HomeMy WebLinkAboutSUN COMMUNITIES - THE FOOTHILLS - FDP220005 - SUBMITTAL DOCUMENTS - ROUND 3 - SUPPLEMENTAL INFORMATION (2)400A
MCB
KWH
METER
#3/0 GEC
(REFER TO GROUNDING
& BONDING DETAIL)
UTILITY 'XFMR'
120/240V. 1Ø. 3W.
LOCAL ENERGY
CTC
RP-"A"
(2) SETS OF 4"C. EA. W/ 3-600KCM
NOTES:
1.REFER TO SHEET E.001 FOR ELECTRICAL SYMBOL LIST,
ABBREVIATIONS, AND PROJECT NOTES.
2.ALL WIRING SHALL BE COPPER UNLESS OTHERWISE NOTED.
3.ALL WORK SHALL BE COORDINATED WITH THE LOCAL ELECTRIC
UTILITY COMPANY REPRESENTATIVE AND PROVIDED IN
ACCORDANCE WITH THEIR REQUIREMENTS.
4.PROVIDE ENGRAVED NAMEPLATES FOR ALL ELECTRICAL
EQUIPMENT (SWITCHBOARDS, TRANSFORMERS, PANEL-BOARDS,
SAFETY SWITCHES, MOTOR STARTERS, ETC.) INDICATING THE
IDENTITY OF THE EQUIPMENT AND THE POWER SOURCE FOR EACH.
5.ELECTRICAL SYSTEM SHALL BE LABELED WITH THE INSTALLING
CONTRACTOR'S COMPANY NAME AND CONTACT INFORMATION.
6.PROVIDE TYPE-WRITTEN DIRECTORY FOR ALL PANEL BOARDS.
POWER ONE-LINE DIAGRAM
N.T.S.
400A
MCB
RP-"B"
4"C. 3-600KCM
#1/0 SEG#1/0 SEG
1"C. 3 #6, #8G. TO
PANEL "MB" IN
MAIL BUILDING
SERVICE LOAD CALCULATION
PANEL "RP-A"64.9 KVA
PANEL "RP-B"68.7 KVA
PANEL "MB"0.64 KVA
SUB-TOTAL 134.24 KVA
SPARE 20.5 KVA
GRAND TOTAL 154.7 KVA = 644 AMPS @ 240V. 1Ø.
3"C. 3 #3/0, #4G. TO
PANEL "PE" IN POOL
BUILDING
Fort Collins - Clubhouse
One-line Diagram
21-0030
Joe Leahu Jordan Koenig
SKE-16/13/22