April 11, 2018
970.221.6750
970.224.6134 - fax
fcgov. con�/develo pmentrevrew
David Houts
Houts Development & Construction LLC
5102 Daylight Ct
Fort Collins, CO 80528
RE: Sunrise Ridge Second Filing Major Amendment, MJA180002, Round Number 1
�
Community Development and
Neighborhood Services
281 North College Avenue
PO Box 580
Fort Collins, CO 80522
.ti-.
^pJ',SE, ��aG
, ,,, ; ��,,s
�.�,�,� �rE
_�
Please see the following summary of comments from City staff and outside reviewing
agencies for your submittal of the above referenced project. If you have questions about
any comments, you may contact the individual commenter or direct your questions through
the Project Planner, Ted Shepard, at 970-221-6343 or tshepard@fcqov.com,
Applicate Comments!Reply in Red — 4/25%�$
Comment Summary:
Department: Engineering Development Review
Contact: Spencer Smith, , ssmith(�a fcgov.com
Topic: General
Comment Number: 1 Variance processing
r�
u
Comment Originated: 04/10/2018
Engineering would prefer that the applicant explore all site layout options to
allow Lot 1 to access Sunglow Ct., as was previously approved for this filing. If
it is determined that the proposed configuration is unable to utilize an access to
Sunglow Ct., then a shared direct access to Rock Creek Dr. would be
considered. An access to Rock Creek Dr. would have to meet all applicable
Larimer County Urban Area Street Standards (LCUASS) for location, spacing,
width, etc. Specifically refer to Chapters 7 and 9 for detailed criteria. Variance
requests will need to be submitted to Engineering for review and approval.
Comment Number: 2 Utility plan to be revised as needed Comment Originated: 04/10/2018
Utility plans will need to be submitted for review and approval by the City as part
of this project. Utility plans will need to show proposed dnveway locations,
existing curb and gutter removals, driveway details, etc., as well as any other
public improvements proposed/required with this project (stormwater, etc.).
�
Comment Number: 3 Amendment Doc as required
•
Comment Originated: 04/10/2018
If an access is going to be approved to Rock Creek Dr., the existing
Development Agreement (DA) will need to be amended. Currently, the
approved DA specifically prohibits driveway access to Rock Creek Dr.
Comment Number: 4 Paid with app fee
Comment Originated: 04/10/2018
The City's Transportation Development Review Fee (TDRF) is due at the time
of submittal. For additional inforrnation on these fees, please see:
http://www.fcgov.com/engineering/dev-review.php
Comment Number: 5 Noted Comment Originated: 04/10/2018
Any damaged curb, gutter and sidewalk existing prior to construction, as well as
streets, sidewalks, curbs and gutters, destroyed, damaged or removed due to
construction of this project, shall be replaced or restored to City of Fort Collins
standards at the Developer's expense prior to the acceptance af completed
improvements and/or prior to the issuance of the first Certificate of Occupancy.
Comment Number: 6 Noted
Comment Onginated; 04/10/2018
All public sidewalk, driveways and ramps, existing or proposed, adjacent or
within the site, need to meet ADA standards. If they currently do not, they will
need to be reconstructed so that they do meet current ADA standards as a part
of this project.
Comment Number: 7 Noted
Comment Originated: 04/10/2018
Any public improvements must be designed and built in accordance with the
LCUASS. They are available online at:
http://www.larimer.org/engineering/GMARdStds/UrbanSt.htm
Comment Number: 8 Noted
Comment Originated: 04/10/2018
As of January 1, 2015, all development plans are required to be on the
NAVD88 vertical datum. Please make your consultants aware of this, prior to
any surveying and/or design work.
Comment Number: 9 N/A
Comment Originated: 04/10/2018
A Development Construction Permit (DCP) will need to be obtained prior to
starting any work on the site.
Comment Number: 10 Noted
Comment Originated: 04/10/2018
All fences, barriers, posts or other encroachments within the public right-of-way
are only permitted upon approval of an encroachment permit. Applications for
encroachment permits shall be made to the Engineering Department for review
and approval prior to installation. Encroachment items shall not be shown on the
site plan as they may not be approved, need to be modified or moved, or if the
permit is revoked then the site/ landscape plan is in non-compliance.
Comment Number: 11 Noted
Comment Originated: 04/10/2018
With regards to construction of this site, the public right-of way shall not be used
for staging or storage of materials or equipment associated with the
Development, nor shall it be used for parking by any contractors,
subcontractors, or other personnel working for or hired by the Developer to
construct the Development. The Developer will need to find a location(s) on
private property to accommodate any necessary staging and/or parking needs
2
associated with th�mpletion of the Development. Informatio�n the
location(s) of these areas will be required to be provided to the City as a part of
the Development Construction Permit application.
Department: Environmental Planning
Contact: Rebecca Everette, 970-416-2625, reverette fcgov.com
Topic: General
Comment Number: 1 No — All proposed to remain Comment Onginated: 04/09/2018
04/09/2018: LANDSCAPE PLAN: Will any of the Ponderosa pine trees along
the southern boundary be impacted by the proposed changes? If so, pfease
show those to be planted elsewhere on the site.
Comment Number: 2 Changes noted on Site Plan Comment Originated: 04/09/2018
04/09/2018: LANDSCAPE PLAN: Please replace the 9 Patmore Ash trees
with a non-ash species. The City does not allow the planting of new ash trees as
they are vulnerable to a future emerald ash borer infestation.
Please see the Fort Collins Plant List for approved species:
https://www.fcgov.com/forestrylplant_list.pdf
Comment Number: 3 Change �oted on Site Plan Comment Originated: 04/09/2018
04/09/2018: LANDSCAPE PLAN: Please remove Lincoln Smooth Brome from
the seed mix for the sod areas, as it is no longer an acceptable species in Fort
Collins.
Comment Number: 4 Added ta Site Pian Comment Originated
04/09/2018: SITE AND LANDSCAPE PLAN: Please update the site and
landscape plans with the current City of Fort Collins standard notes, which can
be found here:
Comment Number: 5 Added to Site Plan Comment Originated
04/09/2018: LANDSCAPE PLAN: Please add the following notes to the
landscape plans for the dryland seed mix:
NATIVE SEED MIX NOTES
1. PREPARE SOIL AS NECESSARY AND APPROPRIATE FOR NATIVE
SEED MIX SPECIES THROUGH AERATION AND ADDITION OF
AMENDMENTS, THEN SEED IN TWO DIRECTIONS TO DISTRIBUTE SEED
EVENLY OVER ENTIRE AREA. DRILL SEED ALL INDICATED AREAS AS
SOON AS POSSIBLE AFTER COMPLETION OF GRADING OPERATIONS.
2. IF CHANGES ARE TO BE MADE TO SEED MIX BASED ON SITE
CONDITIONS THEN APPROVAL MUST BE PROVIDED BY CITY
ENVIRONMENTAL PLANNER.
3. APPROPRIATE NATIVE SEEDING EQUIPMENT WILL BE USED
(STANDARD TURF SEEDING EQUIPMENT OR AGRICULTURE EQUIPMENT
SHALL NOT BE USED).
4. DRILL SEED APPLICATION RECOMMENDED PER SPECIFIED
APPLICATION RATE TO NO MORE THAN 1/2 INCH DEPTH. FOR
BROADCAST SEEDING INSTEAD OF DRILL SEEDING METHOD DOUBLE
04/09/2018
04/09/2018
3
SPECIFIED APPLICATION RATE. REFER TO NATIVE SEED �TABLE
FOR SPECIES, PERCENTAGES AND APPLICATION RATES.
5. PREPARE A WEED MANAGEMENT PLAN TO ENSURE THAT WEEDS
ARE PROPERLY MANAGED BEFORE, DURING AND AFTER SEEDING
ACTIVITIES.
6. AFTER SEEDING THE AREA SHALL BE COVERED WITH CRIMPED
STRAW, JUTE MESH, OR OTHER APPROPRIATE METHODS.
7. WHERE NEEDED, TEMPORARY IRRIGATION SHOULD BE PROVIDED
UNTIL SEED IS ESTABLISHED. IF IRRIGATION IS USED, THE IRRIGATION
SYSTEM FOR SEEDED AREAS SHALL BE FULLY OPERATIONAL AT THE
TIME OF SEEDING AND SHALL ENSURE 100% HEAD-TO-HEAD
COVERAGE OVER ALL SEEDED AREAS. ALL METHODS AND
REQUIREMENTS IN THE APPROVED IRRIGATION PLAN SHALL BE
FOLLOWED.
8. CONTRACTOR SHALL MONITOR SEEDED AREA FOR PROPER
IRRIGATION, EROSION CONTROL, GERMINATION AND RESEEDING AS
NEEDED TO ESTABLISH COVER.
9. THE APPROVED SEED MIX AREA IS INTENDED TO BE MAINTAINED IN
A NATURAL LIKE LANDSCAPE AESTHETIC. IF AND WHEN MOWING
�CCURS IN NATIVE GRASS SEED MIX AREAS DO NOT MOW LOWER
THAN 6 TO 8 INCHES IN HEIGHT TO AVOID INHIBITING NATIVE PLANT
GROWTH.
10. NATIVE SEED AREA WILL BE CONSIDERED ESTABLISHED WHEN
SEVENTY PERCENT VEGETATIVE COVER IS REACHED WITH NO
LARGER THAN ONE FOOT SQUARE BARE SPOTS AND/OR UNTIL
DEEMED ESTABLISHED BY CITY PLANNING SERVICES AND EROSION
CONTROL.
11. THE DEVELOPER AND/OR LANDSCAPE CONTRACTOR IS
RESPONSIBLE FOR ADEQUATE SEEDLING COVERAGE AND GROWTH
AT THE TIME OF FINAL STABILIZATION, AS DEFINED BY STATE AND
LOCAL AGENCIES. IF FINAL STABILIZATION IS NOT ACHIEVED TO THE
SATISFACTION OF THE AGENCY, THE DEVELOPER AND/OR
LANDSCAPE CONTRACTOR SHALL BE RESPONSIBLE FOR ADDITIONAL
CORRECTIVE MEASURES TO SATISFY FINAL VEGETATIVE
REQUIREMENTS FOR CLOSEOUT.
Department: Forestry
Contact: Molly Roche, , mroche _ fcgov.com
Topic: Landscape Plans
Comment Number: 1 Tree list updated Comment Originated: 04/10/2018
4/9/2018:
Thank you for providing the approved landscape plan from 2006. Since then,
the City of Fort Collins is not allowing any Ash species to be planted within City
Limits and especially not on City right-of-way. The invasive pest, Emeraltl Ash
Borer, will eventually reach Fort Collins and kill all untreated Ash trees. In an
effort to diversify the urban forest as well as to prevent the removal of more Ash
trees, please do not plant Fraxinus pennsylvanica as a part of this development.
4
Please plant an al�ative species such as Kentucky Coffeetre�Hackberry
in place of the (9� proposed Ash.
Comment Number: 2 Reviewed and confirmed Comment Originated: 04/10/2018
4/9/2018:
Please use the most current City of Fort Collins General Landscape Notes,
Tree Protection Notes, Street Tree Notes, and street tree permit note. These
notes are available from City Forestry (Molly Roche — mroche@fcgov.com).
Comment Number: 3 Noted and added Comment Originated: 04/10/2018
4/9/2018:
Please show irrigatetl turf in the right-of-way (area between curb and sidewalk)
and provide a detail in the legend.
Department: Light And Power
Contact: Luke Unruh, 9704162724, lunruh(a�fc�ov.com
Topic: General
Comment Number: 1 NfA
Comment Originated: 04/10/2018
04/10/2018: Light & Power has no comments to add regarding this major
amendment.
Department: PFA
Contact: Andrew Rosen,
Topic: General
, arosen fcgov.com
Comment Number: 1 Noted
Comment Originated: 04/05/2018
04/05/2018:
SPRINKLER SYSTEM
These proposed duplexes will be built under the IRC and it is my understanding
that, as of 2014, they be will be designed with an automated fire sprinkler
system. Please contact the Building Department to verify.
Comment Number: 2 Noted Comment Originated: 04/05/2018
04/05I2018:
ACCESS
Access is required to within 150ft of all portions of the exterior penmeter of
each residence. Dnveways built to Fire Lane standards (please see comment 3
below) can be utilized to achieve this access requirement. Part of an out of
access condition may be mitigated by the residential spnnkler system with
approval of the fire marshal.
Comment Number: 3 Noted Comment Originated: 04/05/2018
04/05/2018:
FIRE LANE SPECIFICATIONS
A fire lane plan shall be submitted for approval prior to installation. In addition to
the design criteria already contained in relevant standards and policies, any
new fire lane must meet the following general requirements:
> Shall be designated on the plat or by separate document as an Emergency
Access Easement.
> Maintain the required 20 foot minimum unobstructed width & 14 foot minimum
overhead clearance. Where road widths exceed 20' in width, the full width shall
be dedicated unless otherwise approved by the AHJ.
5
> Be designed as�t, hard, all-weather driving surface capab�supporting
40 tons.
> Dead-end fire access roads in excess of 150 feet in length shall be provided
with an approved area for tuming around fire apparatus.
> The required turning radii of a fire apparatus access road shali be a minimum
of 25 feet inside and 50 feet outside. Tuming radii shall be detailed on
submitted plans.
> Be visible by red curb and/or signage, and maintained unobstructed at all
times. Sign locations or red curbing should be labeled and detailed on final
plans. Refer to LCUASS detail #1418 ֋ for sign type, placement, and
spacing. Appropriate directional arrows required on alf signs.
Comment Number: 4 Noted Comment Originated
04/05/2018:
ADDRESSINGNVAYFINDING
The address for each residence shall be clearly visible from the street. Code
language follows:
IFC 505.1: New and existing buildings shall have approved address numbers,
building numbers or approved building identification placed in a position that is
plainly legible, visible from the street or road fronting the property, and posted
with a minimum of eight-inch numerals on a contrasting background.
Comment Number: 5
04/05/2018:
HYDRANT
04/05/2018
Comment Originated: 04/05/2018
A hydrant is required within 400ft of a residence. This requirement is met by the
hydrant in Sunglow Ct but it is the project team's responsibility to verify
adequate water flow and pressure.
Department: Stormwater Engineering
Contact: Dan Mogen, 970-224-6192, dmogen(a�fcgov.com
Topic: General Per Dan Mogan, Applicate processing variance for alternative compliance
Comment Number: 1 Noted Comment Originated: 03/26/2018
03/26/2018: The building locations proposed on the site plan encroach into the
setback adjacent to Tract A. This tract contains public storm sewer and
encroaching into this tract will not be acceptable. Please note that fences,
window wells, enhanced landscaping, etc. are not allowable in this 20' tract
between lots 1 and 2.
Comment Number: 2 Noted Comment Originated: 03/26/2018
03/26/2018: The increased density proposed will increase the amount of
impervious area on each lot compared to what was originally planned and
approved. Please show how this increase affects the drainage design for this
subdivision including how water quality and detention volumes are affected as
well as capacities for proposed swales. Is there adequate conveyance capacity
and will detention pond modifications be warranted?
Comment Number: 3 Noted
Comment Originated: 03/26/2018
03/26/2018: I see a note stating that overall site grading will still be in general
conformance with the original plan. Even maintaining general conformance, the
grading plan will need to be altered to accommodate additional buildings.
Please provide an updated grading plan showing how drainage will function on
0
each lot. •
Contact: Jesse Schlam, 970-218-2932, ischlam@fcgov.com
Topic: Erosion Control Noted - State permit processing
Comment Number: 4
•
Comment Originated: 03/30/2018
03/30/2018: The site disturbs more than 10,000 sq. ft. and therefore Erosion
and Sediment Control Materials need to be submitted. The erosion control
requirements can be located in the Stormwater Design Criteria under the
Amendments of Volume 3 Chapter 7 Section 1.3.3. a copy of the erosion
control requirements can be found at www.fcgov.com/eroison. The Erosion
Control Materials will need to be submitted at time of the first round of FDP.
Erosion Control Materials that were accepted for this site prior were based off
the old standards, therefore Erosion and Sediment Control Materials need to be
reworked and updated to meet the current standards then resubmitted for
review, Based upon the area of disturbance, a State permit for discharge of
stormwater from construction activity will be required since the site is over an
acre and this will need to be pulled before Construction Activities begin. If you
need clarification conceming the Erosion Control Material Requirements or
Comments presented above please contact myself. Jesse Schlam (970)
224-6015 jschlam@fcgov.com
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcounty@fcgov.com
Topic: Site Plan No#ed
Comment Number: 1
04/06/2018: All plan sheets must be 24"x36".
Comment Number: 2
04/06/2018: There are text over text issues. See redlines.
Comment Number: 3
04/06/2018: Please add the street names to the plan.
Department: Traffic Operation
Contact: Tim Tuttle, , TTUTTLE fcgov.com
Topic: General Noted
Comment Number: 1
Comment Originated: 04/06/2018
Comment Originated: 04/06/2018
Comment Originated: 04/06/2018
Comment Onginated: 04/09/2018
04/09/2018: Please coordinate with engineering on the location of the
proposed access point on Rock Creek Drive.
Comment Number: 2 Comment Originated: 04/10/2018
04/10/2018: Please show on the plans a stop sign with street name sign at the
access onto Rock Creek.
7
Department: Zoning
Contact: Marcus Glasgow,
Topic: General Noted
►�.�
�
970-416-2338, mglasgow@fcgov.com
Comment Number: 1 Comment Originated
04/11/2018: Please provide amended site plan with existing setback lines
removed and modification notes added to the table.
Comment Number: 2 Comment Originated
04111/2018: Will there be any changes to the approved landscaping plan? If
so, please provide amended landscape plan.
04/11 /2018