HomeMy WebLinkAboutNORTH LEMAY PLAZA PUD - FINAL - 57-87A - CORRESPONDENCE - APPLICANT COMMUNICATION■
n�
GEFROH HATTMAN INC.
ARCHITECTS/PLANNERS
CONSTRUCTION MANAGEMENT
135 West Swallow Road
Fort Collins, CO 80525
January 1 1 , 1988 (303) 223-7335
Mr. Felix Lee
City of Fort Collins
Director of Building Department
Box 580
Fort Collins, CO 80522
RE: NORTH LEMAY P.U.D.
Dear Mr. Lee:
�r i' gees
--JV
The information submitted with this letter is being forwarded to your office
for review through the Planning Department.
This information is provided as documentation to support this project request
of energy related points within the Planning process.
The project consists of two buildings -- one, a 2604 sq. ft. convenience store;
the other, a 10,672 sq. ft. retail building. The construction techniques for
both buildings will be similar. Each will be single story in nature, 2"A''
framing wall with brick veneer slab on grade floors and wood truss pitches roof
framing.
There are two separate points charts submitted for this project: A points chart
"D" for road side and auto related commercial and a points chart "E" business
service uses. On both charts we are requesting 4 points out of a possible 8
points or 50% of the total energy points allowable for such a complex.
The following is a review of Chapter 6 of the model energy code for the City and
State. It is our contention that by designing a more thermally efficient build-
ing envelope that this can reduce the non-renewable fossil type fuel consumption
of this project to warrant credit for these points. The following summary of the
two thermal envelopes demonstrates an average of 40% savings of energy through a
heating season which we think is a substantial savings over and above the base
line requirements set by City standards; therefore, warranting the points being
granted.
The following is our findings.
S i nce re y you •��is���sriz�°•
a•• V VC
F edric F�eJ. Haftm
V ice Pres, dent
kam rr.-1637 e
cc: Ted Shepard °°o`'Q0 AR'��`�,
41/U 11 I II a'�•••
MODEL ENERGY CODE COMPLIANCE
CONVENIENCE STORE
NORTH LEMAY P.U.D.
BUILDING ENVELOPE
Building Footprint 26o4 Sq. Ft.
Building Dimensions 62X42
Floor to Ceiling Height of
Heated Space 10 Ft.
Temperature Differential 72° F.
Heating Season 6600 Degree Days
CODE COMPLIANT - Base Data For This Building
Table Values of Surface Aggregate
Walls U = 0.26
Roof/Ceiling U° = 0.07
Slab R° = 5.4
BASE CRITERIA U Wall X Area Wall + U Roof X Area Roof
Building U0 = 0 0
SURFACE AREA
= 0.26 X 2080 + 0.07 X 2604
4684
0.15
SPECIFIC BUILDING - Envelope Value
Wall Face Brick
R =
.75
Insulated Sheathing
R =
2.50
Air Space
R =
1.01
Batt Insulation
R =
19.00
Wood Studs
R =
6.875
Gypsum Board
R =
0.45
Assume 14% of Wall is
Solid Wood Framing R = 11.58
Assume 86% of Wall is
Filled With Insulation R = 23.71
Glass Store Front Aluminum Frame and 1" Insulation Glass U = .49
Wall Surfaces 540 Sq. Ft. Glass tore Front
216 Sq. Ft. Solid Wall
1324 Sq. Ft. Void Wall
Wall U0 = UG X Glass Area + USW X Solid Wall Area + UVW X Void Wall Area
Surface Area
= 0.49_X_540 + 0.086 X 216 + 0.042 X 1324
2080
338.77
2080
.16
A
MODEL ENERGY CODE COMPLIANCE
NORTH LEMAY P.U.D.
Page 2
Roof/Ceiling Suspended Ceiling R = 1.78
MR Space R = .94
Truss R = 6.875
Insulation R = 40.00
Assume 14% of Roof is Framing R = 9.59
Assume 86% of Roof Space is Void R = 42.72
Uo Roof = UR Area Truss + UR X Area of Insulation
Roof Area
0.104 x 364. + 0.023 X 2240
2 0
+ .034
Overall Envelope U Values = UW X AW + UR + A
SURFACE AREA
.16 X 2080 + .034 X 2604
46
Uo = 0.09
Base Data Uo = 0.15
ENERGY CONSUMPTION- At design differential
Base Data AS X Uo X At = BTUH
4684 X 0.15 X 72 = 51936 BTUH
Building as Designed AS X Uo X At = BTUH
4684 X 0.09 X 72 = 30352 BTUH
ENERGY CONSUMPTION - Seasonal
Base Data AS X Uo X DD = MBTU/Season
4684 X 0.15 X 6600 = 4,760 MBTU/Season =
Building as designed AS X Uo X DD = MBTU/Season
4684 X 0.09 X 6600 = 2782 MBTU/Season =
2782 MBTU = 58%
7�+ 6o MBTU -
Percent of Fuel Savings 42% Per Season
4
MODEL ENERGY CODE COMPLIANCE
RETAIL STORES
NORTH LEMAY P.U.D.
BUILDING ENVELOPE
Building Footprint 10,672 Sq. Ft.
Building Dimensions 70 X 160
Floor to Ceiling Height of
Heated Space 10 Ft.
Temperature Differential 72° F.
Heating Season 6600 Degree Days
CODE COMPLIANT - Base Data for this Building
Table Values of Surface Aggregate
Walls U = 0.26
Roof/Ceiling U° = 0.07
Slab R° = 5.4
BASE CRITERIA
Uo = U° Wall X Area Wall + U° Roof X Area Roof
SURFACE AREA
0.26 X 4600 + m7 X 1o,672
15,272
Uo =
0.127
SPECIFIC BUILDING - Envelope Value
Wall - Face Brick
R = .75
Insulating Sheathing
R = 2.50
Air Space
R = 1.01
Batt Insulation
R = 19.00
Wood Studs
R = 6.875
Gypsum Board
R = 0.45
Assume 140 of Wall is
Solid
Wood Framing
R = 11.58
Assume 86% of Wall is
Stud Space
R = 23.71
Glass Store Front Aluminum
Frame and 1"
Insulating Glass UG = .49
Wall Surfaces
1400 Sq. Ft. Glass
448 Sq. Ft. Framing
2752 Sq. Ft. Stud Space
UW =
Uc X A Glass
+ OF X A Framing + US X A Space
600 Sq. Ft.
_ o.49 X 1400 + 0.089 X 448 + o.o43 X 2752
600 Sq. Ft.
0.034
0
•
MODEL ENERGY CODE COMPLIANCE
RETAIL STORES
NORTH LEMAY P.U.D.
Page 2
Roof/Ceiling - Suspended Ceiling
Air Space
Truss
Truss Space Insulation
Assume 14% of Wall is Solid Wood
Frame
Assume 860 of Insulated Space
R = 1.78
R = .94
R = 6.875
R = 40.00
R = 9.59
R = 42.72
U0 Roof = UR X A Truss + UR X A Insulation
Roof Area
0.104 x 1494 + 0.023 X 5178
10, 672 Sq. Ft.
0.034
Overall Envelope U Value = UW X AW + UR + AR
Surface Area
0.18 x 4600 + 0.034 X 1o,672
15,27E Sq. Ft.
U = 0.078
0
Base Data U0 = 0.127
ENERGY CONSUMPTION - At Design Differential
Base Data - A X U X At = BTUH
15�9274ox 0.127 x 72 = 139,665 BTUH
Building As Designed - A X U X At = BTUH
15,274oX 0.078 X 72 = 85,778 BTUH
ENERGY CONSUMPTION - Seasonal
Base Data - A X U X DD = MBTU/Season
1�,2740X 0.127 X 6600 = 12,802 MBTU/Season =
Building As Designed - A X U X DD = MBTU/Season
1�,274oX 0.078 x 6600 = 7863 MBTU/Season =
7,863 _ 610
12,802
Percent of Fuel Savings 39%
CONCLUSIONS: The code calls for slab on grade to have a perimeter insulation
R = 5.4. Using a dow SM board 1�" thick, the insulation value is R = 7.5. The
perimeter edge loss is 50% higher than code standard for purposes of these cal-
culations of energy savings. This differential in values was negated in order to
establish values for the envelope subject to air to air heat loss.
The decrease in fuel consumption due to the increase in thermal value for the
exposed envelope shows a measured reduction in fossil fuel required for these
structures over City standards. Values approaching 40% were achieved by both
buildings which we feel warrant the allowance of 4 points for energy conservation
for each Point Chart.