HomeMy WebLinkAboutKUM & GO #0951 - FDP230009 - SUBMITTAL DOCUMENTS - ROUND 2 - SUPPORTING DOCUMENTATIONUTILITY TRANSFORMER
208Y/120V 3Ø 4W
GROUND BUS
NEUTRAL BUS
TO BUILDING FOOTING (UFER)
TO WATER SERVICE
TO ABOVE GROUND METAL PIPING
TO STRUCTURAL STEEL
TELEPHONE BOARD (TTB)
TO GROUND BAR AT MAIN
TO GROUND ROD(S)
IG BUS
PNLBD P1225PNLBD P2224PNLBD P3224PNLBD F124PNLBD MDPPNLBD RPA541531532043P
200A
NEMA 3R
200A
PROTOCOL AM
3P
150A
NEMA 3R
200A
3P
150A
NEMA 3R
200A
RTU-1M
RTU-2M 1004TG0G1200G1200G1200G200G150MBJ
MBJ
3P
1000A
NEMA 3R
1000AS1004BUILDING LOAD SUMMARY (MDP)
BUILDING OCCUPANCY: STORE
BUILDING SQUARE FOOTAGE: 6000
SERVICE VOLTAGE:
208Y/120 V
LOAD TYPE CONNECTED
LOAD
DEMAND
FACTOR
NEC DEMAND
EXISTING LOAD (E) 0 VA 100% 0 VA
COOLING (C) 0 VA 0% 0 VA
HEATING (H) 97994 VA 100% 97994 VA
LIGHTING (L) (PER NEC-220) 18000 VA 125% 22500 VA
RECEPTACLES (R) 14128 VA 85% 12064 VA
MOTORS (M) 894 VA 100% 894 VA
SUPPLEMENTAL HEAT (U) 24000 VA 100% 24000 VA
MISC EQUIP (Z) 42637 VA 100% 42637 VA
REFRIGERATION (F) 65185 VA 100% 65185 VA
SIGNAGE (S) 5701 VA 125% 7126 VA
KITCHEN (K) 32888 VA 65% 21377 VA
LARGEST MOTOR 1200 VA 125% 1500 VA
SHOW WINDOW (W) 9300 VA 125% 11625 VA
TRACK LIGHTING 0 VA 100% 0 VA
TOTAL LOAD 311927 VA 306902
TOTAL AMPACITY 866 AMPS 852
SERVICE AMPACITY AMPS 1000
SPARE CAPACITY AMPS 148
UTILITY TRANSFORMER DESIGN CRITERIA: PAD MOUNT
UTILITY TRANSFORMER SECONDARY VOLTAGE:
208Y/120V 3PH, 4W
FOR PURPOSES OF DESIGN A VALUE OF 22,030 AMPS
SHORT CIRCUIT CURRENT IS CONSIDERED AT THE
SERVICE ENTRANCE. VALUE PROVIDED BY ROB IRISH
OF CITY OF FORT COLLINS.
ELECTRICAL SERVICE NOTE:
UTILITY COMPANY : CITY OF FORT COLLINS
UTILITY CONTACT: ROB IRISH
UTILITY PHONE: 970-224-6167
F5 F6 F7F8F9F4F11F10
EO2EO4
C
RK1
CURRENT
LIMITING
RK1
CURRENT
LIMITING
POWERWALL
MANUFACTUERER
INSTALLED
EO1
F1
F3
M
UTILITY
METER
CT CABINET
NEMA 3R
EO5
ST
EO6
F2
SE RATED
EO3
EO10
S
F
S
F
S
F
6
E3.0
FUEL PUMP
CONTROLS
PETRO
CONDUITS
5' - 0"
ELECTRICAL GUTTER
BY PETROLEUM VENDOR
FINISHED FLOOR
HOUSEKEEPING PAD BY
ELECTRICAL CONTRACTOR
CONTRACTOR TO PLACE PLACACARD ON
PANELS STATING: "CAUTION -ENGINEERED
SERIES COMBINATION SYSTEM RATED
65,000 AMPERES. IDENTIFIED
REPLACEMENT COMPONENTS REQUIRED."
3' - 9"
REFRIGERATION
REMOTE PANEL RPA
LIGHTING CONTACTORS
PROVIDE (2) 1" CONDUITS
TO ROOFTOP PROTOCOL
REFRIGERATION SYSTEM
FOR CONTROL WIRING
PROVIDE (1) 2" CONDUIT FOR
LOW VOLTAGE CABLE.
CONDUIT SHALL ENTER AT TOP
RIGHT SIDE OF THE CABINET.1' - 1"HOUSEKEEPING PAD BY
ELECTRICAL CONTRACTOR
FROM ADJACENT WALL
1' - 3"
MDP
3' - 6"
FINISHED
FLOOR
HOUSEKEEPING
PAD BY
ELECTRICAL
CONTRACTOR
BRANCH
MOUNTED MAIN.
FURNISH WITH
ENERGY
REDUCTION
MAINTENANCE
SETTING
MONITORING
PNL
F
PNL
P3
PNL F
CONT
125A
(1) DUPLEX AND (1) QUAD
RECEPTACLE ON SIDE BY
E-WALL VENDOR
PNL
P1
PNL
P2
3' - 6"
PROVIDE (2) 2" CONDUITS TO
DATA RACK FOR LOW VOLTAGE
CABLES.
PROVIDE (2) 2" CONDUITS FOR
INCOMING TELEPHONE SERVICE.
PROVIDE (1) 1" CONDUIT FOR
IRRIGATION CONTROL CABLES
LANDSCAPE
IRRIGATION
CONTROLLER
TELEPHONE
DEMARC
DOUBLE DUPLEX RECEPTACLES
PER PLANS (TYPICAL OF 2)
PROVIDE PLYWOOD BACKBOARD
FOR TELEPHONE EQUIPMENT
FINISHED FLOOR
SOIL OR SAND FILL
GROUND ROD(S) 3/4" x 8'-0" MIN
REMOVABLE BOLTED/SECURED
COVER -LABELED "GROUND".
USE SATURATED FELT PAPER
AROUND COVER WHEN
POURING CONCRETE.
TRAFFIC AREAS: PROVIDE POLYMER CONCRETE BOX AND COLLAR RING OR
APPROVED ALTERNATE MATERIAL. REMOVABLE COVER SHALL BE REINFORCED
CONCRETE, STEEL, CAST IRON OR APPROVED ALTERNATE MATERIAL. BOX, RING
AND COVER SHALL HAVE A MINIMUM H-20 LOAD RATING AND SHALL BE SUITABLE
FOR LOCATION.
PROVIDE LOW-RESISTIVITY,
GROUND-ENHANCING BACKFILL
MATERIAL AS NEEDED FOR HIGH
GROUND RESISTIVITY OR IF
RECOMMENDED BY THE
ELECTRODE MANUFACTURER.
FINISHED GRADE
(PAVED)
NON-TRAFFIC AREAS: PROVIDE PROVIDE HIGH DENSITY POLYETHYLENE OR
APPROVED ALTERNATE MATERIAL. BOX, RING AND COVER SHALL HAVE A
MINIMUM ANSI 77 TIER 8 LOAD RATING AND SHALL BE SUITABLE FOR LOCATION.
GROUNDING ELECTRODE
CONDUCTOR
1'-0" MIN FINISHED GRADE
(GRASS)1'-0"4"GROUNDING ELECTRODE
CONDUCTOR (IF APPLICABLE)
GROUND ROD CLAMP OR
EXOTHERMIC WELD
4" MIN
FAXTEL
Sheet No.
This drawing was prepared for use on a
specific site contemporaneously with its issue
date and it is not suitable for use on a
different project site or at a later time. Use of
this drawing for reference or example on
another project requires the services of
properly licensed architects and engineers.
Reproduction of this drawing for reuse on
another project is not authorized and may be
contrary to the law.
BRR Original printed on recycled paper
Copyright Notice
Project No.
Sheet Title
Issues & Revisions
ARCHITECT OF RECORD:
8131 METCALF AVENUE
SUITE 300
OVERLAND PARK, KS 66204
www.brrarch.com
Tel: 913-262-9095
Fax: 913-262-9044
Drawn by:
Professional Seal
Project Manager:
Document date:
Checked By:
Project Phase
Project Name
Project Address
TREVOR TYSON HOLCOMB
WWW.HENDERSONENGINEERS.COM
2/27/2023 1:13:08 PMELECTRICAL ONE-LINE
AND SCHEDULES
E3.0
63109510
02/28/23
JC
DC/AH
PROTO RIGHT GLAZING
AH
KUM & GO
949 E Prospect Rd.
Fort Collins, CO
#0951
DEAN W. CHANDLER2150004674
2150004674
8345 LENEXA DRIVE, SUITE 300
LENEXA, KS 66214
913.742.5000 913.742.5001
NTS1ONE-LINE DIAGRAM
EO1 SURGE SUPPRESSION DEVICE (SPD) IS FURNISHED WITH POWERWALL. SPD SHALL BE
INTERNALLY MOUNTED. REFER TO SPECIFICATIONS FOR REQUIREMENTS.
EO2 ROUTE ISOLATED GROUND CONDUCTOR FOR PANELBOARD P1 TO MAIN SERVICE
GROUND GROUNDING POINT.
EO3 FUEL DISPENSER PANELBOARD AND MAIN CONTACTOR ARE FURNISHED AND INSTALLED
IN POWERWALL. COORDINATE ALL REQUIREMENTS FOR INSTALLATION WITH FUEL
CONTRACTOR.
EO4 REFRIGERATION REMOTE PANEL A (RPA) FURNISHED BY REFRIGERATION SUPPLIER
AND INSTALLED BY ELECTRICAL CONTRACTOR.
EO5 #4/0 AWG EXOTHERMICALLY WELDED TO BUILDING STEEL AND BONDED TO THE
INCOMING METAL WATER PIPING PER N.E.C. GROUNDING (ART. 250), LOCAL UTILITY
REQUIREMENTS, AND PER LOCAL AUTHORITY. PROVIDE BONDING JUMPER IN "MAIN
SERVICE DISCONNECT SWITCH". SIZED IN ACCORDANCE WITH N.E.C. ARTICLE 250-30.
SEE GROUNDING ELECTRODE DETAIL, THIS SHEET.
EO6 ELECTRICAL POWER-WALL FURNISHED BY OWNER.
EO10 INSTALL FEEDERS UNDERSLAB. COORDINATE ROUTING W ITH OTHER TRADES PRIOR TO
INSTALLATION.
ONE-LINE PLAN NOTES
FEEDER TAG FEEDER DESCRIPTION
54 (4)#8, (1)#10G, 3/4" C
124 (4)#1, (1)#6G, 1-1/2" C
153 (3)#1/0, (1)#6G, 1-1/2" C
204 (4)#3/0, (1)#6G, 2" C
224 (4)#4/0, (1)#4G, 2-1/2" C
225 (4)#4/0, (1)#4G, (1)#4 IG, 2-1/2" C
1004 (3) 3" C, EACH W/ (4)-400kcmil, (1)#2/0G
G150 #6 COPPER GROUND, 3/4” C
G200 #4 COPPER GROUND, 3/4” C
G1200 #3/0 COPPER GROUND, 3/4” C
MBJ MAIN BONDING JUMPER, #4/0
S103 (3)#3, 1-1/4" C
S1004 (3) 3" C, EACH W/ (4)-400kcmil
TG0 #1/0 cu
ALL CONDUCTOR SIZES ARE BASED ON
75 DEG C RATED TERMINATION AND COPPER
CONDUCTORS WITH TYPE THHN/THWN-2
INSULATION. WHERE ALUMINUM CONDUCTORS
ARE ALLOWED PER SPECIFICATIONS AND
FOR TERMINATION OR INSULATION TYPES
RATED LESS THAN 75 DEG C, MODIFY
SIZES ACCORDING TO NFPA 70.
CIRCUIT SCHEDULE:
ELECTRICAL ONE-LINE GENERAL NOTES
1.ALL ELECTRICAL PANELBOARDS SHALL BE MANUFACTURED BY SQUARE D. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2.ELECTRICAL POWERWALL FURNISHED BY OWNER. CONTACT DAVE ROACH, CD CONTROLS,
706-356-0325, DAVEROACH@CDCONTROLS.COM FOR COORDINATION PRIOR TO ROUGH-IN.
3. THE POWERWALL IS PART OF A NATIONAL RECOGNIZED TEST LABORATORY LISTED BREAKER
RATED SYSTEM THAT REQUIRES THE DOWN STREAM BREAKERS TO BE TESTED WITH THE
POWERWALL AS A COMPLETE SERIES RATED LISTED SYSTEM. THE MANUFACTURER WILL
PROVIDE SPECIFIC BREAKER TYPES (CATALOG NUMBERS) TO COMPLY WITH THE TESTS FOR A
SERIES RATED SYSTEM. ANY REPLACEMENT BREAKERS SUPPLIED SHALL MATCH EXISTING
TYPES (CATALOG NUMBERS) SUPPLIED BY THE ORIGINAL SYSTEM MANUFACTURER. FAILURE
TO SUPPLY THE CORRECT BREAKERS WILL VOID THE SERIES RATED SYSTEM RATING OF THE
COMPLETE ELECTRICAL SYSTEM.
4. CIRCUIT BREAKERS RATED 1200A OR HIGHER SHALL HAVE APPROPRIATE DOCUMENTATION AND
METHOD TO REDUCE CLEARING TIME IN ORDER TO REDUCE ARC FLASH ENERGY PER CODE.
PROVIDE ELECTRONIC TRIP UNIT WITH INSTANTANEOUS TRIP AND ENERGY-REDUCING
MAINTENANCE SWITCH WITH LOCAL STATUS INDICATOR FOR COMPLIANCE. PROVIDE
PROVISIONS TO INTERFACE WITH OWNER ALARM/MONITORING SYSTEM TO INDICATE
MAINTENANCE SWITCH STATUS.
1/2" = 1'-0"3 MECH/ELEC ROOM ELEVATION 1
1/2" = 1'-0"4 RPA PANEL ELEVATION
1/2" = 1'-0"2 MECH/ELEC ROOM ELEVATION
11 RTU-2 3 3 18660 M CU 1 Set(s) of 1 AWG 7293 -- 208 60 0.85 136 0.000160 0.000057 0.554811 1.278 0.44 8190 -1.13% -2.58% 11
10 RTU-1 3 3 18660 M CU 1 Set(s) of 1 AWG 7293 -- 208 90 0.85 136 0.000160 0.000057 0.554811 1.918 0.34 6396 -1.69% -3.15% 10
9 Protocol A 3 3 18660 M CU 1 Set(s) of 3/0 AWG 12844 -- 208 65 0.9 153 0.000079 0.000052 0.451027 0.786 0.56 10446 -0.78% -2.23% 9
8 Panelboard RPA 3 3 18660 M CU 1 Set(s) of 8 AWG 1557 -- 208 20 0.9 40 0.000780 0.000065 0.451027 1.996 0.33 6228 -0.49% -1.94% 8
7 Panelboard F 3 3 18660 M CU 1 Set(s) of 1 AWG 7293 -- 208 8 0.9 61 0.000160 0.000057 0.451027 0.170 0.85 15943 -0.07% -1.52% 7
6 Panelboard P3 3 3 18660 M CU 1 Set(s) of 4/0 AWG 15082 -- 208 6 0.9 191 0.000063 0.000051 0.451027 0.062 0.94 17574 -0.08% -1.53% 6
5 Panelboard P2 3 3 18660 M CU 1 Set(s) of 4/0 AWG 15082 -- 208 6 0.9 137 0.000063 0.000051 0.451027 0.062 0.94 17574 -0.05% -1.51% 5
4 Panelboard P1 3 3 18660 M CU 1 Set(s) of 4/0 AWG 15082 -- 208 8 0.9 132 0.000063 0.000051 0.451027 0.082 0.92 17239 -0.07% -1.52% 4
3 Panelboard MDP 2 3 19229 M CU 4 Set(s) of 350 kcmil 19704 -- 208 15 0.9 1161 0.000039 0.000050 0.451027 0.030 0.97 18660 -0.21% -1.45% 3
2 Disconnect Switch 1 3 23338 NM CU 4 Set(s) of 350 kcmil 22737 -- 208 100 0.9 1161 0.000038 0.000040 0.451027 0.214 0.82 19229 -1.25% -1.25% 2
Motor Contribution 218 The connected full load motor amps (includes compressors) on the system
1 Utility Service Point 22,030 at the secondary of the utility transformer Source Isc + 6X Motor Contribution = 23338 1
(Radians)
Conduit
Type/ TX Material Quantity of Parallel Sets and Bus/ Phase
& Neutral Size
Resistance
(R)
Reactance
(X)
Arccos (pf)Type Degree
Rise kVA New Xfmr
Z
Existing
Xfmr Z
Secondary
Voltage
Tap
Setting
Fault
Point
(F#)
Bus/Feeder Description
Source
(Fault
Point)
Phase Source Isc
(amps)
Feeder
Conductor 'C'
Value
Busway 'C'
Value
L-L Voltage
(E)
Circuit
Length
(L)
Load Power
Factor (pf)
Circuit Load
(Amperage)
Conductor Transformer
f M
Fault
Current
(amps)
Voltage
Drop (%VD)
Cumulative
Voltage Drop
(%VD)
Fault
Point
(F#)
System Voltage: 208Y/120V - 3 phase
NM - Non Magnetic Conduit, M - Magnetic Conduit, FB - Feeder Busway, PB - Plug-in Busway, TX - Transformer
Feeder Types =
C ="C" Factor from Bussman table where "C" = 1 / impedance per linear foot
L = Length of circuit E = Line to line volts X= reactances in ohms per LF
Vs=Secondary voltage R=resistance in ohms per LF
IS= Secondary short circuit current %VD CUM= Cumulative Voltage Drop from Fault Point 1 to Fault Point #
Vp = Primary voltage
IP = Primary short circuit current
C x E 100,000 x KVA
ISC (2) = short circuit current at fault point 2 Feeder: f (1Ø)= 2 x L x Isc XFMR: f (1Ø)= IP(sca)x Vp x %Z %VD= ((R x cos(arccos(pf)) + X x sin(arccos(pf))) x 2 x L/# x I) / E
ISC (1) = short circuit current at fault point 1 C x E 100,000 x KVA Vs VOLTAGE DROP (1Ø):
ISC (2) = ISC(1) x M(1)M= 1/(1+f) Feeder: f (3Ø) = 1.732 x L x Isc XFMR: f (3Ø) = IP(sca)x Vp x 1.73 x %Z IS(sca)= Vp x M x IP(sca)%VD= ((R x cos(arccos(pf)) + X x sin (arccos(pf))) x L/# x I x 1.73) / E
The following calculations are based on the "Point-by-Point" method where:VOLTAGE DROP (3Ø):
Distances are for calculation purposes only and shall not be used for contractor takeoffs nor bidding - Contractor shall notify Engineer of any field condition that results in a change of 10% or greater circuit distance
Short-Circuit and Voltage Drop Calculations
1/2" = 1'-0"5 TELEPHONE ELEVATION
12" = 1'-0"6 GROUNDING TEST WELL INSTALLATION
NO. DATE DESCRIPTION
02/27/2023