Loading...
HomeMy WebLinkAboutIMPALA REDEVELOPMENT - FDP230001 - SUBMITTAL DOCUMENTS - ROUND 3 - SUPPORTING DOCUMENTATION (6)Project Number Building address or number Residential or Non-Residential Pressure Zone at Project Fixture Value Number of Subtotal Fixture or Appliance (at 60 psi) Fixtures Fixture Value Toilet (tank) 4 13 52 Toilet (flush valve) 35 0 Urinal (wall or stall) 16 0 Urinal (flush valve) 35 0 Bidet 2 0 Shower (single head) 2.5 11 27.5 Sink (lavatory) 1.5 20 30 Kitchen Sink 2.2 11 24.2 Utility Sink 4 1 4 Dishwasher 2 11 22 Bathtub 8 10 80 Clothes Washer 6 10 60 Hose connections (with 50 ft of hose) 1/2 in. 5 6 30 5/8 in. 9 0 3/4 in. 12 0 Miscellaneous Bedpan washers 10 0 Drinking fountains 2 0 Dental units 2 0 Combined Fixture Value 329.7 Demand (gpm) 38 Pressure Adjustment Factor 0.9 Total Adjusted demand (gpm) 34.2 Preliminary Demand Size 1" Velocity (fps) 14.0 Required Meter Size 1-1/2" Review by: Approved by: Water Demand Estimate and Meter Sizing Using Fixture Values (Based on AWWA M22 Manual, Second Edition) Impala Redevelopment Building A