UTILITY XFMR
208/120V, 3PH, 4W
300KVA
T
HA
MLO
200A
EVA
MCB
400A
LCX
MCB
150A
150/2
150/2
150/2
150/2
400/3
150/2
150/2
150/2
150/2
150/2
150/2
200/3
METERSTACK 'MS-A'
1200A, 120/208V, 3PH, 4W, 65KAIC200NG400NG
G
N
#3/0
DWELLING UNIT LOAD CENTER
(TYPICAL FOR 10 UNITS)
HOUSE
PANEL
EVSE
PANEL
600A
3P 150SNG1200N
x X1 x X2
x X3 x X4 x X5
x X6
SERVICE DISCONNECT #1
SERVICE DISCONNECT #2 & #3
FEEDER SCHEDULE -ALUMINUM
FEEDER
TAG SETS NEUTRAL
SIZE
GROUND
SIZE
CONDUIT
(3W+G)
CONDUIT
(4W+G)
20 1 #12 Cu #12 Cu #12 Cu 3/4"3/4"
30 1 #8 #8 #8 3/4" 3/4"
40 1 #6 #6 #8 1" 1"
50 1 #4 #4 #8 1-1/4" 1-1/4"
60 1 #3 #3 #8 1-1/4" 1-1/2"
70 1 #2 #2 #6 1-1/2" 1-1/2"
80 1 #1 #1 #6 1-1/2" 2"
90 1 #1/0 #1/0 #6 2" 2"
100 1 #1/0 #1/0 #6 2" 2"
125 1 #2/0 #2/0 #4 2" 2"
150 1 #3/0 #3/0 #4 2" 2-1/2"
175 1 #4/0 #4/0 #4 2-1/2" 2-1/2"
200 1 250 kcmil 250 kcmil #4 2-1/2" 3"
225 1 300 kcmil 300 kcmil #2 3" 3"
250 1 350 kcmil 350 kcmil #2 3" 3"
275 1 500 kcmil 500 kcmil #2 3" 3-1/2"
300 1 500 kcmil 500 kcmil #2 3" 3-1/2"
350 2 #4/0 #4/0 #1 2-1/2" 2-1/2"
400 2 250 kcmil 250 kcmil #1 2-1/2" 3"
500 2 350 kcmil 350 kcmil #1/0 3" 3"
600 2 500 kcmil 500 kcmil #2/0 3" 3-1/2"
800 3 400 kcmil 400 kcmil #3/0 3" 3-1/2"
1000 4 350 kcmil 350 kcmil #4/0 3" 3"
1200 4 500 kcmil 500 kcmil 250 kcmil 3" 3-1/2"
1400 5 500 kcmil 500 kcmil 350 kcmil 3" 3-1/2"
1600 6 400 kcmil 400 kcmil 350 kcmil 3" 3-1/2"
2000 7 500 kcmil 500 kcmil 400 kcmil 3-1/2" 3-1/2"
3000 10 500 kcmil 500 kcmil 600 kcmil 4" 4"
4000 13 500 kcmil 500 kcmil 750 kcmil 4" 4"
NOTES:
PHASE
SIZE
A. FEEDER TAG WITH SUBSCRIPT "G" INDICATES (3) PHASE CONDUCTORS AND (1)
EQUIPMENT GROUND CONDUCTOR.
B. FEEDER TAG WITH SUBSCRIPT "NG" INDICATES (3) PHASE CONDUCTORS, (1)
NEUTRAL CONDUCTOR AND (1) EQUIPMENT GROUND CONDUCTOR.
C. FEEDER TAG WITH SUBSCRIPT "NNG" INDICATES (3) PHASE CONDUCTORS, (2)
NEUTRAL CONDUCTORS AND (1) EQUIPMENT GROUND CONDUCTOR.
D. FEEDER TAG WITH SUBSCRIPT "N" INDICATES (3) PHASE CONDUCTORS AND (1)
NEUTRAL CONDUCTOR.
E. FEEDER TAG WITH SUBSCRIPT "SG" INDICATES (2) PHASE CONDUCTORS AND (1)
EQUIPMENT GROUND CONDUCTOR.
F. FEEDER TAG WITH SUBSCRIPT "SNG" INDICATES (2) PHASE CONDUCTORS, (1)
NEUTRAL CONDUCTOR AND (1) EQUIPMENT GROUND CONDUCTOR.
A. ALL ELECTRICAL EQUIPMENT SHOWN IS NEW, UNLESS OTHERWISE NOTED.
B. METER MOUNTING HEIGHTS SHALL BE NO LOWER THAN 24" FROM FINAL GRADE
AND NO HIGHER THAN 78" FROM GRADE TO THE CENTER OF THE HIGHEST
METERS. REFER TO FORT COLLINS UTILITIES ELECTRIC SERVICE STANDARDS
FOR MORE INFORMATION.
C. REFER TO FEEDER SCHEDULE FOR FEEDER SIZE REQUIREMENTS BASED ON
DESIGNATION.
D. REFER TO PANEL SCHEDULES FOR ADDITIONAL EQUIPMENT INFORMATION.
E. REFER TO SHORT CIRCUIT SCHEDULE FOR CALCULATIONS OF AVAILABLE FAULT
CURRENT AT ELECTRICAL EQUIPMENT.
F. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED PER NEC 250.
INCLUDING METAL UNDERGROUND WATER PIPE, METAL FRAME OF BUILDING,
CONCRETE ENCASED ELECTRODE AND ROD AND PIPE ELECTRODES.
GROUNDING ELECTRODE CONDUCTOR SIZE AS NOTED ON ONE-LINE.
G. PROVIDE TYPE 1 OR 2 SPD INTEGRAL TO MAIN SWITCHGEAR EQUIPMENT OR AT
DWELLING UNIT LOAD CENTERS.
SHEET NOTES
1999 BROADWAY
SUITE 2205
DENVER, CO
80202 | USA
(T) 720 644 5044
www.mazzetti.com
Project Number:
3575 Ringsby Ct, Ste 300A
STUDIO ARCHITECTURE
Denver, CO 80216
theSTUDIOarchitecture.com
866.529.9130
COPYRIGHTPLOT DATE:C
STUDIO Project No:
Sheet Issue & Revision Log
It is the client's responsibility prior to or during construction to notify the architect in
writing of any perceived errors or omissions in the plans and specifications of
which a contractor thoroughly knowledgeable with the building codes and methods
of construction should reasonably be aware. Written instructions addressing such
perceived errors or omissions shall be received from the architect prior to the client
or client's subcontractors proceeding with the work. The client shall be responsible
for any defects in construction if these procedures are not followed.
No Date Description
FOR REFERENCE ONLY
DRAWN BY:REVIEWED BY:BUILDING A004-600611
3/22/2023 9:33:27 AME500
SINGLE LINE DIAGRAM
& LOAD CALCS -
BLDG-A
21-017.00306 & 400 IMPALA DRIVEFORT COLLINS, COAuthor CheckerIMPALAREDEVELOPMENT
NTSE500
1 SINGLE LINE DIAGRAM - BLDG-A
2 12/16/22 100% DD
8 03/22/23 FDP RD 3
9 03/22/23 100% CD
SYSTEM VOLTAGE: 208 /1PH 131 A
TOTAL: 27,193 VA
SUB-TOTAL #2: 8,694 VA
V-1 8,694 VA
(1) HEAT PUMP
HEATING AND A/C LOADS - NEC 220.82(C)
(40%>10kVA) DEMAND SUB-TOTAL #1:18,499 VA
SUB-TOTAL: 31,247 VA
WATER HEATER 6,000 VA
(3)d WATER HEATERS
CLOTHES DRYER 5,000 VA
(3)c ELECTRIC CLOTHES DRYER
ELECTRIC RANGE 9,900 VA
(3)b ELECTRIC RANGE
REFRIGERATOR 750 VA
MICROWAVE 1,000 VA
DISHWASHER 750 VA
DISPOSAL 1,130 VA
(3)a APPLIANCES
SMALL APPLIANCE: 2 1,500 3,000 VA
LAUNDRY: 1 1,500 1,500 VA
(2) SMALL APPLIANCE & LAUNDRY BRANCH CIRCUITS
739 3 2,217 VA
(1) GENERAL LTG & RECS (SF x...
GENERAL LOADS - NEC 220.82(B)
LARGEST (1) BEDROOM UNIT - NEC 220.82
LOAD CALCULATION
SYSTEM VOLTAGE: 208 /1PH 132 A
TOTAL: 27,433 VA
SUB-TOTAL #2: 8,694 VA
V-1 8,694 VA
(1) HEAT PUMP
HEATING AND A/C LOADS - NEC 220.82(C)
(40%>10kVA) DEMAND SUB-TOTAL #1:18,739 VA
SUB-TOTAL: 31,847 VA
WATER HEATER 6,000 VA
(3)d WATER HEATERS
CLOTHES DRYER 5,000 VA
(3)c ELECTRIC CLOTHES DRYER
ELECTRIC RANGE 9,900 VA
(3)b ELECTRIC RANGE
REFRIGERATOR 750 VA
MICROWAVE 1,000 VA
DISHWASHER 750 VA
DISPOSAL 1,130 VA
(3)a APPLIANCES
SMALL APPLIANCE: 2 1,500 3,000 VA
LAUNDRY: 1 1,500 1,500 VA
(2) SMALL APPLIANCE & LAUNDRY BRANCH CIRCUITS
939 3 2,817 VA
(1) GENERAL LTG & RECS (SF x...
GENERAL LOADS - NEC 220.82(B)
LARGEST (2) BEDROOM UNIT - NEC 220.82
LOAD CALCULATION
SYSTEM VOLTAGE: 208 /1PH 141 A
TOTAL: 29,367 VA
SUB-TOTAL #2: 10,233 VA
V-2 10,233 VA
(1) HEAT PUMP
HEATING AND A/C LOADS - NEC 220.82(C)
(40%>10kVA) DEMAND SUB-TOTAL #1:19,134 VA
SUB-TOTAL: 32,834 VA
WATER HEATER 6,000 VA
(3)d WATER HEATERS
CLOTHES DRYER 5,000 VA
(3)c ELECTRIC CLOTHES DRYER
ELECTRIC RANGE 9,900 VA
(3)b ELECTRIC RANGE
REFRIGERATOR 750 VA
MICROWAVE 1,000 VA
DISHWASHER 750 VA
DISPOSAL 1,130 VA
(3)a APPLIANCES
SMALL APPLIANCE: 2 1,500 3,000 VA
LAUNDRY: 1 1,500 1,500 VA
(2) SMALL APPLIANCE & LAUNDRY BRANCH CIRCUITS
1268 3 3,804 VA
(1) GENERAL LTG & RECS (SF x...
GENERAL LOADS - NEC 220.82(B)
LARGEST (3) BEDROOM UNIT - NEC 220.82
LOAD CALCULATION
NEC TABLE 220.84 DEMAND FACTOR:43% 474 A
SYSTEM VOLTAGE: 208 /3PH 1,102 A
TOTAL: 396,709 VA
TOTAL DESIGN LOAD
(NEC 220.84 OPTIONAL METHOD)
SUB-TOTAL #2: 323,779 VA
V-1 (7.5 KW) 9 8,694 78,246 VA
V-2 (10 KW) 1 10,233 10,233 VA
F. HEATING AND A/C
WATER HEATER 5,000 50,000 VA
REFRIGERATOR 750 7,500 VA
MICROWAVE 1,000 10,000 VA
DISPOSAL 1,130 11,300 VA
DISHWASHER 750 7,500 VA
E. APPLIANCE LOADS (NEC 220.53)
ELECTRIC RANGE 9,900 99,000 VA
D. ELECTRIC RANGE (NEC 220.55)
CLOTHES DRYER 5,000 50,000 VA
C.ELECTRIC CLOTHES DRYER
(NEC 220.54)
SUB-TOTAL #1: 72,930 VA
SMALL APPLIANCE: 2 1,500 30,000 VA
LAUNDRY: 1 1,500 15,000 VA
B.SMALL APPLIANCE AND LAUNDRY
(NEC 220.52)
GENERAL LIGHTING (3VA/SF) 931 3 27,930 VA
A. LIGHTING LOADS (NEC 220.42)
QUANTITY: 10 UNITS
Impala Townhomes - Building A
LOAD CALCULATION
TOTAL:363.1 1009.1
PANEL 'EVA' 134.9 375.0
HOUSE PANEL 'HA' 57.6 160.0
DWELLING UNITS 170.6 474.1
kVA Amps
1200A, 120/208V, 3φ, 4-WIRE
LOAD SUMMARY: MS-A
NOTE: SHORT CIRCUIT CALCULATIONS ARE BASED ON BUSSMAN POINT TO POINT METHOD
F = (Isc,primary x Vprimary x 1.73 x %Z)/(100,000 x kVAxfmr)
THE SAME CALCULATIONS FOR THE FAULT CURRENT AT THE SECONDARY SIDE OF THE TRANSFORMER, F VALUE CHANGES:
F = (2 x L x Iavailable)/(C x n x EL-L)
THE SAME CALCULATIONS FOR SINGLE (1) PHASE LINE TO LINE, F VALUE CHANGES:
n = NUMBER OF CONDUCTORS PER PHASE
L = LENGTH OF RUN IN FEET
EL-L = LINE TO LINE VOLTAGE
C = VALUES FOUND IN BUSSMANN SPD HANDBOOK FOR CONDUCTORS AND BUSWAY
F = (1.73 x L x Iavailable)/(C x n x EL-L)
M = 1/(1+F)
Isc = (Iavailable)*M
THREE (3) PHASE LINE TO LINE SHORT CIRCUIT CALCULATIONS:
X6 UNIT LOAD CENTER (10KAIC) 9,806 0.199 4.031 8,826 208 75 49,335 --- ---
X5 UNIT LOAD CENTER (22KAIC) 10,359 0.210 3.762 8,826 208 70 49,335 --- ---
X4 EVA 34,654 0.702 0.424 24,244 208 25 49,335 --- ---
X3 HA 32,708 0.663 0.508 12,122 208 15 49,335 --- ---
X2 MS-A 49,335 0.640 0.563 85,560 208 75 77,100 --- ---
X1 AVAILABLE AT XFMR SECONDARY 77,100
POINT DESCRIPTION
SHORT
CIRCUIT
(Isc SYM RMS)
MULTIPLIE
R (M)
F FACTOR
(F)
CONSTANT
(C x n)
LINE-LINE
VOLTAGE
(V)
LENGTH
OF RUN (L)
CURRENT
AVAILABLE
(Iavailable)
XFMR
RATED
(kVA)
XFMR
IMPED (%Z)
SHORT CIRCUIT SCHEDULE