H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.0_Storm A_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM A PLAN & PROFILE
C6.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.1_Storm B_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM B PLAN & PROFILE
C6.1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.1_Storm B_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
ALS
JEP
STORM B PLAN & PROFILE
C6.2
SCALE: 1"=50'
0 20 5010
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.1_Storm B_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM B2,B3 PLAN & PROFILE
C6.3
SCALE: 1"=50'
0 20 5010
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.4_Storm C_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM C PLAN & PROFILE
C6.4
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.4_Storm C_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM C,C2,C3 PLAN & PROFILE
C6.5
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.6_Storm D_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM D PLAN & PROFILE
C6.6
CENTERLINE
10' WIDE DIRT ROAD
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.7_Storm E_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM E, E3 PLAN & PROFILE
C6.7
SCALE: 1"=50'
0 20 5010
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.7_Storm E_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
ALS
JEP
STORM Z PLAN & PROFILE
C6.8
SCALE: 1"=50'
0 20 5010
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.7_Storm E_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM E5, Z2, Z3, Z5, Z2.1 PLAN & PROFILE
C6.9
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
F
F
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.10_Storm F_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM F PLAN & PROFILE
C6.10
FGFFF-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.10_Storm F_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM F2,F3, F4 PLAN & PROFILE
C6.11
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
F
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.10_Storm F_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM F3-A, F4A,F5 PLAN & PROFILE
C6.12
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
CENTERLINE10' WIDE DIRT ROAD-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.13_Storm G_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM G PLAN & PROFILE
C6.13
CENTERLINE
10' WIDE DIRT ROAD
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.14_Storm H_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM H AND H5 PLAN & PROFILE
C6.14
SCALE: 1"=50'
0 20 5010
G
F
F
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.15_Storm I_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM I AND I4-A PLAN & PROFILE
C6.15
SCALE: 1"=50'
0 20 5010
G
F GF-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.15_Storm I_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM I,I2-A.1-1, I-3A PLAN & PROFILE
C6.16
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
GGGFFG
F
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.15_Storm I_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM I2A,I2A.2 PLAN & PROFILE
C6.17
SCALE: 1"=50'
0 20 5010
G
F
G
F
F
G GF-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.15_Storm I_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM I2A.3,I2A.4,I2A.5,I2A.6 PLAN & PROFILE
C6.18
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
F F-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.15_Storm I_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
ALS
JEP
STORM I4,I4.1,I4.2-1, I4.3 PLAN & PROFILE
C6.19
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.15_Storm I_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
ALS
JEP
STORM I5,I5A,I5A.1 PLAN & PROFILE
C6.20
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.15_Storm I_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
ALS
JEP
STORM I6,I6A,I6.1 PLAN & PROFILE
C6.21
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
CENTERLINE DITCH
CENTERLINE
DIRT DITCH
G
F
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.22_Storm J_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM J PLAN & PROFILE
C6.22
CENTERLINE DITCH-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.22_Storm J_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM J2,J3,J4 PLAN & PROFILE
C6.23
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
CENTERLINE DITCHDIRT DITCHCENTERLINE DITCH CENTERLINE DITCHDIRT DITCHCENTERLINEDITCH-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.22_Storm J_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
ALS
JEP
STORM J4.1,J5,J6,J7 PLAN & PROFILE
C6.24
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.25_Storm K,L_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM K PLAN & PROFILE
C6.25
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.25_Storm K,L_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM K2,K4,L, P PLAN & PROFILE
C6.26
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.27_Storm M_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM M PLAN & PROFILE
C6.27
DIRT DITCH-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.27_Storm M_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
ALS
JEP
STORM M,M1,M4,M7 PLAN & PROFILE
C6.28
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
SCALE: 1"=50'
0 20 5010
CITY OF GREELEY
MODULAR
HOME
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.29_Storm N_P&P.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
Know what's
before you dig.
SCALE: 1"=50'
0 20 5010
AMG
JEP
STORM N AND M-A PLAN AND PROFILE
C6.29
SCALE: 1"=50'
0 20 5010
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.XX_DR Details.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
JKD
JEP
STORM DETAILS
C6.30Know what's
before you dig.
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.XX_DR Details.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
JKD
JEP
STORM DETAILS
C6.31Know what's
before you dig.
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.XX_DR Details.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
JKD
JEP
STORM DETAILS
C6.32Know what's
before you dig.
CC
A
A
B
B
SECTION C-C
SECTION A-A SECTION B-B
WELL SCREEN FLOW CONTROL PLATE
PLAN
GENERAL NOTES
SECTION D-D
D
D
A A
ABBREVIATIONS
LEGEND
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.XX_DR Details.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
Know what's
before you dig.
JKD
JEP
STORM DETAILS
C6.33
CC
A
A
B
B
SECTION C-C
SECTION A-A SECTION B-B
WELL SCREEN FLOW CONTROL PLATE
PLAN
GENERAL NOTES
SECTION D-D
D
D
A A
ABBREVIATIONS
LEGEND
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.XX_DR Details.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
Know what's
before you dig.
JKD
JEP
STORM DETAILS
C6.34
CC
A
A
B
B
SECTION C-C
SECTION A-A SECTION B-B
WELL SCREEN FLOW CONTROL PLATE
PLAN
GENERAL NOTES
SECTION D-D
D
D
A A
ABBREVIATIONS
LEGEND
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.XX_DR Details.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
Know what's
before you dig.
JKD
JEP
STORM DETAILS
C6.35
CC
A
A
B
B
SECTION C-C
SECTION A-A SECTION B-B
WELL SCREEN FLOW CONTROL PLATE
PLAN
GENERAL NOTES
SECTION D-D
D
D
A A
ABBREVIATIONS
LEGEND
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.XX_DR Details.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
Know what's
before you dig.
JKD
JEP
STORM DETAILS
C6.36
CC
A
A
B
B
SECTION C-C
SECTION A-A SECTION B-B
WELL SCREEN FLOW CONTROL PLATE
PLAN
GENERAL NOTES
SECTION D-D
D
D
A A
ABBREVIATIONS
LEGEND
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.XX_DR Details.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
Know what's
before you dig.
JKD
JEP
STORM DETAILS
C6.37
CC
A
A
B
B
SECTION C-C
SECTION A-A SECTION B-B
WELL SCREEN FLOW CONTROL PLATE
PLAN
GENERAL NOTES
SECTION D-D
D
D
A A
ABBREVIATIONS
LEGEND
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.XX_DR Details.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
Know what's
before you dig.
JKD
JEP
STORM DETAILS
C6.38
CC
A
A
B
B
SECTION C-C
SECTION A-A SECTION B-B
WELL SCREEN FLOW CONTROL PLATE
PLAN
GENERAL NOTES
SECTION D-D
D
D
A A
ABBREVIATIONS
LEGEND
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6.XX_DR Details.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
Know what's
before you dig.
JKD
JEP
STORM DETAILS
C6.39
G
G
G
F
F
F
F
FFAIRCHILD STREETFAIRCHILD STREETDELOZIER ROADALLEY A
LOT 10 LOT 11 LOT 12 LOT 13 LOT 14
LOT 19
LOT 20LOT 21LOT 22
LOT 18
LOT 17
LOT 16
LOT 15
LOT 13
LOT 10 LOT 11
LOT 12
LOT 3
LOT 2
LOT 4
LOT 5
LOT 6
LOT 7
LOT 8
LOT 1
LOT 14
LOT 13
LOT 12
LOT 11
LOT 10
LOT 9
LOT 16
LOT 15
LOT 5 LOT 6 LOT 7
LOT 10LOT 11LOT 12
LOT 7LOT 6LOT 5
LOT 9
LOT 8
LOT 8
LOT 5 LOT 6 LOT 7
LOT 10LOT 11LOT 12 LOT 9
LOT 8
LOT 15 LOT 14 LOT 13 LOT 12 LOT 11
LOT 8LOT 7LOT 6LOT 5LOT 4
LOT 10
LOT 9
LOT 3 LOT 4 LOT 5 LOT 6 LOT 7
LOT 10LOT 11LOT 12LOT 13LOT 14 LOT 9
LOT 8
BLOCK 21
BLOCK 22
BLOCK 23
BLOCK 22
BLOCK 24
BLOCK 26
BLOCK 28
BLOCK 30
S S
S S
S S
S S
S S
S S
S
S
S
S
S
S
MM M
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C6_LIDLocations.dwg - Nate Whitcomb - 8/17/2022Init.# Issue / DescriptionDateBLOOM FILING ONEPRELIMINARY DEVELOPMENT PLANFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
HFH022
08.17.2022
Know what's
before you dig.
DESIGN POINT
DETENTION POND BASIN BOUNDARY
(i.e., MHFD-Detention_v4.03 and/or SWMM)
SUB-BASIN BOUNDARY (i.e., Rational Method)
OVERLAND FLOW DIRECTION
(I.E., LANDSCAPING)
DIRECT FLOW DIRECTION
(I.E., PAVEMENT, CURB AND
GUTTER)
BASIN ID
2-YR RUNOFF
COEFFICIENT
BASIN AREA
(ACRES)
acres
A1
0.05
0.35 2.50
A
APPROXIMATE DETENTION POND
OVERFLOW PATH
100-YR RUNOFF
COEFFICIENT
BASE FLOOD ELEVATION
IRRIGATION POND LIMITS
IRRIGATION POND LIMITS
JKD
JEP
LID LOCATIONS
C6.40
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.0-C7.2_Waterline 1_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAPLINEMATCHSTA28+00MATCH LINESEE SHEET:STA:C7.128+00SCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
WATERLINE 1 PLAN & PROFILE
C7.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.0-C7.2_Waterline 1_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAP
LINEMATCHSTA19+00MATCH LINESEE SHEET:STA:C7.219+00SCALE: 1"=50'
0 20 5010LINEMATCHSTA28+00MATCH LINESEE SHEET:STA:C7.028+00Know what's
before you dig.
ALS
JEP
WATERLINE 1 PLAN & PROFILE
C7.1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.0-C7.2_Waterline 1_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAPSCALE: 1"=50'
0 20 5010LINEMATCHSTA19+00MATCH LINESEE SHEET:STA:C7.119+00Know what's
before you dig.
ALS
JEP
WATERLINE 1 PLAN & PROFILE
C7.2
WWWWWWWWWWWWWWWWWWWW W W WWW W W W W WWWWWWWW W
W WW F
W
F
W
W-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.3-C7.4_Waterline 2_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAP
LINEMATCHSTA24+00SCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
WATERLINE 2 PLAN & PROFILE
C7.3MATCH LINESEE SHEET:STA:C7.424+00
W F
CENTERLINE
10' WIDE DIRT ROAD
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.3-C7.4_Waterline 2_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAPSCALE: 1"=50'
0 20 5010
LINEMATCHSTA24+00MATCH LINESEE SHEET:STA:C7.324+00Know what's
before you dig.
ALS
JEP
WATERLINE 2 PLAN & PROFILE
C7.4
WWWWWWWWWW WWWWWWWWWWWWWWWWWWWWW
W
WWWWW
W
WWW
W
WWWWWW-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.5-C7.8_Waterline 3_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAPLINEMATCHSTA60+00MATCH LINESEE SHEET:STA:C7.660+00SCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
WATERLINE 3 PLAN & PROFILE
C7.5
WWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWW W
WWWWWWWWWWWWWWWWWWWWWWWWWW W GWWFWFWF-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.5-C7.8_Waterline 3_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAP
LINEMATCHSTA49+50MATCH LINESEE SHEET:STA:C7.749+50SCALE: 1"=50'
0 20 5010
LINEMATCHSTA60+00MATCH LINESEE SHEET:STA:C7.560+00Know what's
before you dig.
ALS
JEP
WATERLINE 3 PLAN & PROFILE
C7.6
WWWWWWWWWWWWW WWWWWWWWWW W W W
WWW W
WWWFW-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.5-C7.8_Waterline 3_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAPSCALE: 1"=50'
0 20 5010LINEMATCHSTA49+50MATCH LINESEE SHEET:STA:C7.649+50LINEMATCHSTA39+50MATCH LINESEE SHEET:STA:C7.839+50Know what's
before you dig.
ALS
JEP
WATERLINE 3 PLAN & PROFILE
C7.7
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.5-C7.8_Waterline 3_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAPSCALE: 1"=50'
0 20 5010
LINEMATCHSTA39+50MATCH LINESEE SHEET:STA:C7.739+50Know what's
before you dig.
ALS
JEP
WATERLINE 3 PLAN & PROFILE
C7.8
WWWWWWWW
W
W
W
W
W
W
W
W
W
WWWWWWWWWWWWWWWWW WWWWW-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.9-C7.10_Waterline 4-5_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAPSCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
WATERLINE 4 PLAN & PROFILE
C7.9
W WW W W W W
W WW
W W W W W W
WW
W
W
W
W
W
W
W
W
W
W
W
W W
W
W
WWW
W
WWWW
W
W
W
WWWW
W
WWWWW
CENTERLINE
10' WIDE DIRT ROAD
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.9-C7.10_Waterline 4-5_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAPSCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
WATERLINE 5 PLAN & PROFILE
C7.10
W
W WW
W
W
W
W
W
W
W
W
W
W
W
W
WW
W
W
WWWWWWWWWW
W
WWWW
W
W
CENTERLINE
10' WIDE DIRT ROAD
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.11-C7.12_Waterline 6-7_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAPSCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
WATERLINE 6 PLAN & PROFILE
C7.11
W
W
W
W
W
W
W
W
W
W
W WW W
W W
W
W
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.11-C7.12_Waterline 6-7_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAP
SCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
WATERLINE 7 PLAN & PROFILE
C7.12
WWWWWWWWWWWW WWWWWWWWWWWWWW
W WWW-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.13-C7.14_Waterline 8_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAPLINEMATCHSTA84+00MATCH LINESEE SHEET:STA:C7.1484+00SCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
WATERLINE 8 PLAN & PROFILE
C7.13
WWWWWWWWW
WWWWWWWWWWWWWWW WWWW
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.13-C7.14_Waterline 8_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAPSCALE: 1"=50'
0 20 5010LINEMATCHSTA84+00MATCH LINESEE SHEET:STA:C7.1384+00Know what's
before you dig.
ALS
JEP
WATERLINE 8 PLAN & PROFILE
C7.14
WWWWWWWWW WWWWWWWWWWWWWWWWWWWW WWWW W W W WWWWWWW WWWWW W W W
G
WWW W
W F
W
F
WW
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.15-C7.17_Waterline 9_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAP
LINEMATCHSTA99+00MATCH LINESEE SHEET:STA:C7.1699+00SCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
WATERLINE 9 PLAN & PROFILE
C7.15
WWW WWWWWWWWWWWWWWWWWGGGWFWFWW-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.15-C7.17_Waterline 9_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAPLINE
MATCH STA
105+00
MATCH LINESEE SHEET:STA:C7.17105+00SCALE: 1"=50'
0 20 5010
LINE
MATCH STA
99+00
MATCH LINESEE SHEET:STA:C7.1599+00Know what's
before you dig.
ALS
JEP
WATERLINE 9 PLAN & PROFILE
C7.16
W WWWWWW WWWWWWWWWW WWWWWWWWWGWWWWWWW WWFWWCENTERLINEDITCH-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.15-C7.17_Waterline 9_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAPSCALE: 1"=50'
0 20 5010
LINEMATCHSTA105+00MATCH LINESEE SHEET:STA:C7.16105+00Know what's
before you dig.
ALS
JEP
WATERLINE 9 PLAN & PROFILE
C7.17
WWWWWWW WW WWWWWWWWWWWW WW WWWWWW WWWWWWW W
WWW W
WWW W W-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.18-C7.20_Waterline 10-11_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAP
SCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
WATERLINE 10 PLAN & PROFILE
C7.18
DIRT DITCH
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.18-C7.20_Waterline 10-11_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAP
LINEMATCHSTA115+00MATCH LINESEE SHEET:STA:C7.20115+00SCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
WATERLINE 11 PLAN & PROFILE
C7.19
CITY OF GREELEY
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.18-C7.20_Waterline 10-11_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAPSCALE: 1"=50'
0 20 5010LINEMATCHSTA115+00MATCH LINESEE SHEET:STA:C7.19115+00Know what's
before you dig.
ALS
JEP
WATERLINE 11 PLAN & PROFILE
C7.20
CITY OF GREELEY
DIRT DITCH-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.21-7.22_Waterline 12_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAP
SCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
WATERLINE 12 PLAN AND PROFILE
C7.21LINEMATCHSTA127+50MATCH LINESEE SHEET:STA:C7.22127+50
CENTERLINEDITCHKnow what's
before you dig.
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.21-7.22_Waterline 12_P&P_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALLBE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL UNDERGROUND UTILITIES IN THE AREA OF THE WORK.BEFORE COMMENCING NEW CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES ANDSHALL BE RESPONSIBLE FOR ALL UNKNOWN UNDERGROUND UTILITIES.
2.ALL WATER AND SEWER CONSTRUCTION SHALL BE PER EAST LARIMER COUNTY WATER DISTRICT AND BOXELDER SANITATION DISTRICTSTANDARD CONSTRUCTION SPECIFICATIONS LATEST EDITION.
3.ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVEUTILITY PROVIDERS, AND ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL SANITARY SEWER MAINS, STORM SEWER MAINS, WATERMAINS & SERVICES.
6.CONFIRM EXISTING SANITARY SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
7.CONFIRM EXISTING STORM SEWER INVERT IN THE FIELD. IF IT DOESN'T MATCH THE ASSUMED INVERT, CONTACT THE DESIGN ENGINEER.
8.CONFIRM HORIZONTAL LOCATION OF WATER TO EXISTING LOCATIONS PRIOR TO CONSTRUCTION. CONTACT DESIGN ENGINEER WITH ANYDISCREPANCIES.
9.MINIMUM SEWER SLOPE IS 1.04% (18" / 1') FOR 6" DIAMETER AND 2.08% (14" / 1') FOR 4" DIAMETER.
10.CONTRACTOR TO COORDINATE GAS, ELECTRIC AND TELEPHONE CABLE SERVICES.
11.THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS OTHERWISE NOTED. EXACT LOCATIONS(HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVEDARCHITECTURAL DRAWINGS.
12.ROOF DRAIN CONNECTIONS TO BE COORDINATED WITH FINAL ARCHITECTURAL PLANS.
KEYMAP
SCALE: 1"=50'
0 20 5010
ALS
JEP
WATERLINE 12 PLAN AND PROFILE
C7.22LINEMATCHSTA127+50MATCH LINESEE SHEET:STA:C7.21127+50
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.X1-C7.X2_Water_Details_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
WATER DETAILS
C7.23CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.before you dig.Call
R
ALS
JEP
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C7.X1-C7.X2_Water_Details_F1.dwg - Matthew Kasch - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
WATER DETAILS
C7.24CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.before you dig.Call
R
ALS
JEP
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C8.0-C8.2_Irrigation P&P_F1.dwg - Jared Licht - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
SCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
IRRIGATION 1 PLAN & PROFILE
C8.0
LEGEND:
NOTES:
1. ALL UTILITY LOCATIONS SHOWN ARE BASED ON MAPS PROVIDED BY THE APPROPRIATE UTILITY COMPANY
AND FIELD SURFACE EVIDENCE AT THE TIME OF SURVEY AND IS TO BE CONSIDERED AN APPROXIMATE
LOCATION ONLY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY THE LOCATION OF ALL
UTILITIES, PUBLIC OR PRIVATE, WHETHER SHOWN ON THE PLANS OR NOT, PRIOR TO CONSTRUCTION.
REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO CONSTRUCTION.
2. PIPE LENGTHS ARE CALCULATED FROM THE CENTER OF MANHOLES AND INLET BOX STRUCTURES. LAYING
LENGTH INCLUDES FLARED END SECTIONS.
3. RCP SHALL BE CLASS III OR GREATER. PIPE MATERIAL, BEDDING, AND INSTALLATION WITHIN PUBLIC
RIGHTS-OF-WAY SHALL BE GOVERNED BY THE TOWN OF TIMNATH. ALTERNATES (SUCH AS ADS N-12 OR HP
SANITITE) OUTSIDE OF THE R.O.W. SHALL BE APPROVED IN ADVANCE BY THE ENGINEER. ALL JOINTS SHALL
BE 'WATERTIGHT' USING APPROPRIATE GASKETS OR JOINT WRAPS (PER ASTM C443 FOR RCP AND PER ASTM
F477 / D3212 FOR PLASTIC PIPE).
4. ALL STORM MANHOLES LOCATED IN SIDEWALKS AND TRAILS SHALL HAVE PEDESTRIAN RATED LIDS.
5. MANHOLE DIAMETERS SHOWN ARE PER CITY STANDARDS. CONTRACTOR SHALL VERIFY THAT MANHOLE
DIAMETERS ARE SUFFICIENT FOR INSTALLATION (i.e., WITHIN PRE-CASTER'S TOLERANCES, ETC.) OR 1' FROM
PIPE O.D. TO PIPE O.D. ON MANHOLE INSIDE FACE.
6. PROVIDE WATER TIGHT JOINTS PER ASTM C443 AT ALL CIRCULAR STORM PIPE.
7. MANHOLES SHALL BE SHAPED UNLESS OTHERWISE NOTED. REFER TO PLAN VIEW FOR SHAPED MANHOLES.
8. THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS
OTHERWISE NOTED. EXACT LOCATIONS (HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO
THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVED ARCHITECTURAL DRAWINGS.
9. CONTRACTOR TO FIELD VERIFY EXISTING INVERT ELEVATIONS AND REPORT ANY DISCREPANCIES TO THE
ENGINEER PRIOR TO CONSTRUCTION.
10. SEE SHEETS C8.3 AND C8.4 FOR IRRIGATION STRUCTURE DETAILS.
11. BOOSTER PUMPS SHALL NOT BE USED FOR IRRIGATION SYSTEMS.
12. IF NOTED AS SINGLE TAP WATER METER SHALL BE 3/4".
13. THE MINIMUM COVER OVER WATER LINES IS 5 FEET AND THE MAXIMUM COVER IS 6 FEET UNLESS OTHERWISE
NOTED IN THE PLANS AND APPROVED BY THE WATER UTILITY.
14. WATER MAINS SHALL BE C900 PVC WITH TRACER WIRE.
15. ALL WATER APPURTENANCES TO BE MECHANICALLY RESTRAINED. SEE NORTH WELD COUNTY WATER
DISTRICT VERTICAL AND HORIZONTAL BEND RESTRAINT DETAILS ON SHEET C8.2.
17. WATER TAPS SHALL BE 1" TO METER PIT AND 3/4" METER PIT TO RESIDENCE, FOR DOUBLE METER
CONDITIONS UNLESS OTHERWISE NOTED.
18. SEE DETAIL SHEET C8.5 FOR DOUBLE METER PIT DETAIL.
19. BACKFLOW PREVENTION DEVICES ARE REQUIRED ON ALL WATER SERVICES, REGARDLESS OF TYPE OR
HAZARD.
PROPOSED STORM INLET
EASEMENT LINE
PROPOSED LOTLINE
PROPOSED RIGHT-OF-WAY
PROPERTY BOUNDARY
PROPOSED CURB & GUTTER
EXISTING STORM SEWER
PROPOSED STORM SEWER
PROPOSED FIRE HYDRANT
EXISTING SANITARY SEWER
PROPOSED SANITARY SEWER
EXISTING WATER MAIN
PROPOSED WATER MAIN 8"W
8"SS
4900PROPOSED MAJOR CONTOUR
16"W
SS
EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
44PROPOSED MINOR CONTOUR
4552
4550
PROPOSED MANHOLE
EXISTING IRRIGATION
EXISTING FIBER OPTIC
IRR
FO
EXISTING GAS
EXISTING UNDERGROUND ELECTRIC UE
G
PROPOSED PIPE ENCASEMENT
CENTERLINE10' WIDE DIRT ROAD-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C8.0-C8.2_Irrigation P&P_F1.dwg - Jared Licht - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
SCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
IRRIGATION 2 PLAN & PROFILE
C8.1LINEMATCHSTA30+00MATCH LINESEE SHEET:STA:C8.230+00LEGEND:
NOTES:
1. ALL UTILITY LOCATIONS SHOWN ARE BASED ON MAPS PROVIDED BY THE APPROPRIATE UTILITY COMPANY
AND FIELD SURFACE EVIDENCE AT THE TIME OF SURVEY AND IS TO BE CONSIDERED AN APPROXIMATE
LOCATION ONLY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY THE LOCATION OF ALL
UTILITIES, PUBLIC OR PRIVATE, WHETHER SHOWN ON THE PLANS OR NOT, PRIOR TO CONSTRUCTION.
REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO CONSTRUCTION.
2. PIPE LENGTHS ARE CALCULATED FROM THE CENTER OF MANHOLES AND INLET BOX STRUCTURES. LAYING
LENGTH INCLUDES FLARED END SECTIONS.
3. RCP SHALL BE CLASS III OR GREATER. PIPE MATERIAL, BEDDING, AND INSTALLATION WITHIN PUBLIC
RIGHTS-OF-WAY SHALL BE GOVERNED BY THE TOWN OF TIMNATH. ALTERNATES (SUCH AS ADS N-12 OR HP
SANITITE) OUTSIDE OF THE R.O.W. SHALL BE APPROVED IN ADVANCE BY THE ENGINEER. ALL JOINTS SHALL
BE 'WATERTIGHT' USING APPROPRIATE GASKETS OR JOINT WRAPS (PER ASTM C443 FOR RCP AND PER ASTM
F477 / D3212 FOR PLASTIC PIPE).
4. ALL STORM MANHOLES LOCATED IN SIDEWALKS AND TRAILS SHALL HAVE PEDESTRIAN RATED LIDS.
5. MANHOLE DIAMETERS SHOWN ARE PER CITY STANDARDS. CONTRACTOR SHALL VERIFY THAT MANHOLE
DIAMETERS ARE SUFFICIENT FOR INSTALLATION (i.e., WITHIN PRE-CASTER'S TOLERANCES, ETC.) OR 1' FROM
PIPE O.D. TO PIPE O.D. ON MANHOLE INSIDE FACE.
6. PROVIDE WATER TIGHT JOINTS PER ASTM C443 AT ALL CIRCULAR STORM PIPE.
7. MANHOLES SHALL BE SHAPED UNLESS OTHERWISE NOTED. REFER TO PLAN VIEW FOR SHAPED MANHOLES.
8. THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS
OTHERWISE NOTED. EXACT LOCATIONS (HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO
THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVED ARCHITECTURAL DRAWINGS.
9. CONTRACTOR TO FIELD VERIFY EXISTING INVERT ELEVATIONS AND REPORT ANY DISCREPANCIES TO THE
ENGINEER PRIOR TO CONSTRUCTION.
10. SEE SHEETS C8.3 AND C8.4 FOR IRRIGATION STRUCTURE DETAILS.
11. BOOSTER PUMPS SHALL NOT BE USED FOR IRRIGATION SYSTEMS.
12. IF NOTED AS SINGLE TAP WATER METER SHALL BE 3/4".
13. THE MINIMUM COVER OVER WATER LINES IS 5 FEET AND THE MAXIMUM COVER IS 6 FEET UNLESS OTHERWISE
NOTED IN THE PLANS AND APPROVED BY THE WATER UTILITY.
14. WATER MAINS SHALL BE C900 PVC WITH TRACER WIRE.
15. ALL WATER APPURTENANCES TO BE MECHANICALLY RESTRAINED. SEE NORTH WELD COUNTY WATER
DISTRICT VERTICAL AND HORIZONTAL BEND RESTRAINT DETAILS ON SHEET C8.2.
17. WATER TAPS SHALL BE 1" TO METER PIT AND 3/4" METER PIT TO RESIDENCE, FOR DOUBLE METER
CONDITIONS UNLESS OTHERWISE NOTED.
18. SEE DETAIL SHEET C8.5 FOR DOUBLE METER PIT DETAIL.
19. BACKFLOW PREVENTION DEVICES ARE REQUIRED ON ALL WATER SERVICES, REGARDLESS OF TYPE OR
HAZARD.
PROPOSED STORM INLET
EASEMENT LINE
PROPOSED LOTLINE
PROPOSED RIGHT-OF-WAY
PROPERTY BOUNDARY
PROPOSED CURB & GUTTER
EXISTING STORM SEWER
PROPOSED STORM SEWER
PROPOSED FIRE HYDRANT
EXISTING SANITARY SEWER
PROPOSED SANITARY SEWER
EXISTING WATER MAIN
PROPOSED WATER MAIN 8"W
8"SS
4900PROPOSED MAJOR CONTOUR
16"W
SS
EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
44PROPOSED MINOR CONTOUR
4552
4550
PROPOSED MANHOLE
EXISTING IRRIGATION
EXISTING FIBER OPTIC
IRR
FO
EXISTING GAS
EXISTING UNDERGROUND ELECTRIC UE
G
PROPOSED PIPE ENCASEMENT
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C8.0-C8.2_Irrigation P&P_F1.dwg - Jared Licht - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
KEYMAP
SCALE: 1"=50'
0 20 5010
Know what's
before you dig.
ALS
JEP
IRRIGATION 2,3 PLAN & PROFILE
C8.2LINEMATCHSTA30+00MATCH LINESEE SHEET:STA:C8.130+00SCALE: 1"=50'
0 20 5010
LEGEND:
NOTES:
1. ALL UTILITY LOCATIONS SHOWN ARE BASED ON MAPS PROVIDED BY THE APPROPRIATE UTILITY COMPANY
AND FIELD SURFACE EVIDENCE AT THE TIME OF SURVEY AND IS TO BE CONSIDERED AN APPROXIMATE
LOCATION ONLY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY THE LOCATION OF ALL
UTILITIES, PUBLIC OR PRIVATE, WHETHER SHOWN ON THE PLANS OR NOT, PRIOR TO CONSTRUCTION.
REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO CONSTRUCTION.
2. PIPE LENGTHS ARE CALCULATED FROM THE CENTER OF MANHOLES AND INLET BOX STRUCTURES. LAYING
LENGTH INCLUDES FLARED END SECTIONS.
3. RCP SHALL BE CLASS III OR GREATER. PIPE MATERIAL, BEDDING, AND INSTALLATION WITHIN PUBLIC
RIGHTS-OF-WAY SHALL BE GOVERNED BY THE TOWN OF TIMNATH. ALTERNATES (SUCH AS ADS N-12 OR HP
SANITITE) OUTSIDE OF THE R.O.W. SHALL BE APPROVED IN ADVANCE BY THE ENGINEER. ALL JOINTS SHALL
BE 'WATERTIGHT' USING APPROPRIATE GASKETS OR JOINT WRAPS (PER ASTM C443 FOR RCP AND PER ASTM
F477 / D3212 FOR PLASTIC PIPE).
4. ALL STORM MANHOLES LOCATED IN SIDEWALKS AND TRAILS SHALL HAVE PEDESTRIAN RATED LIDS.
5. MANHOLE DIAMETERS SHOWN ARE PER CITY STANDARDS. CONTRACTOR SHALL VERIFY THAT MANHOLE
DIAMETERS ARE SUFFICIENT FOR INSTALLATION (i.e., WITHIN PRE-CASTER'S TOLERANCES, ETC.) OR 1' FROM
PIPE O.D. TO PIPE O.D. ON MANHOLE INSIDE FACE.
6. PROVIDE WATER TIGHT JOINTS PER ASTM C443 AT ALL CIRCULAR STORM PIPE.
7. MANHOLES SHALL BE SHAPED UNLESS OTHERWISE NOTED. REFER TO PLAN VIEW FOR SHAPED MANHOLES.
8. THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS 5' OUTSIDE OF BUILDING UNLESS
OTHERWISE NOTED. EXACT LOCATIONS (HORIZONTAL AND VERTICAL) OF ALL UTILITY CONNECTIONS INTO
THE PROPOSED BUILDING SHALL BE COORDINATED WITH THE APPROVED ARCHITECTURAL DRAWINGS.
9. CONTRACTOR TO FIELD VERIFY EXISTING INVERT ELEVATIONS AND REPORT ANY DISCREPANCIES TO THE
ENGINEER PRIOR TO CONSTRUCTION.
10. SEE SHEETS C8.3 AND C8.4 FOR IRRIGATION STRUCTURE DETAILS.
11. BOOSTER PUMPS SHALL NOT BE USED FOR IRRIGATION SYSTEMS.
12. IF NOTED AS SINGLE TAP WATER METER SHALL BE 3/4".
13. THE MINIMUM COVER OVER WATER LINES IS 5 FEET AND THE MAXIMUM COVER IS 6 FEET UNLESS OTHERWISE
NOTED IN THE PLANS AND APPROVED BY THE WATER UTILITY.
14. WATER MAINS SHALL BE C900 PVC WITH TRACER WIRE.
15. ALL WATER APPURTENANCES TO BE MECHANICALLY RESTRAINED. SEE NORTH WELD COUNTY WATER
DISTRICT VERTICAL AND HORIZONTAL BEND RESTRAINT DETAILS ON SHEET C8.2.
17. WATER TAPS SHALL BE 1" TO METER PIT AND 3/4" METER PIT TO RESIDENCE, FOR DOUBLE METER
CONDITIONS UNLESS OTHERWISE NOTED.
18. SEE DETAIL SHEET C8.5 FOR DOUBLE METER PIT DETAIL.
19. BACKFLOW PREVENTION DEVICES ARE REQUIRED ON ALL WATER SERVICES, REGARDLESS OF TYPE OR
HAZARD.
PROPOSED STORM INLET
EASEMENT LINE
PROPOSED LOTLINE
PROPOSED RIGHT-OF-WAY
PROPERTY BOUNDARY
PROPOSED CURB & GUTTER
EXISTING STORM SEWER
PROPOSED STORM SEWER
PROPOSED FIRE HYDRANT
EXISTING SANITARY SEWER
PROPOSED SANITARY SEWER
EXISTING WATER MAIN
PROPOSED WATER MAIN 8"W
8"SS
4900PROPOSED MAJOR CONTOUR
16"W
SS
EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
44PROPOSED MINOR CONTOUR
4552
4550
PROPOSED MANHOLE
EXISTING IRRIGATION
EXISTING FIBER OPTIC
IRR
FO
EXISTING GAS
EXISTING UNDERGROUND ELECTRIC UE
G
PROPOSED PIPE ENCASEMENT
IN
18"Ø
T.O.B.=4950.28
OUT
AASECTION A-A
SECTION B-B
B B
IRR STRC. 1.1 DETAILCCCONCRETE IRRIGATION
STRUCTURE- COLORADO
PRECAST (OR APPROVED EQUAL)
MH STEPS 12" O.C.
18" N-2000
CDOT CLOSE MESH GRATE
BOLTED TO BOX (or approved equal)
INV IN=4938.74
INSTALL 18" SLIDE GATE
(FRESNO VALVES OR
APPROVED EQUAL)
18" N-2000
3.5'
0.5'3.5'3.5'1.5'18"Ø
T.O.B.=4950.28
CDOT CLOSE MESH GRATE
BOLTED TO BOX (or approved equal)
INV IN=4938.74
INSTALL 18" SLIDE GATE
(FRESNO VALVES OR
APPROVED EQUAL)
3.5'1.5'SECTION C-C
18"Ø
T.O.B.=4950.28
CDOT CLOSE MESH GRATE
BOLTED TO BOX (or approved equal)
INV IN=4941.80
3.5'1.5'OUT18" N-2000-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C8.3_Irr_Details_F1.dwg - Jared Licht - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
IRRIGATION DETAILS
C8.3CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.before you dig.Call
R
ALS
JEP
SCALE: 1"=2'
0 1 2
IN
OUT18"Ø
T.O.B.=4948.59
OUT
AASECTION A-A
B B
CCCONCRETE IRRIGATION
STRUCTURE- COLORADO
PRECAST (OR APPROVED EQUAL)
MH STEPS 12" O.C.
18" N-2000
CDOT CLOSE MESH GRATE
BOLTED TO BOX (or approved equal)
INV IN=4935.19
18" N-2000
3.5'
0.5'3.5'3.5'1.5'18" N-200018"Ø
T.O.B.=4948.59
SECTION B-B
CDOT CLOSE MESH GRATE
BOLTED TO BOX (or approved equal)
INV IN=4935.19
INSTALL 18" SLIDE GATE
(FRESNO VALVES OR
APPROVED EQUAL)
3.5'1.5'18"Ø
T.O.B.=4948.59
SECTION C-C
CDOT CLOSE MESH GRATE
BOLTED TO BOX (or approved equal)
INV IN=4935.19
INSTALL 18" SLIDE GATE
(FRESNO VALVES OR
APPROVED EQUAL)
3.5'1.5'-
-
-
-
-
-
-
-
-
-
-
-
-
-
STAMP
H:\Hartford Homes\CO Fort Collins HFH22 - Mulberry\0CIV\3-CD\FDP_F1\HFH022_C8.3_Irr_Details_F1.dwg - Jared Licht - 8/17/2022Init.# Issue / DescriptionDateFINAL DEVELOPMENT PLANS BLOOM FILING ONEFORT COLLINS, COTHESE PLANS ARE AN INSTRUMENT OF SERVICE
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED
WITHOUT THE WRITTEN CONSENT OF GALLOWAY.
COPYRIGHTS AND INFRINGEMENTS WILL BE
ENFORCED AND PROSECUTED.
COPYRIGHT
GallowayUS.com
5265 Ronald Reagan Blvd., Suite 210
Johnstown, CO 80534
970.800.3300
PRELIMINARYNOT FOR BIDDINGNOT FOR CONSTRUCTIONDate:
Drawn By:
Project No:
Checked By:
08.17.2022
HFH000022
IRRIGATION DETAILS
C8.4CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.before you dig.Call
R
ALS
JEP
SCALE: 1"=2'
0 1 2