE SPACE PROVIDED WHILE
MAINTAINING ALL CLEARANCE AND WORKING SPACE
REQUIREMENTS.
5.ALUMINUM ALLOY CONDUCTORS SHALL BE PERMITTED WHERE
ALLOWED BY THE NEC EXCEPT TO ROTATING EQUIPMENT INCLUDING
MECHANICAL EQUIPMENT AND ELEVATORS.
6.ALUMINUM BUSSING IS PERMITTED IN ALL ELECTRICAL EQUIPMENT.
7.APPLICABLE OVERCURRENT PROTECTION DEVICES SHALL COMPLY
WITH ARC ENERGY REDUCTION REQUIREMENTS OF NEC 240.87.
UTILITY
METER
5
T1
M
LEVEL 1
SPD
N
G
4000/3
2
SERVICE
GROUND 1
800/3
4
MAIN SWITCHBOARD 1 - MSB-1:
4000A, 120/208V, 3Ø, 4-WIRE,
100,000 AIC, NEMA-3R
1
E0.1
ELECTRICAL ONE-LINE DIAGRAM
NO SCALE
(3)3"C.6
LEVEL 2
PAD MOUNTED UTILITY
TRANSFORMER
120/208V SECONDARY
1200/3
PANEL
M2N
3
600/3
PANEL
M1S
3
400/3
PANEL
K
3
225/3
PANEL
L1SA
3
PANEL
LTG.
5
LCP-L1 PANEL
L1SB
3
400/3
PANEL
L1NA
3
PANEL
LTG.
5
LCP-L1 PANEL
L1NB
3
250/3
PANEL
L2NA
3
PANEL
L2NB
3
FEEDER SCHEDULE ALUMINUM
4000/W
3000/W
2500/W
2000/W
1600/W
1200/W
1000/W
800/W
750/W
600/W
500/W
400/W
350/W
300/W
250/W
225/W
200/W
175/W
150/W
125/W
100/W
90/W
80/W
70/W
60/W
50/W
40/W
THIS TABLE INDICATES MINIMUM CONDUCTOR SIZE
FOR FEEDERS OF THE AMPACITY INDICATED
WHERE #/W INDICATES THE #-AMPACITY AND
W-NUMBERS OF WIRE, #S/W INDICATES NO
GROUND. ALL CONDUCTORS SHALL BE ALUMINUM
UNLESS NOTED OTHERWISE.
*CONDUCTOR AMPACITIES SHALL BE BASED ON
TABLE 310.15(B)(16) 60 DEGREE COLUMN UP TO
100 AMPS AND 75 DEGREE COLUMN ABOVE 100
AMPS UNLESS OTHERWISE PERMITTED BY NEC.
AMPACITY RATING SHALL BE SELECTED IN
ACCORDANCE WITH NEC 110.14 (C).
THE MASTER ELECTRICIAN SHALL BE RESPONSIBLE
FOR ENSURING THAT NO FEEDERS OR BRANCH
CIRCUITS ARE INSTALLED IN A MANNER OR SIZED
IN SUCH A WAY AS TO VIOLATE NEC
SERVICE
GROUND
TABLE
150G/CU #6
200G/CU #4
300G/CU 2
500G/CU 1/0
1000G/CU 2/0
>1000G/CU 3/0
SERVICE GROUND CONDUCTORS SIZED PER NEC
TABLE 250.66 EQUIPMENT GROUND CONDUCTORS
SIZED PER NEC TABLE 250.122 ALL CONDUCTORS
SHALL BE ALUMINUM UNLESS NOTED OTHERWISE
THE SERVICE GROUND CHART INDICATES THE
MINIMUM SERVICE GROUND CONDUCTOR BASED
ON #G WHERE # IS THE AMPACITY FROM THE
CHART ABOVE, AND THE EQUIPMENT GROUND
CHART INDICATES THE MINIMUM EQUIPMENT
GROUNDING CONDUCTOR SIZE #EG WHERE # IS
THE RATING/SETTING OF THE OVERCURRENT
DEVICE PROTECTING THE CONDUCTORS
AND EQUIPMENT
WHERE DISCREPANCIES OCCUR BETWEEN THE
FEEDER SCHEDULE SCHEDULE AND THE
GROUNDING TABLES, THE LARGER CONDUCTOR
SHALL BE USED UNLESS OTHERWISE PERMITTED
BY THE NEC.
THE INSTALLATION SHALL MEET ALL NEC 250
GROUNDING AND BONDING REQUIREMENTS
INCLUDING 250.4 PATH FOR FAULT CURRENT.
PROVIDE COMPLETE RACEWAY SYSTEMS
METALLICALLY JOINED, CONNECTED, AND
FITTINGS AS REQUIRED FOR ELECTRICAL
CONTINUITY PER NEC 300.10
13[W-500kcmil, 750kcmilG, 4"C]
8[W-700kcmil, 600kcmilG, 4"C]
7[W-700kcmil, 600kcmilG, 4"C]
6[W-600kcmil, 400kcmilG, 4"C]
5[W-600kcmil, 350kcmilG, 4"C]
4[W-500kcmil, 250kcmilG, 3-1/2"C]
4[W-350kcmil, 4/0G, 3"C]
3[W-400kcmil, 3/0G, 3"C]
3[W-350kcmil, 3/0G, 3"C]
2[W-500kcmil, 2/0G, 3-1/2"C]
2[W-350kcmil, 1/0G, 3"C]
2[W-250kcmil, #1G, 3"C]
2[W-4/0, #1G, 2-1/2"C]
W-500kcmil, #2G, 3-1/2"C
W-350kcmil, #2G, 3"C
W-300kcmil, #2G, 3"C
W-250kcmil, #4G, 3"C
W- 4/0, #4G, 2-1/2"C
W- 3/0, #4G, 2"C
W- 2/0, #4G, 2"C
W-1/0, #6G, 2"C
W-1/0, #6G, 2"C
W#1, #6G, 1-1/2"C
W#2, #6G, 1-1/4"C
W#2, #8G, 1-1/4"C
W#4, #8G, 1-1/4"C
W#6, #8G, 1"C
EQUIPMENT
GROUND
TABLE
20EG #10
60EG #8
100EG #6
200-1200A PER ABOVE
1600EG 350KCMIL
2000EG 400KCMIL
1200/3
DWH
1
400/3
DWH
2
(2)400/3
SPARE
4000S/4
1200/4 600/4 400/4 250/4 400/4 225/4 1200/4 400/4
1 2
3
4 5
6
7
8
9
10
11
12 13
SHORT CIRCUIT CALCULATIONS BASED ON BUSSMAN POINT TO POINT METHOD.
SHORT CIRCUIT SCHEDULE
POINT
X1
X2
X3
X4
X5
X6
X7
X8
X9
X10
X11
X12
X13
Three (3) phase Line to Line Short Circuit Calculations:
The same calculations for single (1) phase Line to Line, F value changes:
The same calculations for the fault current at the secondary side of a transformer, F value changes:
For multiple conductors per phase, the single conductor C value from the table is multiplied by the number of conductors per phase.
NOTES:
1.
DESCRIPTION
UTILITY TRANSFORMER
MAIN SWITCHBOARD MSB-1
PANEL M2N
PANEL M1S
PANEL K
PANEL L2NA
PANEL L2NB
PANEL L1NA
PANEL L1NB
PANEL L1SA
PANEL L1SB
DWH 1
DWH 2
Is.c = (Iavailable)*M
M = 1/(1+F)
F = (1.732 x L x Iavailable3Ø)/(C x V)
C = values found in BUSSMANN SPD Handbook for conductors and busway
V = the line to line voltage
L = length of run in feet
F = (2 x L x Iavailable1Ø)/(C x V)
F = (IscPrimary x Vprimary x 1.732 x %Z)/(100,000 x kVAtrans)
"Length of Run" is shown for calculations only, and should not be used for bidding purposes.
Short
Circuit
ISC SYM RMS
52,190
50,331
39,342
32,292
26,996
21,387
20,446
26,996
26,031
20,080
19,159
39,342
26,996
Multiplier
M
0.964
0.782
0.642
0.536
0.425
0.956
0.536
0.964
0.399
0.954
0.782
0.536
F factor
F
0.037
0.279
0.559
0.864
1.353
0.046
0.864
0.037
1.507
0.048
0.279
0.864
Constant
C
235,301
75,024
37,512
24,244
15,484
15,484
24,244
24,244
13,910
13,910
75,024
24,244
Line-Line
Voltage
V
208
208
208
208
208
208
208
208
208
208
208
208
Length
of run
L
20
50
50
50
50
4
50
4
50
4
50
50
I
available
I
52,190
50,331
50,331
50,331
50,331
21,387
50,331
26,996
50,331
20,080
50,331
50,331
Xfmer
Rated
kVA
-----
-----
-----
-----
-----
-----
-----
-----
-----
-----
-----
-----
Xfmer
Imped
%Z
-----
-----
-----
-----
-----
-----
-----
-----
-----
-----
-----
-----
G 400/3
G
TEMPORARY
GENERATOR
125kW/156.3kVA RATED (AT SITE
ELEVATION), NATURAL GAS
NON-EMERGENCY GENERATOR.
7
TAP
BOX
TRYSTAR 400/3 MANUAL
TRANSFER SWITCH "MTS-GEN"
WITH INTEGRAL TAP BOX FOR
TEMP GENSET CONNECTION
N
G
BOND TO
SERVICE
GROUND
PANEL
ST1
SPD2
3
ATS-ST
400/3
4-POLE
PANEL
ST2
SPD2
3
400/3
400/4400/4
400/4
400/4
DESIGNED UNDER THE FOLLOWING CODES:
CITY OF FT. COLLINS REQUIREMENTS AND CODE AMENDMENTS AND
FPD REQUIREMENTS
2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL ENERGY CONSERVATION CODE
2021 INTERNATIONAL FIRE CODE
2023 NATIONAL ELECTRICAL CODE
CODES:
1/8" = 1'-0"
ELECTRICAL
ONE-LINE
E0.01
E0.01.dwg
PROJECT #:
DRAWN:
REV:
SCALE:
NO.
SHEET TITLE:
REVIEWED:
DATE:
FILE:
12345
A
B
C
D
6
E
7
1234567
A
B
C
D
E
FO
R
T
C
O
L
L
I
N
S
R
E
S
C
U
E
M
I
S
S
I
O
N
13
1
1
N
.
C
O
L
L
E
G
E
F
O
R
T
C
O
L
L
I
N
S
C
O
L
O
R
A
D
O
J:
\
2
0
2
3
\
2
0
2
3
-
0
1
9
-
0
0
\
C
a
d
\
E
l
e
c
\
E
0
.
0
1
.
d
w
g
R
o
b
e
r
t
C
0
2
.
0
8
.
2
4
1
1
:
3
1
a
m
J:
\
2
0
2
3
\
2
0
2
3
-
0
1
9
-
0
0
\
C
a
d
\
E
l
e
c
\
E
0
.
0
1
.
d
w
g
R
o
b
e
r
t
C
0
2
.
0
8
.
2
4
1
1
:
3
1
a
m
MTV
SCHEMATIC DESIGN
MTV
07/24/2023
2023-019-00