HomeMy WebLinkAboutIMPALA REDEVELOPMENT - FDP230001 - SUBMITTAL DOCUMENTS - ROUND 3 - SUPPORTING DOCUMENTATION (5)UTILITY XFMR
240-120V, 1PH, 3W
100KVA
T M
M
M
M
M
M
M
HD
MLO
150A
LCD
MCB
150A
M
M
EVD
MCB
200A
FIRE PUMP
5HP
150/2
150/2
150/2
150/2
150/2
150/2
150/2
METERSTACK 'MS-D'
800A, 120/240V, 1PH, 3W, 65KAIC 150SNGG
N
#3/0
DWELLING UNIT
LOAD CENTER
(TYPICAL FOR 6
UNITS)HOUSE
PANEL
600A
2P 150SNG800SN
UTILITY
METER
240V FIRE PUMP
CONTROLLER
(SERVICE
ENTRANCE
RATED)
100SN100SN
100SNG
x X1X1 x
x X4
x X2
x X3x X4
x X5
200/2200SNGEVSE
PANEL
x X3
#6
FEEDER SCHEDULE -ALUMINUM
FEEDER
TAG SETS NEUTRAL
SIZE
GROUND
SIZE
CONDUIT
(3W+G)
CONDUIT
(4W+G)
20 1 #12 Cu #12 Cu #12 Cu 3/4"3/4"
30 1 #8 #8 #8 3/4" 3/4"
40 1 #6 #6 #8 1" 1"
50 1 #4 #4 #8 1-1/4" 1-1/4"
60 1 #3 #3 #8 1-1/4" 1-1/2"
70 1 #2 #2 #6 1-1/2" 1-1/2"
80 1 #1 #1 #6 1-1/2" 2"
90 1 #1/0 #1/0 #6 2" 2"
100 1 #1/0 #1/0 #6 2" 2"
125 1 #2/0 #2/0 #4 2" 2"
150 1 #3/0 #3/0 #4 2" 2-1/2"
175 1 #4/0 #4/0 #4 2-1/2" 2-1/2"
200 1 250 kcmil 250 kcmil #4 2-1/2" 3"
225 1 300 kcmil 300 kcmil #2 3" 3"
250 1 350 kcmil 350 kcmil #2 3" 3"
275 1 500 kcmil 500 kcmil #2 3" 3-1/2"
300 1 500 kcmil 500 kcmil #2 3" 3-1/2"
350 2 #4/0 #4/0 #1 2-1/2" 2-1/2"
400 2 250 kcmil 250 kcmil #1 2-1/2" 3"
500 2 350 kcmil 350 kcmil #1/0 3" 3"
600 2 500 kcmil 500 kcmil #2/0 3" 3-1/2"
800 3 400 kcmil 400 kcmil #3/0 3" 3-1/2"
1000 4 350 kcmil 350 kcmil #4/0 3" 3"
1200 4 500 kcmil 500 kcmil 250 kcmil 3" 3-1/2"
1400 5 500 kcmil 500 kcmil 350 kcmil 3" 3-1/2"
1600 6 400 kcmil 400 kcmil 350 kcmil 3" 3-1/2"
2000 7 500 kcmil 500 kcmil 400 kcmil 3-1/2" 3-1/2"
3000 10 500 kcmil 500 kcmil 600 kcmil 4" 4"
4000 13 500 kcmil 500 kcmil 750 kcmil 4" 4"
NOTES:
PHASE
SIZE
A. FEEDER TAG WITH SUBSCRIPT "G" INDICATES (3) PHASE CONDUCTORS AND (1)
EQUIPMENT GROUND CONDUCTOR.
B. FEEDER TAG WITH SUBSCRIPT "NG" INDICATES (3) PHASE CONDUCTORS, (1)
NEUTRAL CONDUCTOR AND (1) EQUIPMENT GROUND CONDUCTOR.
C. FEEDER TAG WITH SUBSCRIPT "NNG" INDICATES (3) PHASE CONDUCTORS, (2)
NEUTRAL CONDUCTORS AND (1) EQUIPMENT GROUND CONDUCTOR.
D. FEEDER TAG WITH SUBSCRIPT "N" INDICATES (3) PHASE CONDUCTORS AND (1)
NEUTRAL CONDUCTOR.
E. FEEDER TAG WITH SUBSCRIPT "SG" INDICATES (2) PHASE CONDUCTORS AND (1)
EQUIPMENT GROUND CONDUCTOR.
F. FEEDER TAG WITH SUBSCRIPT "SNG" INDICATES (2) PHASE CONDUCTORS, (1)
NEUTRAL CONDUCTOR AND (1) EQUIPMENT GROUND CONDUCTOR.
A. ALL ELECTRICAL EQUIPMENT SHOWN IS NEW, UNLESS OTHERWISE NOTED.
B. METER MOUNTING HEIGHTS SHALL BE NO LOWER THAN 24" FROM FINAL GRADE
AND NO HIGHER THAN 78" FROM GRADE TO THE CENTER OF THE HIGHEST
METERS. REFER TO FORT COLLINS UTILITIES ELECTRIC SERVICE STANDARDS
FOR MORE INFORMATION.
C. REFER TO FEEDER SCHEDULE FOR FEEDER SIZE REQUIREMENTS BASED ON
DESIGNATION.
D. REFER TO PANEL SCHEDULES FOR ADDITIONAL EQUIPMENT INFORMATION.
E. REFER TO SHORT CIRCUIT SCHEDULE FOR CALCULATIONS OF AVAILABLE FAULT
CURRENT AT ELECTRICAL EQUIPMENT.
F. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED PER NEC 250.
INCLUDING METAL UNDERGROUND WATER PIPE, METAL FRAME OF BUILDING,
CONCRETE ENCASED ELECTRODE AND ROD AND PIPE ELECTRODES.
GROUNDING ELECTRODE CONDUCTOR SIZE AS NOTED ON ONE-LINE.
G. PROVIDE TYPE 1 OR 2 SPD INTEGRAL TO MAIN SWITCHGEAR EQUIPMENT OR AT
DWELLING UNIT LOAD CENTERS.
SHEET NOTES
1999 BROADWAY
SUITE 2205
DENVER, CO
80202 | USA
(T) 720 644 5044
www.mazzetti.com
Project Number:
3575 Ringsby Ct, Ste 300A
STUDIO ARCHITECTURE
Denver, CO 80216
theSTUDIOarchitecture.com
866.529.9130
COPYRIGHTPLOT DATE:C
STUDIO Project No:
Sheet Issue & Revision Log
It is the client's responsibility prior to or during construction to notify the architect in
writing of any perceived errors or omissions in the plans and specifications of
which a contractor thoroughly knowledgeable with the building codes and methods
of construction should reasonably be aware. Written instructions addressing such
perceived errors or omissions shall be received from the architect prior to the client
or client's subcontractors proceeding with the work. The client shall be responsible
for any defects in construction if these procedures are not followed.
No Date Description
FOR REFERENCE ONLY
DRAWN BY:REVIEWED BY:BUILDING D004-600611
3/22/2023 10:12:39 AME500
SINGLE LINE DIAGRAM
-BLDG-D
21-017.00306 & 400 IMPALA DRIVEFORT COLLINS, COAuthor CheckerIMPALA RENOVATIONSNTSE500
1 SINGLE LINE DIAGRAM - BLDG-D
1 12/16/22 100% DD
2 03/22/23 100% CD
SYSTEM VOLTAGE: 240 /1PH 113 A
TOTAL: 27,193 VA
SUB-TOTAL #2: 8,694 VA
LARGEST VRP UNIT 8,694 VA
(1) HEAT PUMP
HEATING AND A/C LOADS - NEC 220.82(C)
(40%>10kVA) DEMAND SUB-TOTAL #1:18,499 VA
SUB-TOTAL: 31,247 VA
WATER HEATER 6,000 VA
(3)d WATER HEATERS
CLOTHES DRYER 5,000 VA
(3)c ELECTRIC CLOTHES DRYER
ELECTRIC RANGE 9,900 VA
(3)b ELECTRIC RANGE
REFRIGERATOR 750 VA
MICROWAVE 1,000 VA
DISHWASHER 750 VA
DISPOSAL 1,130 VA
(3)a APPLIANCES
SMALL APPLIANCE: 2 1,500 3,000 VA
LAUNDRY: 1 1,500 1,500 VA
(2) SMALL APPLIANCE & LAUNDRY BRANCH CIRCUITS
739 3 2,217 VA
(1) GENERAL LTG & RECS (SF x...
GENERAL LOADS - NEC 220.82(B)
LARGEST (1) BEDROOM UNIT - NEC 220.82
LOAD CALCULATION
SYSTEM VOLTAGE: 240 /1PH 114 A
TOTAL: 27,433 VA
SUB-TOTAL #2: 8,694 VA
LARGEST VRP UNIT 8,694 VA
(1) HEAT PUMP
HEATING AND A/C LOADS - NEC 220.82(C)
(40%>10kVA) DEMAND SUB-TOTAL #1:18,739 VA
SUB-TOTAL: 31,847 VA
WATER HEATER 6,000 VA
(3)d WATER HEATERS
CLOTHES DRYER 5,000 VA
(3)c ELECTRIC CLOTHES DRYER
ELECTRIC RANGE 9,900 VA
(3)b ELECTRIC RANGE
REFRIGERATOR 750 VA
MICROWAVE 1,000 VA
DISHWASHER 750 VA
DISPOSAL 1,130 VA
(3)a APPLIANCES
SMALL APPLIANCE: 2 1,500 3,000 VA
LAUNDRY: 1 1,500 1,500 VA
(2) SMALL APPLIANCE & LAUNDRY BRANCH CIRCUITS
939 3 2,817 VA
(1) GENERAL LTG & RECS (SF x...
GENERAL LOADS - NEC 220.82(B)
LARGEST (2) BEDROOM UNIT - NEC 220.82
LOAD CALCULATION
NEC TABLE 220.84 DEMAND FACTOR:44% 442 A
SYSTEM VOLTAGE: 240 /1PH 1,005 A
TOTAL: 241,122 VA
TOTAL DESIGN LOAD
(NEC 220.84 OPTIONAL METHOD)
SUB-TOTAL #2: 199,344 VA
V-1 (7.5 KW) 6 8,694 52,164 VA
F. HEATING AND A/C
WATER HEATER 6,000 36,000 VA
REFRIGERATOR 750 4,500 VA
MICROWAVE 1,000 6,000 VA
DISPOSAL 1,130 6,780 VA
DISHWASHER 750 4,500 VA
E. APPLIANCE LOADS (NEC 220.53)
ELECTRIC RANGE 9,900 59,400 VA
D. ELECTRIC RANGE (NEC 220.55)
CLOTHES DRYER 5,000 30,000 VA
C.ELECTRIC CLOTHES DRYER
(NEC 220.54)
SUB-TOTAL #1: 41,778 VA
SMALL APPLIANCE: 2 1,500 18,000 VA
LAUNDRY: 1 1,500 9,000 VA
B.SMALL APPLIANCE AND LAUNDRY
(NEC 220.52)
GENERAL LIGHTING (3VA/SF) 821 3 14,778 VA
A. LIGHTING LOADS (NEC 220.42)
QUANTITY: 6 UNITS
Impala Townhomes - Building D
LOAD CALCULATION
TOTAL:4.0 16.7
5 HP FIRE PUMP 4.0 16.7
kVA Amps
100A, 120/240V, 1φ, 3-WIRE
LOAD SUMMARY: FIRE PUMP
TOTAL:155.3 647.1
PANEL 'EVD'30.0 125.0
HOUSE PANEL 'HD' 19.2 80.0
DWELLING UNITS 106.1 442.1
kVA Amps
800A, 120/240V, 1φ, 3-WIRE
LOAD SUMMARY: MSB-D
NOTE: SHORT CIRCUIT CALCULATIONS ARE BASED ON BUSSMAN POINT TO POINT METHOD
F = (Isc,primary x Vprimary x 1.73 x %Z)/(100,000 x kVAxfmr)
THE SAME CALCULATIONS FOR THE FAULT CURRENT AT THE SECONDARY SIDE OF THE TRANSFORMER, F VALUE CHANGES:
F = (2 x L x Iavailable)/(C x n x EL-L)
THE SAME CALCULATIONS FOR SINGLE (1) PHASE LINE TO LINE, F VALUE CHANGES:
n = NUMBER OF CONDUCTORS PER PHASE
L = LENGTH OF RUN IN FEET
EL-L = LINE TO LINE VOLTAGE
C = VALUES FOUND IN BUSSMANN SPD HANDBOOK FOR CONDUCTORS AND BUSWAY
F = (1.73 x L x Iavailable)/(C x n x EL-L)
M = 1/(1+F)
Isc = (Iavailable)*M
THREE (3) PHASE LINE TO LINE SHORT CIRCUIT CALCULATIONS:
X7 UNIT LOAD CENTER (10KAIC) 9,930 0.241 3.157 8,826 240 81 41,274 --- ---
X6 UNIT LOAD CENTER (22KAIC) 10,024 0.243 3.118 8,826 240 80 41,274 --- ---
X5 FIRE PUMP 7,987 0.194 4.168 5,777 240 70 41,274 --- ---
X4 EVD 30,468 0.738 0.355 24,244 240 25 41,274 --- ---
X3 HD 28,952 0.701 0.426 12,122 240 15 41,274 --- ---
X2 MS-D 41,274 0.535 0.868 55,515 240 75 77,100 --- ---
X1 AVAILABLE AT XFMR SECONDARY 77,100
POINT DESCRIPTION
SHORT
CIRCUIT
(Isc SYM RMS)
MULTIPLIE
R (M)
F FACTOR
(F)
CONSTANT
(C x n)
LINE-LINE
VOLTAGE
(V)
LENGTH
OF RUN (L)
CURRENT
AVAILABLE
(Iavailable)
XFMR
RATED
(kVA)
XFMR
IMPED (%Z)
SHORT CIRCUIT SCHEDULE