February 09, 2022
Jen Daniels
Powder River Development Services, LLC
408 S Eagle Road, Suite 200
Eagle, ID 83616
RE: FTC Lady Moon WTE, BDR190015, Round Number 3
Please see the following summary of comments from City staff and outside reviewing
agencies for your submittal of FTC Lady Moon WTE. If you have questions about any
comments, you may contact the individual commenter or direct your questions through yo ur
Development Review Coordinator, Todd Sullivan via phone at 970-221-6695 or via email at
tsullivan@fcgov.com.
Comment Summary:
Department: Development Review Coordinator
Contact: Todd Sullivan, 970-221-6695, tsullivan@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 02/10/2022
I will be your primary point of contact throughout the development review and
permitting processes. If you have any questions, need additional meetings with
the project reviewers, or need assistance throughout the process, please let me
know and I can assist you and your team. To best serve you, please include me
in all email correspondence with other reviewers and keep me informed of any
phone conversations. Thank you!
Comment Number: 2 Comment Originated: 02/10/2022
All "FOR FINAL APPROVAL / FOR APPROVAL" comments need to be addressed
and resolved prior to moving forward with a formal decision for this project.
Comment Number: 3 Comment Originated: 02/10/2022
As part of your resubmittal, you will respond to the comments provided in this
letter. This letter is provided to you in Microsoft Word format. Please use this
document to insert responses to each comment for your submittal, using a
different font color. When replying to the comment letter please be detailed in
your responses, as all comments should be thoroughly addressed. Provide
Page 2 of 4
reference to specific project plans or explanations of why comments have not
been addressed, when applicable, avoiding responses like noted or acknowledged.
Please follow the Electronic Submittal Requirements and File Naming
Standards found at https://www.fcgov.com/developmentreview/files/electronic
submittal requirements and file naming standards_v1_8 1 19.pdf?1566857888.
Files are to be named PLAN NAME_PROJECT NAME_REVIEW TYPE_ROUND NO.
Example: UTILITY PLANS_MY PROJECT_PDP_RD1.pdf
File names have been updated to meet naming standards
Resubmittals are accepted any day of the week, with Wednesday at noon being
the cut-off for routing the same week. When you are ready to resubmit your
plans, please notify me as much in advance as possible.
Comment Number: 4 Comment Originated: 02/10/2022
LUC 2.211 Lapse, Rounds of Review: Applicants, within one hundred eighty
(180) days of receipt of written comments and notice to respond from the City
on any submittal (or subsequent revision to a submittal) of an application for
approval of a development plan, shall file such additional or revised submittal
documents as are necessary to address such comments from the City. If the
additional submittal information or revised submittal is not filed within said
period of time, the development application shall automatically lapse and
become null and void.
Department: Engineering Development Review
Contact: Dave Betley, 970-221-6573, dbetley@fcgov.com
Topic: General
Comment Number: 4 Comment Originated: 02/07/2022
02/07/2022: FOR APPROVAL:
The applicant will need to submit the paperwork for recordation for the
easements on the site. It does not appear that there is a plat for the document
so the documents will need to be recorded before the plans are signed. Please
add a line to the easement notes where the recordation number for the
easement documents can be entered.
The annotation “RECEPTION NO.________” has been added to the description note on pages
L1.0, A1.0 and survey page LS1 in the plan note and in the description.
Department: Light And Power
Contact: Cody Snowdon, 970-416-2306, csnowdon@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 11/04/2019
06/30/2020: FOR INFORMATION:
Thank you for providing the easement documentation. This easement will need
Page 3 of 4
to be recorded at the time of approval.
Easement is with the city being recorded
11/04/2019: FOR FINAL:
In viewing the provided survey, it appears that the existing transformer is
partially outside of the existing 9' Utility Easement. For this transformer to be
used as a shared power source, it will be required that the transformer and
transformer pad be completely within a dedicated City Utility Easement with 5'
of clearance on all side to allow for construction activities if the transformer
requires replacement. If the Verizon Wireless Utility Easement illustrated on the
plans is to be a City Utility Easement and not a private Easement, the proposed
easement will suffice.
The easement is noted as “City of Fort Collins Utility Easement, Reception No.______”
And will be recorded as such.
Comment Number: 2 Comment Originated: 11/04/2019
02/07/2022: FOR FINAL APPROVAL:
A Customer Owned Service Information Form (C-1 Form) and a one-line
diagram for all commercial meters will need to be completed and submitted to
Light & Power Engineering for review prior to Final Plan. A link to the C-1 Form
is below:
https://www.fcgov.com/utilities/img/site_specific/uploads/c-1_form.pdf?159767 7310
See attached C-1 form and one-line diagram.
06/30/2020: FOR FINAL APPROVAL:
To ensure that the existing transformer is adequate for the project's electrical
requirements, please provide, at a minimum, the anticipated service size and
number of cables required for the service.
See attached C-1 form and one-line diagram.
11/04/2019: FOR FINAL APPROVAL:
A commercial service information form (C 1 form) and a one-line diagram for all
commercial meters will need to be completed and submitted to Light & Power
Engineering for review prior to Final Plan. A link to the C 1 form is below:
http://zeus.fcgov.com/utils procedures/files/EngWiki/WikiPdfs/C/C 1Form.pdf
See attached C-1 form and one-line diagram.
Comment Number: 5 Comment Originated: 02/07/2022
02/07/2022: FOR FINAL:
On the one-line diagram, please show the main disconnect size and meter
sequencing. A copy of our meter sequencing can be found in our electric
policies practices and procedures below.
http://www.fcgov.com/utilities/business/builders-and-developers/development-fo
rms-guidelines-regulations
See attached C-1 form and one-line diagram.
Page 4 of 4
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcounty@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 10/30/2019
02/04/2022: FOR FINAL APPROVAL-UNRESOLVED:
All plan sheets must be 24"x36".
06/26/2020: FOR FINAL APPROVAL-UNRESOLVED:
All plan sheets must be 24"x36".
10/30/2019: FOR FINAL APPROVAL:
All plan sheets must be 24"x36".
Sheets have been updated to 24”x36”
Comment Number: 5 Comment Originated: 02/04/2022
02/04/2022: FOR FINAL APPROVAL:
There are line over text issues. See redlines.
Redlines addressed