April 13, 2018
Oasis Development
231 S Howes St
Fort Collins, CO 80521
RE; Oasis on Olive, PDP180003, Round Number 1
Community Development and
Neighborhood services
281 North College Avenue
PO Box 580
Fort Collins, CO 80522
970.221.6750
970.224.6134 - fax
kgov. com/developmentreview
Please see the following summary of comments from City staff and outside reviewing agencies for
your submittal of the above referenced project.. If you have questions about any comments, you may
contact the individual commenter or direct your questions through the Project Planner, Pete Wray, at
970=221-6754 or pwray@fcgov.com.
Comment Summary:
Department: Engineering Development Review
Contact: Katie Andrews, 970-221-6601, kandrews(a-)-fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 04/09/201.8
04/09/2018: Please clarify what's happening with the two drive approaches— does
2' curb typical existing mean vertical or rollover? The driveways should. be brought
up to current LCUASS standards and designed and reconstructed in accordance
with detail 706.1 (or 707.1 if the traffic warrants a high -volume drive).
Comment Number: 2
Comment Originated: 04/09/2018
04/09/2018` The minimum width for a private drive approach is 24 feet — a variance
would be required to allow for the reduced width.
Comment Number: 3 Comment Originated: 04./09/2018
04/09./2018: If you do not wish to dedicate the standard utility easements, please
provide a variance request in accordance with 1.9.4 of the LCUASS.
Comment Number: 4
Comment Originated: 04/09/2018
04/09/2018: The diagonal chase is not a standard design nor is it ideal for this area
from the City's perspective. We'd like to work with you on the chase design in this
area, there are some locations around the City where the drain directly abuts the
drive approach a good example is 619 S College Ave.
Comment Number: 5
Comment Originated: 04/09/2018
04/09/2018: It appears that a portion of the fence is being left in the ROW frontage —
an encroachment permit would need to be approved in order for this to remain.
Comment Number: 6
Comment Originated: 04/09/2018
04/09/2018: 1 did not notice signage for the entrance only/exit only — this is a critical
part of the access/drive design, please include a proposal for this with the next
submittal. It might be beneficial to include this information in the variance request for
the reduced -width driveway as well.
Page 1 of 10
Comment Number: 7
Comment Originated: 04/11/2018
04/11/2018: Covered chase drains have been approved in the past in the City.
Please include a design for review with your next submittal or provide an exhibit
directly to me for a quick review prior to the next submittal.
Department: Environmental Planning
Contact: Rebecca Everette, 910-416-2626, reveretteOfcgov.com
Topic: General
Comment Number: 1
Comment Originated: 04/09/2018
04/09/2018: LANDSCAPE PLAN: At the time of Final Plan, please provide detailed
species, quantities and planting locations for all shrubs, perennials and grasses,
including species for the turf areas and rain gardens.
Comment Number: 2
Comment Originated: 04/09/2018
04/09/2018: Thank you for selecting 3000K, full cutoff light fixtures for this project.
Comment Number: 3 Comment Originated: 04/09/2018
04/09/2018: Environmental Planning is ready for hearing.
Department: Forestry
Contact: Molly Roche, , mroche(a)fcaov.com
Topic: Landscape Plans
Comment Number: 1
Comment Originated: 04/10/2018
04/10/2018:
There appears to be existing trees on -site.. Please schedule an on -site meeting with
City Forestry to obtain tree inventory and mitigation information. All existing trees
should be retained and protected to the extent reasonably feasible;
Comment Number: 2
Comment Originated: 04/10/2018
04/10/2018:
Will the new driveway installation require any grading? Please note that the Ash tree
adjacent to the proposed driveway is planned to receive treatment for Emerald Ash
Borer by City Forestry..
Comment Number: 3 Comment Originated: 04/10/2018
4/9/2018:
Three of the Ash trees shown on landscape plans will not be treated for Emerald
Ash Borer by City Forestry. This means that they will be removed within the next
couple years. City Forestry would like to discuss a few planting management
options with the developer:
1) Developer remove and replace (3) Ash trees within the right-of-way at time of
project approval. Replace Ash trees with approved species from the City of Fort
Collins Street Tree list.
2) City Forestry remove and replace (3) Ash trees within the right-of-way.
Replacement trees to be included in the Ash Replacement Program — paid for and
planted by City Forestry.
3) Consider `shadow -planting' between existing Ash trees. This will allow new trees
to start establishing before the Ash are removed.
I am throwing out these options so that landscape updates coincide with site
improvements. It will benefit the development to establish new trees now instead of
later.
Page 2 of 10
Comment Number: 4 Comment Originated: 04/10/2018
04/10/2018
Please include any proposed landscaping, including trees, on the landscape plan
and provide a plant legend to detail quantity, species, size, method of transplant, and
species diversity (see LUC 12.1).
Comment Number: 6 Comment Originated: 04/10/2018
04/10/2018t
There appears to be areas of the site that could benefit from additional trees (east
side of parcel). Please consider ornamentals, upright species, or smaller evergreen
plants to this area and others where feasible.
Department: Historic Preservation
Contact: Karen McWilliams, 970-224-6078, kmcwilliams(a-fcaov.com
Topic: General
Comment Number: 1 Comment Originated: 04/06/2018
04/06/2018: The project is subject to land Use Code Section 3.4.7, Historic and
Cultural Resources. This Section is intended to ensure that, to the maximum extent.
feasible, new construction is designed to respect the historic character of the site
and any historic properties in the surrounding neighborhood.
Comment Number: 2 Comment Originated; 04/06/2018
04/06/2018: At its March work session the LPC identified the Area of Adjacency for
the historic review of this project. Designated Fort Collins Landmarks within this
area are 231 S. Howes Street, the Humphry=Davis House, and 223 South Howes
Street, the Dealy-Goode House. Properties with a non -binding determination of
individual eligibility are 227 S. Howes Street, 316 West Olive Street, and the Old
Town professional Center Building at 315 West Oak/211 W. Canyon Avenue.
Comment Number: 3 Comment Originated, 04/06/2018
04/06/2018: The project was discussed at a Conceptual Review by the LPC on
March 21, 2018, and is scheduled to return to the LPC on May 16, 2018. Upon
completion of its review, the LPC will provide a recommendation on the project to
the PBZ.
At this meeting, the LPC requested additional information to be provided by the
applicant; which staff has made the applicant aware of.
Comment Number: 4
Comment Originated: 04/06/2018
04/06/2018: The applicant has indicated that the design will change from that
shown on the submittal and presented to the LPC. Historic Preservation staff will
provide comments on the design compliance with applicable standards when the
revised plans are submitted.
Department: Light And Power
Contact: Clint Reetz, 970-221-6326, creetz(a-)fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 04/06/2018
04/06/2018: Currently single phase power is serving the existing property. Any
upgrades or changes to the existing electric infrastructure will incur system
modification charges.
Comment Number: 2
Comment Originated: 04/06/2018
04/06/2018: Developer will be responsible for supplying and installing electric
service from the transformer to the multi -family units.
Page 3 of 10
Comment Number: 3
Comment Originated: 04/06/2018
04/06/2018: Transformer locations will need to be coordinated with Light & Power.
Transformers must be placed within 10 ft of a drivable surface for installation and
maintenance purposes. The transformer must also have a front clearance of 10 ft
and side/rear clearance of 3 ft minimum.
Comment Number: 4
Comment Originated: 04/06/2018
04/06/2018: Meter locations for multi -family attached units will need to be
coordinated with Light and Power Engineering. Each unit will need its own meter, it
is recommended that the meters be located in one common area.
Comment Number: 5 Comment Originated: 04/06/2018
04/06/2018: Please contact Light & Power Engineering if you have any questions
call me directly at 970-221-6326. Please reference our policies, development
charge processes, and use our fee estimator at
http //WwW.fcgov.com/utilities/business/builders-and-developers.
Comment Number: 6
Comment Originated: 04/13/2018
04/13/2018: Per a discussion had at PDP where the possibility of an existing
transformer on the site may need to be moved, after a site visit it looks like no
conflict exists.
Department: PFA
Contact: Andrew Rosen, , arosen(a-fcgov.com
Topic: General
Page 4 of 10
Comment Number: 1 Comment Originated: 04/05/2018
04-11-2018 UPDATE
The project owner requested clarification on whether an NFPA 13 or 13R sprinkler
system would be required. From the provided documentation, this appears to be a
multi -family project which will require a full NFPA 13 system. If it can be shown that
these are individually owned homes with a lot line between each, then a 13R may be
allowed if there is a 2hr vertical and horizontal separation between units. Please
contact the Fort Collins building department for further information.
04-10-2018 UPDATE
The project team stated that the building was at grade level and that the 29ft 10in
height was taken from true ground level.
04/05/2018:
AUTOMATED FIRE SPRINKLER SYSTEM
This building will require an approved NFPA 13 automated fire sprinkler system. This
typically requires a 6" supply line and the plan shall be provided to PFA for approval
under separate permit. Please contact PFA at 970-416-2891 with any fire sprinkler
questions. Code language follows:
GROUP S-2 AUTOMATIC SPRINKLER SYSTEM REQUIREMENTS
> IFC 903.2.10: An automatic sprinkler system shall be provided throughout
buildings classified as enclosed parking garages (Group &2 occupancy) in
accordance with IBC 406.6 OR where located beneath other groups.
BALCONIES AND DECKS
> IFC 903.3.1.2.1: Sprinkler protection shall be provided for exterior balconies,
decks, and ground floor patios of dwelling units where the building_ is of Type V
construction.
FDC
The FDC should be located where it is easily visible and accessed from Olive
street. This location will require PFA approval. Code language follows:
>IFC 912.2: Fire department connections shall be located on the street side of the
building, fully visible and recognizable from the street or nearest point of fire
department vehicle access. The location of the FDC shall be approved by PFA.
Comment Number: 2 Comment Originated: 04/05/2018
04/05/2018:
ADDRESSING/WAYFINDING
To assist with prompt emergency response, an overall addressing and wayfinding
plan will be required that involves the whole building; the two towers and the single
unit. The street address and number should be clearly visible from Olive street.
Signage shall be affixed to the elevation facing Olive to indicate the appropriate
accessway to each unit.
KNOX BOXES
If garage doors, security gates or access doors into the towers are required to be
opened to gain entrance into the garages or towers, then each one will be designed
with an approved Knox Key Switch or other approved access mechanism. The
overall access plan should be submitted to PFA for approval.
Page 5 of 10
Comment Number: 3
Comment. Originated: 04/05/2018
04/05/2018:
PUBLIC -SAFETY RADIO AMPLIFICATION SYSTEM TEST
> IFC 510 & 110.3.2: New & existing buildings require a fire department, emergency
communication system evaluation after the core/shell but prior to final build out. For
the purposes of this section, fire walls shall not be used to define separate buildings..
Where adequate radio coverage cannot be established within a building,
public=safety radio amplification systems shall be designed and installed in
accordance with criteria established by the Poudre Fire Authority.
Comment Number: 4
Comment Originated: 04/05/2018
04/05/2018'
ACCESS
>Access is required to within 150ft of all exterior portions of the building. On the
provided site plan dated 3-14-2018, this criteria has been met by measuring from
Olive St and Canyon Ave.
Comment Number: 5
Comment Originated: 04/05/2018
04/05/2018:
HYDRANT
A hydrant is required within 300ft of the building. This criteria appears to be met by
the hydrant on Olive St. However it is the project team's responsibility to verify
volume and pressure.
Department: Planning Services
Contact: Pete Wray, 970-2.21-6764, pwray(cDfcgov.com.
Topic: Building Elevations
Comment Number: 9
Comment Originated: 04/10/2018
04/10/2018: Add color to elevations or on separate sheet with material color legend
to match call outs.. If these exist by Architect, then use if they match elevations. Are
there any roof chimney or FP vents used in units?
Comment Number: 10
Comment Originated: 04/10/2018
04/10/2018; Refer to Historic Preservation staff and LPC comments for building
design compatibility requirements.
Topic: General
Comment Number: 7
Comment Originated: 04/10/2018
04/10/2018: Utility Plans.
Label all sheet title blocks and on plans correct address of 310 W Olive, not 312 typ.
all sheets.
Comment Number: 8
Comment Originated: 04/10/2018
04/10/2018: Utility Plan shows new site wall Sheet 3 in front of garage on Olive
Street. Need to show on all other plans including detail of this design.
Comment Number: 11
Comment Originated: 04/10/2018
04/10/2018: PDP R2 Review.
If staff determines this PDP is ready for P & Z Board hearing in May during the staff
review meeting on April 11, 1 will need a revised plan set (same as LPC plan set)
submitted by May 2 for packet.
Prior this this date, please confirm with Katie Andrews Engineering comments are
addressed in revised plan set, including any variances as identified in her
comments. If they are not addressed and she determines this project is not ready
for hearing, it will be deferred to June meeting with the Board.
Page 6 of 10
Topic: Landscape Plans
Comment Number, 4
Comment Originated: 04/10/2018
04/10/2018:
See site plan redline notes for ex. tree on Olive, and ex. metal fence.
Comment Number: 6
Comment Originated: 04/10/2018
04/10/2018:
Please add foundation planting on garage wall facing Olive Street, see redline. Add
some additional taller planting in foundation strip at base of stair tower to soften tall
wall.
Comment Number: 6
Comment. Originated: 04/10/2018
04/10/2018:
Sheet LS-2. Add planting legend, and details of all landscape materials such as
cobble mulch, LID rain garden planters, fencing, other?
Topic: Site Plan
Comment Number: 1
Comment Originated: 04/10/2018
04/10/2018:
Fencing: Label existing metal fence column if maintaining this with removal of
remainder of fence. Add labels for new 6' cedar fence in all locations. New site wall
shown on Utility Plan Sheet 3 in front of garage on Olive St. needs to be shown on
all plans. Need detail of this design.
Comment Number: 2
Comment Originated: 04/10/2018
04/10/2018:
Site Plan Legend: Add parking calculation for existing standard (Required spaces),
then compare to TOD Overlay calculations.
Comment Number: 3 Comment Originated: 04/10/2018
04/10/2018-
Exist. Ash tree on Olive label either retaining or removal.
Department: Stormwater Engineering
Contact: Jesse Schlam, 970-218-2932, jschlam(o�fcgov.com
Topic: Erosion Control
Comment Number: 1
Comment Originated: 03/30/2018
03/30/2018: The site disturbs more than 10,000 sq. ft. and therefore Erosion and
Sediment Control Materials need to be submitted. (the lot is --9700 SF but the off lot.
work with curb gutters and utilities installations put this project about-11,000 SF)
The erosion control requirements can be located in the Stormwater Design Criteria
under -the Amendments of Volume 3 Chapter 7 Section 1.3.3. a copy of the erosion
control requirements can be found at www.fcgov.com/eroison. The Erosion Control
Materials will need to be submitted at time of the first round of FDP. If you need
clarification concerning the Erosion Control Material Requirements or Comments
presented above please contact myself. Jesse Schlam (970) 224-6015
jschlam@fcgov.com
Contact! Mark Taylor, 970-416-2494, mtaylor(cD_fcgov.com
Topic: Drainage Report
Comment Number: 2
Comment Originated: 04/09/2018
04/09/2018: Please describe portions of the site as being in the City's Old Town
Basin and indicate the presence of the City -regulated 100-year floodplain, as well as
the FEMA Map Panel number and the date of the City's Master Plan. Also, include a
copy of the FEMA Map Panel with the site location noted in red.
Page 7 of 10
Comment Number: 3 Comment Originated: 04/09/2018
04/09/2018: The second half of the paragraph CITY FLOODPLAIN/FLOODWAY
should be changed. The building it not in the floodplain, so there is no need for an
RFPE, a minimum elevation of the building, for venting to be provided, or any sort of
hold on the certificate of occupancy. Any grading in the floodway, utility cuts, or
driveway changes will need a floodplain use permit and a no -rise certification.
Topic: Floodplain
Comment Number: 5 Comment Originated: 04/09/2018
04/09/2.018: On Sheets 4 and 5 of the Utility Plans, please add a. note that any utility
work in the floodway must be preceded by a floodplain use permit and no -rise
certification.
Comment Number: 6 Comment Originated: 04/09/2018
04/09/2018: On Sheets 4 and 5 of the. Utility Plans, please add a note stating that
storage of equipment and materials is not allowed within the floodway.
Comment Number: 7 Comment Originated: 04/09/2018
04/09/2018: On Sheet 5 of the Utility Plans, an RFPE is listed with XS #3164. Since
the building is not in the floodplain, this elevation is not relevant and does not need to
be included.
Topic: Site Plan
Comment Number: 4
Comment Originated: 04/09/2018
04/09/2018: Please show and label the current effective City -regulated 100-year
floodplain and floodway boundaries.
Contact: Wes Lamarque, 970-416-2418, wlamaraue(a)-fcgov.com
Topic: General
Comment Number: 8
04/10/2018: The LID concept meets City Criteria.
Department: Technical Services
Contact: Jeff County, 970-221-6588, icountv(aD_fcaov.com
Topic: Building Elevations
Comment Originated: 04/10/2018
Comment Number: 2 Comment Originated: 04/06/2018
04/06/2018: There are line over text issues. See redlines.
Comment Number: 3 Comment Originated: 041/06/2018
04/06/2018: There is text that needs to be masked. Mask all text in hatched areas.
See redlines.
Topic: Construction Drawings
Comment Number: 4 Comment Originated: 04/06/2018
04/06/2018: Please add the Lot, Block, and Subdivision of this project to the
sub -title on sheet 1.
Comment Number: 5 Comment Originated: 04/06/2018
04/06/2018: Please revise the Benchmark Statement as marked. See redlines.
Comment Number: 6
Comment Originated: 04/06/2018
04/061.2018: Some of the sheet titles in the sheet index do not match the sheet titles
on the noted sheets. See redlines.
Page 8 of 10
Comment Number: 7 Comment Originated: 04/06/2018
04/06/2018: There are line over text issues. See redlines.
Topic; Landscape Plans
Comment Number: 1 Comment Originated: 04/06/2018
04/06/2018: There are line over text issues. See redlines.
Department: Traffic Operation
Contact: Tim Tuttle, , TTUTTLE(&fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 04/09/2018
04/09/2018: The distance from the new diagonal parking on Canyon to the driveway
should be 5 ft.
Comment Number, 2 Comment Originated: 04/09/2018
04/09/2018: Please show the location of any new or relocated signs.
Comment Number: 3 Comment. Originated: 04/09/2018
04/09/2018: Signing and striping redlines will be provided at the Staff Review
meeting.
Department: Water Conservation
Contact: Eric Olson, 970-221-6704, eolson(&fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 04/10/2018
04/10/2018: A landscape plan shall contain accurate and identifiable hydrozones,
including a water budget chart that shows the total annual water use, which shall not
exceed fifteen (15) gallons per square foot over the site. If you have questions
contact Eric Olson at eolson@fcgov.com or 970-221-6704. .
Comment Number: 2 Comment Originated: 04/10/2018
04/10/2018: Irrigation plans are required no later than at the time of building permit.
The irrigation plans must comply with the provisions outlined in Section 3.2.1(J) of
the Land Use Code. Direct questions concerning irrigation requirements to Eric
Olson., at 221-6704 or eolson@fcgov,com
Department: Water -Wastewater Engineering
Contact: Wes Lamarque, 970-416-2418, wlamargue(a)-fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 04/10/2018
04/10/2018: The water service does not meet City distance requirements form
other improvements and will need to be relocated.
Comment Number: 2 Comment Originated: 04/10/2018
04/10/2018: Please draw the water meter pit per scale. A 2-inch meter pit requires
a 4-foot manhole.
Department: Zoning
Contact: Missy Nelson, , mnelson(aD-fcgov.com
Topic: General
Page 9 of 10
Comment Number: 1
Comment Originated: 04/09/2018
04/09/2018: The correct address is 310 W. Olive St (I confirmed this with our GIS
department). Please correct on all documents for next rounds submittal.
GIS contact:
Email: gis@fcgov.com
Phone: 970.416.2483
Comment Number: 2
Comment Originated: 04/09/2018
04/09/2018: What is your exiting plan for garage bay/parking space number 8? Is
there an interior pedestrian access? Also, for the car to then exit, will they have to
open the other garage to go through and exit? I have a feeling they won't do so and
will just exit through the entrance.
Pedestrian access to and from parking garage?
Comment Number: 3 Comment Originated: 04/09/2018
04/09/2018: All rooftop mechanical equipment shall be screened from public view
from both above and below by integrating it into building and roof design to the
maximum extent feasible. Where will the mechanical equipment be located?
In addition, conduit, meters, vents and other equipment attached to the building or
protruding from the roof shall be painted to match surrounding building surfaces.
Please make sure there's a note on the site plan.
Comment Number: 4 Comment Originated: 04/09/2018
04/09/2018: Please add drive aisle dimensions.
Comment Number: 6 Comment Originated: 04/09/2018
04/09/2018: A full landscape plan will need to be submitted at Final.
Comment Number: 6 Comment Originated: 04/11/2018
04/1112018: LUC 3.2.2The 1 handicap parking space shall be designated as
van -accessible and must be a minimum of 8 feet wide and adjoin a minimum 8 foot
wide access aisle.
Page 10 of 10