HomeMy WebLinkAboutFORT COLLINS NISSAN-KIA - FDP220011 - DOCUMENT MARKUPS - ROUND 1 - UTILITY PLANSSMOKEY ST.VENUS AVENUECOLLEGE AVE (HWY 287)BUENO DRIVE
MILKY WAY DRIVE
MARS DRIVEMERCURY DRIVENEPTUNE DRIVEFOSSIL CREEK TRAI
L
FOSSIL CREEKTRAILBNSF RAILROAD#5822#5828#5834#200#206#214#218
#201
#5836#5835#5817 EXISTING
#224#230
NISSAN
DEALERSHIP BUILDING
KIA
DEALERSHIP BUILDING
PROPOSED 8" WATER
EXISTING 24" IRRIGATION PIPE
PROPOSED 8" SANITARY
PROPOSED 8" WATER
CONNECT TO EXISTING
6" WATER
SANITARY SERVICE
CONNECT TO EXISTING
6" CAST IRON WATER
CONNECT TO EXISTING
14" AC WATER MAIN
PROPOSED STORM OUTFALL
PROPOSED UNDERGROUND DETENTION
EXISTING 14" AC WATER
PROPOSED 24" NORTH LOUDON
DITCH IRRIGATION BYPASS
PROPOSED GAS TO BE RELOCATED
WITH GRADING (SEE NOTE 11 &
DETAILED UTILITY PLANS)
PROPOSED WATER
& FIRE SERVICES
RELOCATED FIBER
OPTIC VAULTPROPOSED
SANITARY SERVICE
PROPOSED 24"
IRRIGATION LINE
PROPOSED STORM DRAIN
CONNECT
TO EXISTING
SANITARY SEWER
PROPOSED 8" SANITARY
PROPOSED
STORM DRAIN
PROPOSED
STORM DRAIN
PROPOSED STORM DRAIN
PROPOSED STORM DRAIN
PROPOSED STORM DRAIN
PROPOSED 8" WATER
LOT 23
LOT 24
LOT 25
LOT 26
LOT 27
LOT 28
LOT 31
LOT 29
LOT 32
LOT 1
LOT 2
LOT 30
PROPOSED STORM
PROPERTY BOUNDARY (TYP.)
LOT 1
BLOCK 1
LOT 2
BLOCK 1
LOT 1
BLOCK 2
TRACT A
TRACT B
TRACT C
TRACT D
LOT 1
RISING SON
MANOR
SUBDIVISION
SILVERTHORNE LLC
WWW PROPERTIES LLC
CITY OF FORT COLLINS
EXISTING CULVERT TO REMAIN
FOSSIL
C
R
E
E
K
LAN
G
G
U
L
C
H
PROPOSED FIRE HYDRANT
FOSSIL CREEK
FLOODPLAIN/FLOODWAY
FOSSIL CREEK
FLOODPLAIN/FLOODWAY
WATER & FIRE SERVICES
EXISTING SANITARY STUB
TO BE ABANDONED PER
SFCSD STANDARDS
PROPOSED TRANSFORMER
PROPOSED
TRANSFORMER
PRIMARY ELECTRIC PER
CITY OF FORT COLLINS
PROPOSED FDC
PROPOSED
FDC
PROPOSED FIRE HYDRANT
PROPOSED FIRE
HYDRANT
PROPOSED
FIRE HYDRANT
PROPOSED
FIRE HYDRANTVENUS AVENUEPREPARED FOR:JOB NUMBER
SHEET NUMBER
SHEETSOF DATE SUBMITTED:VERTICAL:
HORIZONTAL:
SCALEFINAL REVIEWPLANSNOT FOR CONSTRUCTIONPROJ. MGR:DRAWING NAME:PATH:DESIGNER:DATE:TIME:The engineer preparing these plans will not be responsible for, or liable for, unauthorizedchanges to or uses of these plans. All changes to the plans must be in writing and mustbe approved by the preparer of these plans.NO.BYDATECAUTIONREVISIONS:CIVIL ENGINEERING & CONSULTING
UNITED CIVIL
Design Group
19 OLD TOWN SQUARE #238FORT COLLINS, CO 80524
(970) 530-4044
www.unitedcivil.com
TCC CORPORATIONFORT COLLINS NISSAN-KIA6/15/2022U21004
1" = 80'
1" = N/A
6/15/202210:47:37 AME:\UNITED CIVIL DROPBOX\PROJECTS\U21004 - NISSAN DEALERSHIP\CADD\CP\C3.00 - OVERALL UTILITY PLAN.DWGC3.00 - OVERALL UTILITY PLAN####C3.00
75OVERALL UTILITY PLAN15
NORTH0 80'160'
SCALE: 1" = 80'
40'
NOTES
1. EXISTING UNDERGROUND AND OVERHEAD PUBLIC AND PRIVATE
UTILITIES AS SHOWN ARE INDICATED ACCORDING TO THE BEST
INFORMATION AVAILABLE TO THE ENGINEER. THE ENGINEER DOES
NOT GUARANTEE THE ACCURACY OF SUCH INFORMATION. EXISTING
UTILITY MAINS AND SERVICES MAY NOT BE STRAIGHT LINES OR AS
INDICATED ON THESE DRAWINGS. THE CONTRACTOR SHALL BE
RESPONSIBLE TO CALL ALL UTILITY COMPANIES (PUBLIC AND
PRIVATE) PRIOR TO ANY CONSTRUCTION TO VERIFY EXACT UTILITY
LOCATIONS.
2. THE PROPOSED CONSTRUCTION WILL BE IN CLOSE PROXIMITY TO
SEVERAL UNDERGROUND UTILITIES. THE CONTRACTOR SHALL
COORDINATE WITH ALL UTILITY PROVIDERS PRIOR TO AND DURING
CONSTRUCTION TO MINIMIZE SERVICE INTERRUPTIONS TO
SURROUNDING BUILDINGS OR PROPERTIES.
3. THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS
5' OUTSIDE OF BUILDING UNLESS NOTED OTHERWISE. EXACT
LOCATIONS (HORIZONTAL AND VERTICAL) OF ALL UTILITY
CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE
COORDINATED WITH APPROVED ARCHITECTURAL DRAWINGS.
4. REFER TO APPROVED SITE ELECTRICAL PLANS FOR ALL CONDUITS
AND POWER LINE ROUTING FOR SITE LIGHTING.
5. WATER AND SEWER SERVICE PROVIDED BY THE FORT
COLLINS-LOVELAND WATER AND SOUTH FORT COLLINS SANITATION
DISTRICTS. ALL WATER AND SEWER CONSTRUCTION SHALL BE PER
EACH DISTRICT'S STANDARD CONSTRUCTION SPECIFICATIONS,
LATEST EDITION.
6. MINIMUM DEPTH OF COVER OVER WATER MAINS SHALL BE 5'.
MAXIMUM COVER SHALL BE 6'.
7. MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION
BETWEEN ALL SANITARY SEWER & WATER MAINS & SERVICES.
8. ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY
REPRESENTED AND ARE NOT TO SCALE.
9. SANITARY SEWER SERVICES SHALL BE SDR-35 PVC.
10. WATER MAINS AND FIRE SERVICES SHALL BE AWWA C-900 DR14 PVC.
WATER SERVICES UP TO 2" SHALL BE TYPE K COPPER.
11. CONTRACTOR SHALL COORDINATE ALL UTILITY DEMOLITION AND/OR
RELOCATION ITEMS WITH THE APPROPRIATE UTILITY PROVIDER
PRIOR TO BEGINNING ANY ONSITE DEMOLITION.
12. REFER TO SHEETS C3.01 AND C3.02 FOR DETAILED UTILITY PLANS.
13. ALL UTILITIES IN THE CDOT ROW SHALL HAVE A CDOT UTILITY PERMIT
ISSUED PRIOR TO ANY UTILITY CONSTRUCTION. A SEPARATE UTILITY
PERMIT IS REQURED FOR EACH UTILITY BEING INSTALLED OR
SERVICE CONNECTION IN CDOT ROW. CONTACT THE REGION UTILITY
PERMIT COORDINATOR AT 970-683-6288. FORM #1233 THE UTILITY
PERMIT APPLICATION IS AVAILABLE AT
http://www.coloradodot.info/business/permits.
14. THE CONTRACTOR SHALL CONTACT THE UTILITY NOTIFICATION
CENTER OF COLORADO (UNCC) AT 811 OR 1-800-922-1987, TO HAVE
LOCATIONS OF UNCC REGISTERED LINES MARKED BY MEMBER
COMPANIES. ALL OTHER UNDERGROUND FACILITIES SHALL BE
LOCATED BY CONTACTING THE RESPECTIVE OWNER.
15. EXISTING UTILITY LINES AS SHOWN ON THE PLAN SHEETS ARE
PLOTTED FROM THE BEST AVAILABLE INFORMATION. (SUBSURFACE
UTILITY ENGINEERING (SUE) STANDARD QUALITY LEVEL A OR B IS
RECOMMENDED).
16. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE
LOCATION AND DEPTH OF ALL EXISTING UTILITIES AS NECESSARY TO
INSURE THE UTILITIES WILL NOT BE IMPACTED BY CONSTRUCTION
ACTIVITIES.
17. THE CONTRACTOR SHALL COMPLY WITH ARTICLE 1.5 OF TITLE 9, CRS
("EXCAVATION REQUIREMENTS") WHEN EXCAVATING OR GRADING IS
PLANNED IN THE AREA OF UNDERGROUND UTILITY FACILITIES. THE
CONTRACTOR SHALL NOTIFY ALL AFFECTED UTILITIES AT LEAST TWO
(2) BUSINESS DAYS, NOT INCLUDING THE ACTUAL DAY OF NOTICE,
PRIOR TO COMMENCING SUCH OPERATIONS.
18. ALL UTILITIES SHALL BE INSTALLED OR RELOCATED PER THE CDOT
UTILITY ACCOMMODATION CODE.
LEGEND
CABLE TV LINE
ELECTRIC LINE
OVERHEAD ELECTRIC LINE
FIBER OPTIC LINE
GAS LINE
ABANDONED GAS LINE
G GAS METER
IRRIGATION LINE
SANITARY MANHOLE
SANITARY MAIN
SANITARY SERVICE
SANITARY SERVICE CLEANOUT
DOWNSPOUT
FLARED END SECTION
STORM INLET
STORM MANHOLE
STORM OUTLET STRUCTURE
STORM PIPE
RIP RAP
TELEPHONE LINE
OVERHEAD TELEPHONE LINE
UTILITY POLE AND GUY WIRES
FIRE DEPARTMENT CONNECTION
FIRE HYDRANT
FIRELINE
WATER FITTINGS
WATER MAIN
WATER SERVICE
WATER METER
DRY UTILITY CONDUIT
DS
THRUST BLOCK
GATE VALVE
FIBER, GAS, ELECTRIC, TELEPHONE PEDESTAL
COLLEGE AVE (HWY 287)FOSSI
L
C
R
E
E
K
T
R
AI
L
CONNECT TO EXISTING
14" AC WATER MAIN
EXISTING GAS MAIN
PROPOSED 8" WATER
SEE SHEET C3.20
STORM LINE A
SEE SHEET C3.30
PROPOSED
UNDERGROUND
DETENTION AREA
(SEE SHEET C3.50)
PROPOSED 8" WATER
SEE SHEET C3.21
NISSAN
DEALERSHIP
BUILDING
EXISTING 24" IRRIGATION
CONNECT TO EXISTING
24" IRRIGATION LATERAL
EXISTING 14"
AC WATER MAIN
BUENO
DRIVE
PROPOSED FIRE HYDRANT
PROPOSED
FIRE HYDRANT
STORM LINE A10
SEE SHEET C3.31
FOSSIL CREEK
FLOODPLAIN/FLOODWAY
EROSION BUFFER LIMITS
EXISTING WETLANDS
PROPERTY BOUNDARY
PROPERTY BOUNDARY VENUS AVENUETRACT C
TRACT D
LOT 1
BLOCK 1
EXISTING CULVERT TO REMAIN
PROPOSED TRANSFORMER
PROPOSED 6" FIRE SERVICE
PROPOSED STRUCTURAL
RETAINING WALLS
SEE SHEETS C4.20 & C4.21
FIRE DEPARTMENT CONNECTION
9' UTILITY EASEMENT
15' UTILITY EASEMENT
9' UTILITY
EASEMENT
SLOPE EASEMENT
SLOPE EASEMENT
PROPOSED
UNDERGROUND
WATER QUALITY AREA
(SEE SHEET C3.50)
PROPOSED SAND-OIL
INTERCEPTOR
PROPOSED 2" WATER SERVICE
PRIMARY ELECTRIC PER
CITY OF FORT COLLINS
20' DRAINAGE EASEMENT
DRAINAGE EASEMENT
20' DRAINAGE EASEMENT
20' UTILITY EASEMENT
PROPOSED TRAFFIC SIGNAL (TYP.)
(SEE SIGNAL PLANS)
PROPOSED FIRE HYDRANT
PUBLIC ROW OVERHEAD LIGHT
PER CITY OF FORT COLLINS (TYP.)
ONSITE OVERHEAD LIGHT
(SEE ELEC. PLANS, TYP.)
PUBLIC ROW OVERHEAD LIGHT
PER CITY OF FORT COLLINS (TYP.)
PUBLIC ROW OVERHEAD LIGHT
PER CITY OF FORT COLLINS (TYP.)
RELOCATED GAS LINE EXISTING XCEL
GAS TO BE MOVED WITH GRADING
(SEE NOTE 12 AND DRY UTILITY NOTES)
STORM LINE G
SEE SHEET C3.34
PROPOSED ROOF DRAIN
SEE SHEET C3.36
PROPOSED ROOF DRAIN
SEE SHEET C3.36
PROPOSED ROOF DRAIN
SEE SHEET C3.36
STORM LINE A3.1
SEE SHEET C3.30
STORM LINE A3
SEE SHEET C3.30
STORM LINE A
SEE SHEET C3.30
PROPOSED ROOF DRAIN
SEE SHEET C3.32
STORM LINE A13
SEE SHEET C3.32
STORM LINE A14
SEE SHEET C3.32
STORM LINE A7
SEE SHEET C3.31
SANITARY SERVICE
CONNECTION
SEE SHEET C3.10 PREPARED FOR:JOB NUMBER
SHEET NUMBER
SHEETSOF DATE SUBMITTED:VERTICAL:
HORIZONTAL:
SCALEFINAL REVIEWPLANSNOT FOR CONSTRUCTIONPROJ. MGR:DRAWING NAME:PATH:DESIGNER:DATE:TIME:The engineer preparing these plans will not be responsible for, or liable for, unauthorizedchanges to or uses of these plans. All changes to the plans must be in writing and mustbe approved by the preparer of these plans.NO.BYDATECAUTIONREVISIONS:CIVIL ENGINEERING & CONSULTING
UNITED CIVIL
Design Group
19 OLD TOWN SQUARE #238FORT COLLINS, CO 80524
(970) 530-4044
www.unitedcivil.com
TCC CORPORATIONFORT COLLINS NISSAN-KIA6/15/2022U21004
1" = 40'
1" = N/A
6/15/202210:47:51 AME:\UNITED CIVIL DROPBOX\PROJECTS\U21004 - NISSAN DEALERSHIP\CADD\CP\C3.0X - DETAILED UTILITY PLANS.DWGC3.0X - DETAILED UTILITY PLANS####C3.01
75DETAILED UTILITY PLAN - NORTH16
NORTH0 40'80'
SCALE: 1" = 40'
20'
LEGEND COLLEGE AVE (HWY 287)VENUS AVENUEMILKY WAY DRIVE
N
KEYMAP
1. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE FIELD
CONDITIONS ARE AS SHOWN IN THE DRAWINGS. IF THE
CONTRACTOR FINDS DISCREPANCIES THE CONTRACTOR SHALL
CONTACT THE ENGINEER.
2. EXISTING UNDERGROUND AND OVERHEAD PUBLIC AND PRIVATE
UTILITIES AS SHOWN ARE INDICATED ACCORDING TO THE BEST
INFORMATION AVAILABLE TO THE ENGINEER. THE ENGINEER DOES
NOT GUARANTEE THE ACCURACY OF SUCH INFORMATION. EXISTING
UTILITY MAINS AND SERVICES MAY NOT BE STRAIGHT LINES OR AS
INDICATED ON THESE DRAWINGS. THE CONTRACTOR SHALL BE
RESPONSIBLE TO CALL ALL UTILITY COMPANIES (PUBLIC AND
PRIVATE) PRIOR TO ANY CONSTRUCTION TO VERIFY EXACT UTILITY
LOCATIONS.
3. THE PROPOSED CONSTRUCTION WILL BE IN CLOSE PROXIMITY TO
SEVERAL UNDERGROUND UTILITIES. THE CONTRACTOR SHALL
COORDINATE WITH ALL UTILITY PROVIDERS PRIOR TO AND DURING
CONSTRUCTION TO MINIMIZE SERVICE INTERRUPTIONS TO
SURROUNDING BUILDINGS OR PROPERTIES.
4. THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY LATERALS
5' OUTSIDE OF BUILDING UNLESS NOTED OTHERWISE. EXACT
LOCATIONS (HORIZONTAL AND VERTICAL) OF ALL UTILITY
CONNECTIONS INTO THE PROPOSED BUILDING SHALL BE
COORDINATED WITH APPROVED ARCHITECTURAL DRAWINGS.
5. REFER TO APPROVED SITE ELECTRICAL PLANS FOR ALL CONDUITS
AND POWER LINE ROUTING FOR SITE LIGHTING.
6. WATER AND SEWER SERVICE PROVIDED BY THE FORT
COLLINS-LOVELAND WATER AND SOUTH FORT COLLINS SANITATION
DISTRICTS. ALL WATER AND SEWER CONSTRUCTION SHALL BE PER
EACH DISTRICT'S STANDARD CONSTRUCTION SPECIFICATIONS,
LATEST EDITION.
7. MINIMUM DEPTH OF COVER OVER WATER MAINS SHALL BE 5'.
MAXIMUM COVER SHALL BE 6'.
8. MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION
BETWEEN ALL SANITARY SEWER & WATER MAINS & SERVICES.
9. ALL WATER FITTINGS AND VALVES ARE ONLY GRAPHICALLY
REPRESENTED AND ARE NOT TO SCALE.
10. SANITARY SEWER SERVICES SHALL BE SDR-35 PVC.
11. WATER MAINS AND FIRE SERVICES SHALL BE AWWA C-900 DR14 PVC.
WATER SERVICES UP TO 2" SHALL BE TYPE K COPPER.
12. CONTRACTOR SHALL COORDINATE ALL UTILITY DEMOLITION AND/OR
RELOCATION ITEMS WITH THE APPROPRIATE UTILITY PROVIDER
PRIOR TO BEGINNING ANY ONSITE DEMOLITION.
CABLE TV LINE
ELECTRIC LINE
OVERHEAD ELECTRIC LINE
FIBER OPTIC LINE
GAS LINE
ABANDONED GAS LINE
G GAS METER
IRRIGATION LINE
SANITARY MANHOLE
SANITARY MAIN
SANITARY SERVICE
SANITARY SERVICE CLEANOUT
DOWNSPOUT
FLARED END SECTION
STORM INLET
STORM MANHOLE
STORM OUTLET STRUCTURE
STORM PIPE
RIP RAP
TELEPHONE LINE
OVERHEAD TELEPHONE LINE
UTILITY POLE AND GUY WIRES
FIRE DEPARTMENT CONNECTION
FIRE HYDRANT
FIRELINE
WATER FITTINGS
WATER MAIN
WATER SERVICE
WATER METER
DRY UTILITY CONDUIT
DS
THRUST BLOCK
GATE VALVE
FIBER, GAS, ELECTRIC, TELEPHONE PEDESTAL
NOTES
1. THE LOCATION OF PROPOSED DRY UTILITIES AS SHOWN ON THIS
DRAWING ARE SHOWN FOR HORIZONTAL ALIGNMENTS ONLY AND
ARE APPROXIMATE. FINAL DESIGNS OF DRY UTILITIES WILL BE
PERFORMED BY THE APPROPRIATE UTILITY COMPANY.
2. GAS SERVICE TO BE PROVIDED BY XCEL ENERGY. XCEL SHALL
INSTALL GAS MAINS, SERVICES AND METERS. THE COST OF ALL
SERVICE INSTALLATION SHALL BE THE RESPONSIBILITY OF THE
DEVELOPER. THE SERVICE LOCATIONS AS SHOWN ON THIS
DRAWING ARE APPROXIMATE ONLY. FINAL LOCATION TO BE
DETERMINED BY XCEL, BUT SHALL MAINTAIN SPECIFIED
CLEARANCES FROM OTHER UTILITIES.
3. ELECTRIC SERVICE TO BE PROVIDED BY CITY OF FORT COLLINS. THE
CITY SHALL INSTALL SERVICE AND THE TRANSFORMER. THE COST
OF ALL SERVICE INSTALLATION SHALL BE THE RESPONSIBILITY OF
THE DEVELOPER. THE SERVICE LOCATION AS SHOWN ON THIS
DRAWING IS APPROXIMATE ONLY. FINAL LOCATION TO BE
DETERMINED BY THE CITY, BUT SHALL MAINTAIN SPECIFIED
CLEARANCES FROM OTHER UTILITIES.
4. ALL CONDUIT PLACED BY THE CONTRACTOR FOR CABLE, PHONE AND
INTERNET SHALL BE EQUIPPED WITH PULL TAPE AND LOCATE WIRE
PER THE SPECIFICATIONS OF EACH UTILITY COMPANY.
DRY UTILITY NOTES
STA: 9+50.00
N: 1427816.98
E: 3117518.71
BEGIN ALIGNMENT
EX MH
STA 10+00.00
N: 1427866.87
E: 3117515.47155.3 LF 8" SANITARY15'
15'
MH A1
STA 11+55.34
N: 1428021.88
E: 3117505.39 254.7 LF 8" S
A
N
I
T
A
R
Y
MH A2
STA 14+10.05
N: 1428073.79
E: 3117754.76
343.4 LF 8" SANITARY
MH A4
STA 17+53.50
N: 1428070.21
E: 3118098.19
93°CORE DRILL AND CONNECT TO
EXISTING MH W/ KOR-N-SEAL
PRODUCT OR APPROVED EQUAL
EXISTING 8" SANITARY
EXISTING 8" SANITARY
98°4" PVC @ 2.0%4" PVC @ 2.0%
4" SANITARY CLEANOUT
4" PVC @ 2.0%
4" PVC @ 2.0%
4" PVC @ 2.0%
4" SANITARY CLEANOUT
4" PVC @ 2.0%
168°
STA: 18+00.00
N: 1428069.73
E: 3118144.69
END ALIGNMENT
15'
15'
15'COLLEGE AVE (HWY 287)VENUS AVENUENISSAN DEALERSHIP
BUILDING
KIA DEALERSHIP
BUILDING
LOT 2
BLOCK 1
LOT 1
BLOCK 1
UTILITY & DRAINAGE
EASEMENT (WIDTH VARIES)
60' UTILITY
& DRAINAGE
EASEMENT
EXISTING
BUILDING
TO REMAIN
18+00
9+5010+0011+0012+00
13+00
14+00 15+00 16+00 17+00
BLDG CONNECTION
INV.=5015.00
4'' TEE
INV.=5014.70
BLDG CONNECTION
INV.=5017.25
FG=5022.25
45° BEND W/ CO
INV.=5016.34
45° BEND
INV.=5016.12
FFE=5020.00
FFE=5022.25
SAND OIL INTERCEPTER
N:1428230.68 (CENTER)
E:3118087.37 (CENTER)
(SEE MECH. PLANS)
SAND OIL INTERCEPTER
N:1427981.37 (CENTER)
E:3118090.51 (CENTER)
(SEE MECH. PLANS)
SEE MECH. PLANS
FOR SERVICE LINES
TO INTERCEPTOR
SEE MECH. PLANS
FOR SERVICE LINES
TO INTERCEPTOR
4'' TEE
INV.=5017.02
SANITARY A PROFILE
STA: 9+50 - STA: 18+00
4995
5000
5005
5010
5015
5020
5025
5030
4995
5000
5005
5010
5015
5020
5025
5030
9+50 10+00 10+50 11+00 11+50 12+00 12+50 13+00 13+50 14+00 14+50 15+00 15+50 16+00 16+50 17+00 17+50 18+00EX MHSTA: 10+00.00RIM 5011.3±INV. IN 5004.20 (N)INV. IN 5003.20 (E)INV. OUT 5003.10 (SW)155.3 LF 8" PVC @ 0.50%MH A1STA: 11+55.34RIM 5011.9±INV. IN 5005.18 (E)INV. OUT 5004.98 (S)254.7 LF 8" PVC @ 0.50%MH A2STA: 14+10.05RIM 5015.6±INV. IN 5006.65 (E)INV. OUT 5006.45 (W)343.4 LF 8" PVC @ 1.00%MH A4 (OUTSIDE DROP MH)STA: 17+53.50RIM 5020.5±INV. IN 5011.49 (N)INV. IN 5015.17 (S)INV. OUT 5010.09 (W)STA: 16+52.88INV.= 5013.61PROP. 24" STORMSTA: 14+66.72INV.= 5010.32PROP. 18" STORMGROUNDWATER BARRIER
(SEE DETAILS)GROUNDWATER BARRIER
(SEE DETAILS)
CORE DRILL AND CONNECT TO
EXISTING MH W/ KOR-N-SEAL
PRODUCT OR APPROVED EQUAL
PROPOSED GRADE
@ PIPE CENTERLINE
EXISTING GROUND
STA: 14+43.84INV.= 5011.95PROP. UG ELECTRICSTA: 14+21.31INV.= 5009.19PROP. 8" WATERSTA: 13+87.05INV.= 5012.08PROP. UG ELECTRICGROUNDWATER BARRIER
(SEE DETAILS)
18"
MIN.
EXISTING 8" SANITARY PREPARED FOR:JOB NUMBER
SHEET NUMBER
SHEETSOF DATE SUBMITTED:VERTICAL:
HORIZONTAL:
SCALEFINAL REVIEWPLANSNOT FOR CONSTRUCTIONPROJ. MGR:DRAWING NAME:PATH:DESIGNER:DATE:TIME:The engineer preparing these plans will not be responsible for, or liable for, unauthorizedchanges to or uses of these plans. All changes to the plans must be in writing and mustbe approved by the preparer of these plans.NO.BYDATECAUTIONREVISIONS:CIVIL ENGINEERING & CONSULTING
UNITED CIVIL
Design Group
19 OLD TOWN SQUARE #238FORT COLLINS, CO 80524
(970) 530-4044
www.unitedcivil.com
TCC CORPORATIONFORT COLLINS NISSAN-KIA6/15/2022U21004
1. EXISTING UNDERGROUND AND OVERHEAD PUBLIC AND PRIVATE
UTILITIES AS SHOWN ARE INDICATED ACCORDING TO THE BEST
INFORMATION AVAILABLE TO THE ENGINEER. THE ENGINEER
DOES NOT GUARANTEE THE ACCURACY OF SUCH INFORMATION.
EXISTING UTILITY MAINS AND SERVICES MAY NOT BE STRAIGHT
LINES OR AS INDICATED ON THESE DRAWINGS. THE
CONTRACTOR SHALL BE RESPONSIBLE TO CALL ALL UTILITY
COMPANIES (PUBLIC AND PRIVATE) PRIOR TO ANY
CONSTRUCTION TO VERIFY EXACT UTILITY LOCATIONS.
2. THE PROPOSED CONSTRUCTION WILL BE IN CLOSE PROXIMITY
TO SEVERAL UNDERGROUND UTILITIES. THE CONTRACTOR
SHALL COORDINATE WITH ALL UTILITY PROVIDERS PRIOR TO
AND DURING CONSTRUCTION TO MINIMIZE SERVICE
INTERRUPTIONS TO SURROUNDING BUILDINGS OR PROPERTIES.
3. THE CONTRACTOR SHALL PROTECT ALL EXISTING FEATURES
THAT ARE NOT TO BE REMOVED ADJACENT TO THE
CONSTRUCTION AREA INCLUDING, BUT NOT LIMITED TO,
PAVEMENT, PRIVATE FENCES, ABOVE GROUND OR
UNDERGROUND UTILITIES, STRUCTURES, AND UNDERGROUND
FOUNDATIONS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
ANY DAMAGE THAT SHOULD OCCUR TO ANY ON-SITE, OFF-SITE,
PUBLIC OR PRIVATE FACILITY OR FEATURE AS A RESULT OF THE
CONSTRUCTION PROCESS FOR THIS PROJECT.
4. CONTRACTOR SHALL COORDINATE ALL CONSTRUCTION ITEMS
IMPACTING ADJACENT PROPERTIES WITH THE PROPERTY
OWNER'S PRIOR TO CONSTRUCTION. A RIGHT-OF-WAY WORK
PERMIT FROM THE CITY OF FORT COLLINS SHALL BE OBTAINED
FOR CONSTRUCTION WITHIN PUBLIC RIGHT-OF-WAY.
5. ALL WATER AND SEWER CONSTRUCTION SHALL BE PER THE CITY
OF FORT COLLINS STANDARD CONSTRUCTION SPECIFICATIONS,
LATEST EDITION.
6. MINIMUM HORIZONTAL EDGE TO EDGE SEPARATION BETWEEN
SANITARY & WATERLINES IS 10 FEET.
7. WATER MAINS CROSSING OVER A SANITARY OR STORM SEWER
SHALL MAINTAIN AN 18" VERTICAL EDGE TO EDGE CLEARANCE.
WATER MAINS CLOSER THAN 18" OR UNDER SEWERS SHALL BE
ENCASED.
8. MINIMUM DEPTH OF COVER FOR WATER MAINS IS 5.0 FEET,
MAXIMUM 6.0 FEET.
9. SANITARY SEWER MAIN AND SERVICES SHALL BE SDR-35 PVC.
10. ALL MANHOLES SHALL HAVE THE CONICAL (TOP) SECTION OF
THE MANHOLE ROTATED SO THAT THE RIM AND LID ARE
LOCATED AWAY FROM CURB AND GUTTER, TOWARD THE CROWN
OF THE ROAD.
11. REFER TO WATER AND STORM PLAN AND PROFILES PLANS FOR
CROSSING INFORMATION OF SANITARY SEWER SERVICES.
12. ALL CLEANOUTS IN PAVED AREAS SHALL BE TRAFFIC RATED.
NOTES
LEGEND
PROPOSED BUILDING
N
KEYMAP COLLEGE AVE (HWY 287)VENUS AVENUEMILKY WAY DRIVE
CABLE TV LINE
ELECTRIC LINE
OVERHEAD ELECTRIC LINE
FIBER OPTIC LINE
GAS LINE
IRRIGATION LINE
SANITARY MANHOLE
SANITARY MAIN
SANITARY SERVICE
SANITARY SERVICE CLEANOUT
DOWNSPOUT
FLARED END SECTION
STORM INLET
STORM MANHOLE
STORM OUTLET STRUCTURE
STORM PIPE
RIP RAP
FIRE DEPARTMENT CONNECTION
FIRE HYDRANT
FIRELINE
WATER FITTINGS
WATER MAIN
WATER SERVICE
WATER METER
DRY UTILITY CONDUIT
DS
THRUST BLOCK
GATE VALVE
FIBER, GAS, ELECTRIC, TELEPHONE PEDESTAL
0 50'100'
SCALE: 1" = 50'
25'NORTH1" = 50'
1" = 5'6/15/202210:48:14 AME:\UNITED CIVIL DROPBOX\PROJECTS\U21004 - NISSAN DEALERSHIP\CADD\CP\C3.1X - SANITARY PLAN & PROFILES.DWGC3.1X - SANITARY PLAN & PROFILES####C3.10
75SANITARY SEWER PLAN & PROFILE - LINE A18
9+50 10+00
11+00
12+00
13+00
14+00
15
+
0
0
1
6
+
0
0
1
7
+
0
0
1
8
+
0
0
1
9
+
0
0
STA: 9+50.00
N: 1427928.07
E: 3117799.81
BEGIN ALIGNMENT
STA: 10+00.00
CONNECT TO EXIST. 6" TEE
W/8" INCREASER
N=1427977.66
E=3117793.41
STA: 10+11.02
8" 45° BEND
N=1427988.59
E=3117792.00
STA: 10+23.47
8" 45° BEND
N=1427996.19
E=3117782.14
STA: 10+69.88
8" X 8" TEE
8" GATE VALVES (N&E)
N=1428041.63
E=3117772.68
11.0 LF 8" WATER
12.4 LF 8" WATER
46.4 LF
8" WATER
130.1 LF 8"
W
A
T
E
R
STA: 12+00.00
8" X 6" SWIVEL TEE
6" GATE VALVE (W)
N: 1428169.02
E: 3117746.17
STA. 12+00.00, (-34.42' L)
F.H. ASSEMBLY
N: 1428162.01
E: 3117712.48
77.8 LF 8" W
A
T
E
R
STA: 12+77.81
8" 22.5° BEND
N=1428245.20
E=3117730.32
106.0 LF 8"
W
A
T
E
R
STA: 14+00.78
8" X 6" SWIVEL TEE
6" GATE VALVE (E)
N: 1428366.02
E: 3117753.24
STA: 13+83.78
8" X 6" TEE
6" GATE VALVE (E)
N: 1428349.32
E: 3117750.07
5.0 LF 8" WATER
12.0 LF 8" WATER
25.2 LF 8" WATER
STA: 13+88.78
2" TAPPING SADDLE
N=1428354.23
E=3117751.01
STA: 14+25.96
8" 22.5° BEND
N=1428390.76
E=3117757.94
98
.
1
L
F
8
"
W
A
T
E
R
STA: 15+24.07
8" 11.25° BEND
N=1428472.81
E=3117811.72
MATCHLINESEE SHEET C3.21STA. 14+73.36, (140.87' R)
F.H. ASSEMBLY
N: 1428353.17
E: 3117901.74
3
8
4
.
7
L
F
8
"
W
A
T
E
R
NISSAN DEALERSHIP
BUILDING
FFE = 5020.00
LOT 1
RISING SON MANOR
SUBDIVISION
KIA DEALERSHIP
BUILDING
FFE = 5022.25
#5822
EXISTING
#5828
EXISTING
#5817
EXISTING
V
E
N
U
S
A
V
E
N
U
E
VENUS AVENUE
STA: 13+83.78 (64.50', R)
6" 11.25° BEND
N: 1428337.29
E: 3117813.45
STA: 14+00.78 (63.01', R)
6" 11.25° BEND
N: 1428354.27
E: 3117815.15
64.5 LF
6" FIRE SERVICE
63.0 LF
6" FIRE SERVICE
STA: 13+88.78 (32.25', R)
2" WATER METER
N: 1428348.22
E: 3117782.69
120.0 LF
6" FIRE SERVICE
86.6 LF
6" FIRE SERVICE
8" WATER - PRIVATE DRIVE
(SEE SHEET C3.22)
8" SANITARY
(SEE SHEET C3.10)MILKY WAY DRIVE#200
EXISTING
#206
EXISTING
#214
EXISTING
BUILDING FIRE SERVICE
CONNECTION
BUILDING WATER
SERVICE CONNECTION
WATER - VENUS PROFILE
STA: 9+50 - STA: 16+00
4985
4990
4995
5000
5005
5010
5015
5020
5025
5030
4985
4990
4995
5000
5005
5010
5015
5020
5025
5030
9+50 10+00 10+50 11+00 11+50 12+00 12+50 13+00 13+50 14+00 14+50 15+00 15+50 16+00STA = 10+00.00INV. = 5006.96CONNECT TO EXIST.6" TEE W/8" INCREASERSTA = 10+11.02INV. = 5007.208" 45° BENDSTA = 10+23.47INV. = 5007.478" 45° BENDSTA = 10+48.27INV. = 5008.008" 22.5° BEND (VERT.)STA = 10+52.63INV. = 5006.298" 22.5° BEND (VERT.)STA = 10+62.34INV. = 5006.538" 45° BEND (VERT.)STA = 10+64.29INV. = 5008.558" 45° BEND (VERT.)STA: 11+02.60INV.= 5006.76PROP. 8" SANITARYSTA: 10+57.88INV.= 5009.22PROP. 45" X 29" HERCP2.16%
-5.1
3
%
1.39%
-2.18%
18"
MIN.
18" MIN.STA = 10+69.88INV. = 5008.638" X 8" TEE8" GATE VALVES (N&E)STA = 12+00.00INV. = 5010.448" X 6" SWIVEL TEE6" GATE VALVE (W)STA = 12+77.81INV. = 5008.578" 22.5° BENDSTA: 13+45.16INV.= 5008.79PROP. 15" STORM18" MIN.STA = 13+83.78INV. = 5004.268" X 6" TEE6" GATE VALVE (E)STA = 14+00.78INV. = 5003.388" X 6" SWIVEL TEE6" GATE VALVE (E)STA = 13+88.76INV. = 5004.002" TAPPING SADDLESTA = 14+25.96INV. = 5002.098" 22.5° BENDSTA = 15+24.07INV. = 4997.068" 11.25° BEND8" C
9
0
0
D
R
1
8
P
V
C
W
A
T
E
R
L
I
N
E
EXISTING GROUND
PROPOSED GRADE
@ PIPE CENTERLINE
MATCHLINE - SEE SHEET C3.21JOINT RESTRAINT
(LR=20' MIN. PAST BEND)
JOINT RESTRAINT
(LR=80' MIN. PAST TEE)PREPARED FOR:JOB NUMBER
SHEET NUMBER
SHEETSOF DATE SUBMITTED:VERTICAL:
HORIZONTAL:
SCALEFINAL REVIEWPLANSNOT FOR CONSTRUCTIONPROJ. MGR:DRAWING NAME:PATH:DESIGNER:DATE:TIME:The engineer preparing these plans will not be responsible for, or liable for, unauthorizedchanges to or uses of these plans. All changes to the plans must be in writing and mustbe approved by the preparer of these plans.NO.BYDATECAUTIONREVISIONS:CIVIL ENGINEERING & CONSULTING
UNITED CIVIL
Design Group
19 OLD TOWN SQUARE #238FORT COLLINS, CO 80524
(970) 530-4044
www.unitedcivil.com
TCC CORPORATIONFORT COLLINS NISSAN-KIA6/15/2022U21004
1" = 50'
1" = 5'6/15/202210:48:32 AME:\UNITED CIVIL DROPBOX\PROJECTS\U21004 - NISSAN DEALERSHIP\CADD\CP\C3.2X - WATER PLAN & PROFILES.DWGC3.2X - WATER PLAN & PROFILES####C3.20
75WATER PLAN & PROFILE - VENUS AVENUESTA 9+50 - STA 16+0019
NOTES
LEGEND
SANITARY MANHOLE
SANITARY MAIN
SANITARY SERVICE
SANITARY SERVICE CLEANOUT
FLARED END SECTION
STORM INLET
STORM MANHOLE
STORM OUTLET STRUCTURE
STORM PIPE
FIRE DEPARTMENT CONNECTION
FIRE HYDRANT
FIRELINE
WATER FITTINGS
WATER MAIN
THRUST BLOCK
GATE VALVE
FDC
PROPOSED BUILDING
CURB & GUTTER
EXISTING PROPERTY BOUNDARY
PROPOSED PROPERTY LINE
RIGHT OF WAY
N
KEYMAP COLLEGE AVE (HWY 287)VENUS AVENUEMILKY WAY DRIVE
1. EXISTING UNDERGROUND AND OVERHEAD PUBLIC AND PRIVATE
UTILITIES AS SHOWN ARE INDICATED ACCORDING TO THE BEST
INFORMATION AVAILABLE TO THE ENGINEER. THE ENGINEER DOES
NOT GUARANTEE THE ACCURACY OF SUCH INFORMATION. EXISTING
UTILITY MAINS AND SERVICES MAY NOT BE STRAIGHT LINES OR AS
INDICATED ON THESE DRAWINGS. THE CONTRACTOR SHALL BE
RESPONSIBLE TO CALL ALL UTILITY COMPANIES (PUBLIC AND
PRIVATE) PRIOR TO ANY CONSTRUCTION TO VERIFY EXACT UTILITY
LOCATIONS.
2. THE CONTRACTOR SHALL PROTECT ALL EXISTING FEATURES THAT
ARE NOT TO BE REMOVED ADJACENT TO THE CONSTRUCTION AREA
INCLUDING, BUT NOT LIMITED TO, PAVEMENT, PRIVATE FENCES,
ABOVE GROUND OR UNDERGROUND UTILITIES, STRUCTURES, AND
UNDERGROUND FOUNDATIONS. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY DAMAGE THAT SHOULD OCCUR TO ANY
ON-SITE, OFF-SITE, PUBLIC OR PRIVATE FACILITY OR FEATURE AS A
RESULT OF THE CONSTRUCTION PROCESS FOR THIS PROJECT.
3. THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY SERVICES
5' OUTSIDE OF BUILDING UNLESS NOTED OTHERWISE. EXACT
LOCATIONS (HORIZONTAL AND VERTICAL) OF ALL UTILITY
CONNECTIONS INTO THE PROPOSED BUILDINGS SHALL BE
COORDINATED WITH APPROVED ARCHITECTURAL DRAWINGS.
4. ALL WATERLINE CONSTRUCTION SHALL BE PER FORT COLLINS
LOVELAND WATER DISTRICT STANDARD CONSTRUCTION
SPECIFICATIONS, LATEST EDITION.
5. MINIMUM DEPTH OF COVER OVER WATER MAINS SHALL BE 5'.
MAXIMUM COVER SHALL BE 6' UNLESS OTHERWISE NOTED ON THESE
DRAWINGS.
6. WATER MAINS AND FIRE SERVICES SHALL BE AWWA C-900 DR14 PVC.
WATER SERVICES UP TO 2" SHALL BE TYPE K COPPER.
7. MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION
BETWEEN ALL SANITARY SEWER & WATER MAINS & SERVICES.
SHOULD THE WATER LINE CROSS UNDER EITHER STORM DRAIN OR
SANITARY SEWER, THE STORM OR SANITARY SHALL BE CONCRETE
ENCASED FOR 10' ON EITHER SIDE OF THE CROSSING.
8. BENDS AND FITTINGS ON ALL NEW WATER MAIN (EXCEPT WHERE
CONNECTING TO EXISTING MAINS) SHALL USE MECHANICALLY
RESTRAINED JOINTS PER FORT COLLINS-LOVELAND WATER DISTRICT
STANDARDS AND LENGTHS PER THE JOINT RESTRAINT LENGTHS
TABLE AND VERTICAL PROFILES PROVIDED ON THIS DRAWING. ALL
FIRE HYDRANT LEADS AND FIRE SERVICES TO BUILDINGS SHALL BE
INSTALLED WITH JOINT RESTRAINTS PER THE SAME REQUIREMENTS.
WET TAP LOCATIONS SHALL BE INSTALLED WITH THRUST BLOCKS.
9. WHERE RESTRAINED JOINTS FOR HORIZONTAL AND VERTICAL
FITTINGS OVERLAP RESTRAINTS SHALL BE EXTENDED USING THE
LONGEST LENGTH.
10. BACKFLOW PREVENTION FOR WATER SERVICES SHALL BE PROVIDED
WITHIN EACH BUILDING AND NO CONNECTIONS TO THE WATER
SERVICES (INCLUDING IRRIGATION TAPS) SHALL BE MADE PRIOR TO
THE BACKFLOW PREVENTION DEVICE.
0 50'100'
SCALE: 1" = 50'
25'
NORTH
HORIZONTAL JOINT RESTRAINT LENGTHS
FITTING TYPE 6" PIPE 8" PIPE
11.25 DEGREE 2'3'
22.5 DEGREE 4'5'
45 DEGREE 8'10'
90 DEGREE 18' 24'
VALVES, FIRE HYDRANTS, DEAD-ENDS, TEES 60' 80'
(1) JOINT RESTRAINT SHALL BE PLACED ON EACH BRANCH OF EACH FITTING AT THE
LENGTHS SHOWN.
(2) JOINT RESTRAINT LENGTHS ARE CALCULATED USING FCLWD SPECIFICATIONS.
(3) LENGTHS SHOWN IN TABLE ARE FOR HORIZONTAL FITTINGS. REFER TO THE PROFILES
FOR JOINT RESTRAINT REQUIREMENTS ON VERTICAL FITTINGS.
(4) REFER TO NOTES 8 AND 9.
LOT 1LOT 22
2
+
5
0
11+0012+0013+0014+0015+00 16+00 17+00 18+00 19+00
20+0
0
2
1
+
0
0
2
2
+
0
0MATCHLINESEE SHEET C3.20 384.7 LF 8" WATER
VENUS AVENUE
10.6 LF 8" WATER
167.
8
L
F
8
"
W
A
T
E
R
1
0
8
.
5
L
F
8
"
W
A
T
E
R
11.4 LF 8" WATER
STA: 19+19.40
8" 22.5° BEND
N=1428749.95
E=3118093.63
STA: 19+08.76
8" X 6" SWIVEL TEE
6" GATE VALVE (SE)
N: 1428742.50
E: 3118086.04
STA. 19+08.76, (23.72' R)
F.H. ASSEMBLY
N: 1428725.58
E: 3118102.67
STA. 20+98.58, (-33.31' L)
F.H. ASSEMBLY
N: 1428846.00
E: 3118261.02
STA: 20+98.58
8" X 6" SWIVEL TEE
6" GATE VALVE (N)
N: 1428812.70
E: 3118260.57
STA: 20+87.22
8" 22.5° BEND
N=1428812.85
E=3118249.21
STA: 22+50.00
N: 1428810.69
E: 3118411.98
END ALIGNMENT
STA: 22+07.05
14" X 8" WET TAP W/ T.B.
8" GATE VALVE (W)
N=1428811.26
E=3118369.04 COLLEGE AVENUE (HWY 287)B
U
E
N
O
D
R
I
V
E
NISSAN DEALERSHIP
BUILDING
FFE = 5020.00
WATER - VENUS PROFILE
STA: 16+00 - STA: 22+50
4975
4980
4985
4990
4995
5000
5005
5010
5015
5020
4975
4980
4985
4990
4995
5000
5005
5010
5015
5020
16+00 16+50 17+00 17+50 18+00 18+50 19+00 19+50 20+00 20+50 21+00 21+50 22+00 22+50MATCHLINE - SEE SHEET C3.208" C900 DR18
P
V
C
W
A
T
E
R
L
I
N
E
EXISTING GROUND
PROPOSED GRADE
@ PIPE CENTERLINE
STA = 17+01.46INV. = 4990.548" 22.5° BEND (VERT.)STA = 17+09.59INV. = 4986.998" 22.5° BEND (VERT.)STA = 17+46.59INV. = 4986.768" 22.5° BEND (VERT.)STA = 17+55.68INV. = 4990.438" 22.5° BEND (VERT.)-2.50%
1.93%
-0.24%
18" MIN.STA: 17+16.29INV.= 4989.46PROP. 18" STORMSTA: 17+45.75INV.= 4991.59PROP. 15" STORMSTA = 19+08.76INV. = 4993.388" X 6" SWIVEL TEE6" GATE VALVE (SE)STA = 19+19.40INV. = 4993.598" 22.5° BENDSTA = 20+98.58INV. = 4995.638" X 6" SWIVEL TEE6" GATE VALVE (N)STA = 20+87.22INV. = 4995.668" 22.5° BENDSTA = 22+07.05INV. = 4995.3714" X 8" WET TAP W/ T.B.8" GATE VALVE (W)JOINT RESTRAINT
(LR=20' MIN. PAST BEND)
JOINT RESTRAINT
(LR=20' MIN. PAST BEND)PREPARED FOR:JOB NUMBER
SHEET NUMBER
SHEETSOF DATE SUBMITTED:VERTICAL:
HORIZONTAL:
SCALEFINAL REVIEWPLANSNOT FOR CONSTRUCTIONPROJ. MGR:DRAWING NAME:PATH:DESIGNER:DATE:TIME:The engineer preparing these plans will not be responsible for, or liable for, unauthorizedchanges to or uses of these plans. All changes to the plans must be in writing and mustbe approved by the preparer of these plans.NO.BYDATECAUTIONREVISIONS:CIVIL ENGINEERING & CONSULTING
UNITED CIVIL
Design Group
19 OLD TOWN SQUARE #238FORT COLLINS, CO 80524
(970) 530-4044
www.unitedcivil.com
TCC CORPORATIONFORT COLLINS NISSAN-KIA6/15/2022U21004
1" = 50'
1" = 5'6/15/202210:48:37 AME:\UNITED CIVIL DROPBOX\PROJECTS\U21004 - NISSAN DEALERSHIP\CADD\CP\C3.2X - WATER PLAN & PROFILES.DWGC3.2X - WATER PLAN & PROFILES####C3.21
75WATER PLAN & PROFILE - VENUS AVENUESTA 16+00 - STA 22+5020
NOTES
LEGEND
SANITARY MANHOLE
SANITARY MAIN
SANITARY SERVICE
SANITARY SERVICE CLEANOUT
FLARED END SECTION
STORM INLET
STORM MANHOLE
STORM OUTLET STRUCTURE
STORM PIPE
FIRE DEPARTMENT CONNECTION
FIRE HYDRANT
FIRELINE
WATER FITTINGS
WATER MAIN
THRUST BLOCK
GATE VALVE
FDC
PROPOSED BUILDING
CURB & GUTTER
EXISTING PROPERTY BOUNDARY
PROPOSED PROPERTY LINE
RIGHT OF WAY
N
KEYMAP COLLEGE AVE (HWY 287)VENUS AVENUEMILKY WAY DRIVE
1. EXISTING UNDERGROUND AND OVERHEAD PUBLIC AND PRIVATE
UTILITIES AS SHOWN ARE INDICATED ACCORDING TO THE BEST
INFORMATION AVAILABLE TO THE ENGINEER. THE ENGINEER DOES
NOT GUARANTEE THE ACCURACY OF SUCH INFORMATION. EXISTING
UTILITY MAINS AND SERVICES MAY NOT BE STRAIGHT LINES OR AS
INDICATED ON THESE DRAWINGS. THE CONTRACTOR SHALL BE
RESPONSIBLE TO CALL ALL UTILITY COMPANIES (PUBLIC AND
PRIVATE) PRIOR TO ANY CONSTRUCTION TO VERIFY EXACT UTILITY
LOCATIONS.
2. THE CONTRACTOR SHALL PROTECT ALL EXISTING FEATURES THAT
ARE NOT TO BE REMOVED ADJACENT TO THE CONSTRUCTION AREA
INCLUDING, BUT NOT LIMITED TO, PAVEMENT, PRIVATE FENCES,
ABOVE GROUND OR UNDERGROUND UTILITIES, STRUCTURES, AND
UNDERGROUND FOUNDATIONS. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY DAMAGE THAT SHOULD OCCUR TO ANY
ON-SITE, OFF-SITE, PUBLIC OR PRIVATE FACILITY OR FEATURE AS A
RESULT OF THE CONSTRUCTION PROCESS FOR THIS PROJECT.
3. THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY SERVICES
5' OUTSIDE OF BUILDING UNLESS NOTED OTHERWISE. EXACT
LOCATIONS (HORIZONTAL AND VERTICAL) OF ALL UTILITY
CONNECTIONS INTO THE PROPOSED BUILDINGS SHALL BE
COORDINATED WITH APPROVED ARCHITECTURAL DRAWINGS.
4. ALL WATERLINE CONSTRUCTION SHALL BE PER FORT COLLINS
LOVELAND WATER DISTRICT STANDARD CONSTRUCTION
SPECIFICATIONS, LATEST EDITION.
5. MINIMUM DEPTH OF COVER OVER WATER MAINS SHALL BE 5'.
MAXIMUM COVER SHALL BE 6' UNLESS OTHERWISE NOTED ON THESE
DRAWINGS.
6. WATER MAINS AND FIRE SERVICES SHALL BE AWWA C-900 DR14 PVC.
WATER SERVICES UP TO 2" SHALL BE TYPE K COPPER.
7. MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION
BETWEEN ALL SANITARY SEWER & WATER MAINS & SERVICES.
SHOULD THE WATER LINE CROSS UNDER EITHER STORM DRAIN OR
SANITARY SEWER, THE STORM OR SANITARY SHALL BE CONCRETE
ENCASED FOR 10' ON EITHER SIDE OF THE CROSSING.
8. BENDS AND FITTINGS ON ALL NEW WATER MAIN (EXCEPT WHERE
CONNECTING TO EXISTING MAINS) SHALL USE MECHANICALLY
RESTRAINED JOINTS PER FORT COLLINS-LOVELAND WATER DISTRICT
STANDARDS AND LENGTHS PER THE JOINT RESTRAINT LENGTHS
TABLE AND VERTICAL PROFILES PROVIDED ON THIS DRAWING. ALL
FIRE HYDRANT LEADS AND FIRE SERVICES TO BUILDINGS SHALL BE
INSTALLED WITH JOINT RESTRAINTS PER THE SAME REQUIREMENTS.
WET TAP LOCATIONS SHALL BE INSTALLED WITH THRUST BLOCKS.
9. WHERE RESTRAINED JOINTS FOR HORIZONTAL AND VERTICAL
FITTINGS OVERLAP RESTRAINTS SHALL BE EXTENDED USING THE
LONGEST LENGTH.
10. BACKFLOW PREVENTION FOR WATER SERVICES SHALL BE PROVIDED
WITHIN EACH BUILDING AND NO CONNECTIONS TO THE WATER
SERVICES (INCLUDING IRRIGATION TAPS) SHALL BE MADE PRIOR TO
THE BACKFLOW PREVENTION DEVICE.
0 50'100'
SCALE: 1" = 50'
25'NORTHHORIZONTAL JOINT RESTRAINT LENGTHS
FITTING TYPE 6" PIPE 8" PIPE
11.25 DEGREE 2'3'
22.5 DEGREE 4'5'
45 DEGREE 8'10'
90 DEGREE 18' 24'
VALVES, FIRE HYDRANTS, DEAD-ENDS, TEES 60' 80'
(1) JOINT RESTRAINT SHALL BE PLACED ON EACH BRANCH OF EACH FITTING AT THE
LENGTHS SHOWN.
(2) JOINT RESTRAINT LENGTHS ARE CALCULATED USING FCLWD SPECIFICATIONS.
(3) LENGTHS SHOWN IN TABLE ARE FOR HORIZONTAL FITTINGS. REFER TO THE PROFILES
FOR JOINT RESTRAINT REQUIREMENTS ON VERTICAL FITTINGS.
(4) REFER TO NOTES 8 AND 9.
LOT 24
LOT 25
LOT 26
LOT 27
KIA DEALERSHIP
BUILDING
FFE = 5022.25
NISSAN DEALERSHIP
BUILDING
FFE = 5020.00
LOT 1
RISING SON MANOR
SUBDIVISION
STA: 29+50.00
N: 1428032.52
E: 3117723.52
BEGIN ALIGNMENT
STA: 30+00.00
8" X 8" TEE
8" GATE VALVES (N&E)
N: 1428041.63
E: 3117772.68
STA: 31+08.98
8" 11.25° BEND
N=1428061.48
E=3117879.84
109.0 LF 8" W
A
T
E
R
213.2 LF 8" WATER
24.6 LF 8" WATER
10.0 LF 8" WATER
63.7 LF 8" WATER
28.7 LF 8" WATER
23.1 LF 8" WATER
STA: 33+22.23
8" 11.25° BEND
N=1428059.27
E=3118093.08
51.8 LF 8" WATER
STA: 33+52.11
2" TAPPING SADDLE
N=1428053.42
E=3118122.38
STA: 33+74.03
8" X 6" TEE
6" GATE VALVE (S)
N=1428049.13
E=3118143.88
STA: 33+98.68
8" X 6" SWIVEL TEE
6" GATE VALVE (S)
N=1428044.31
E=3118168.05
STA: 34+08.68
8" 11.25° BEND
N=1428042.35
E=3118177.86
STA: 34+72.41
8" 45° BEND
N=1428042.31
E=3118241.59
STA: 35+01.15
8" 45° BEND
N=1428021.98
E=3118261.90
STA: 35+50.00
N: 1428021.98
E: 3118310.75
END ALIGNMENT
STA: 35+24.27
CONNECT TO EXISTING 6" STUB
WITH 8"x6" REDUCER
N=1428021.96
E=3118285.01
STA. 34+04.22, (40.14' R)
F.H. ASSEMBLY
N: 1428003.86
E: 3118165.63
STA: 33+56.58 (33.22', R)
2" WATER METER
N: 1428019.97
E: 3118120.26
BUILDING WATER SERVICE
CONNECTION
BUILDING FIRE SERVICE
CONNECTION 83 LF 6" FIRE SERVICE
86 LF 2" WATER SERVICE COLLEGE AVENUE (HWY 287)SMOKEY ST.VENUS DRIVE35+50
29+50
30+00
31+00 32+00 33+00
34+00
3
5
+
0
0
WATER - PRIVATE DRIVE PROFILE
STA: 29+50 - STA: 35+50
4990
4995
5000
5005
5010
5015
5020
5025
5030
5035
4990
4995
5000
5005
5010
5015
5020
5025
5030
5035
29+50 30+00 30+50 31+00 31+50 32+00 32+50 33+00 33+50 34+00 34+50 35+00 35+50
8" C900 DR18 PVC WATERLINE
EXISTING GROUND
PROPOSED GRADE
@ PIPE CENTERLINESTA = 30+00.00INV. = 5008.638" X 8" TEE8" GATE VALVES (N&E)STA = 30+34.64INV. = 5008.628" 22.5° BEND (VERT.)STA = 30+52.63INV. = 5008.898" 22.5° BEND (VERT.)STA = 30+49.64INV. = 5007.918" 22.5° BEND (VERT.)STA = 30+37.01INV. = 5007.878" 22.5° BEND (VERT.)STA: 30+43.43INV.= 5010.26PROP. 18" STORM18" MIN.STA = 32+17.09INV. = 5012.908" 22.5° BEND (VERT.)STA = 32+21.13INV. = 5011.308" 22.5° BEND (VERT.)STA = 32+33.40INV. = 5011.478" 22.5° BEND (VERT.)STA = 32+37.64INV. = 5013.278" 22.5° BEND (VERT.)18" MIN.STA: 32+26.79INV.= 5013.74PROP. 24" STORMSTA = 31+08.98INV. = 5010.268" 11.25° BENDSTA = 33+22.23INV. = 5013.178" 11.25° BENDSTA = 33+52.11INV. = 5013.132" TAPPING SADDLE18" MIN.STA: 33+27.28INV.= 5015.41PROP. 4" SANITARYSTA = 33+74.03INV. = 5013.118" X 6" TEE6" GATE VALVE (S)STA = 33+98.68INV. = 5013.088" X 6" SWIVEL TEE6" GATE VALVE (S)STA = 34+26.95INV. = 5013.058" 22.5° BEND (VERT.)STA = 34+32.45INV. = 5010.818" 22.5° BEND (VERT.)STA = 34+61.13INV. = 5010.978" 22.5° BEND (VERT.)STA = 34+66.49INV. = 5013.268" 22.5° BEND (VERT.)18" MIN.STA: 34+38.65INV.= 5013.19PROP. 24" STORMSTA: 34+57.34INV.= 5014.31PROP. 24" IRRG. BYPASSSTA = 34+72.41INV. = 5013.348" 45° BENDSTA = 34+08.68INV. = 5013.078" 11.25° BEND1.43%
-0.02%
2.45%
-0.11%STA = 35+01.15INV. = 5013.758" 45° BENDSTA = 35+24.27INV. = 5014.08CONNECT TO EXIST. 6" STUBWITH 8"x6" REDUCERSTA: 35+06.06INV.= 5016.3±RELOCATED GASSTA: 35+15.45INV.= 5017.08PROP. ELECTRICJOINT RESTRAINT
(EXTEND TO TEE)
JOINT RESTRAINT
(LR=20' MIN. PAST BEND)
JOINT RESTRAINT
(LR=20' MIN. PAST BEND)
JOINT RESTRAINT
(LR=20' MIN. PAST BEND)
JOINT RESTRAINT
(EXTEND TO REDUCER)PREPARED FOR:JOB NUMBER
SHEET NUMBER
SHEETSOF DATE SUBMITTED:VERTICAL:
HORIZONTAL:
SCALEFINAL REVIEWPLANSNOT FOR CONSTRUCTIONPROJ. MGR:DRAWING NAME:PATH:DESIGNER:DATE:TIME:The engineer preparing these plans will not be responsible for, or liable for, unauthorizedchanges to or uses of these plans. All changes to the plans must be in writing and mustbe approved by the preparer of these plans.NO.BYDATECAUTIONREVISIONS:CIVIL ENGINEERING & CONSULTING
UNITED CIVIL
Design Group
19 OLD TOWN SQUARE #238FORT COLLINS, CO 80524
(970) 530-4044
www.unitedcivil.com
TCC CORPORATIONFORT COLLINS NISSAN-KIA6/15/2022U21004
1" = 50'
1" = 5'6/15/202210:48:42 AME:\UNITED CIVIL DROPBOX\PROJECTS\U21004 - NISSAN DEALERSHIP\CADD\CP\C3.2X - WATER PLAN & PROFILES.DWGC3.2X - WATER PLAN & PROFILES####C3.22
75WATER PLAN & PROFILE - PRIVATE DRIVESTA 29+50 - STA 35+5021
NOTES
LEGEND
SANITARY MANHOLE
SANITARY MAIN
SANITARY SERVICE
SANITARY SERVICE CLEANOUT
FLARED END SECTION
STORM INLET
STORM MANHOLE
STORM OUTLET STRUCTURE
STORM PIPE
FIRE DEPARTMENT CONNECTION
FIRE HYDRANT
FIRELINE
WATER FITTINGS
WATER MAIN
THRUST BLOCK
GATE VALVE
FDC
PROPOSED BUILDING
CURB & GUTTER
EXISTING PROPERTY BOUNDARY
PROPOSED PROPERTY LINE
RIGHT OF WAY
N
KEYMAP COLLEGE AVE (HWY 287)VENUS AVENUEMILKY WAY DRIVE
1. EXISTING UNDERGROUND AND OVERHEAD PUBLIC AND PRIVATE
UTILITIES AS SHOWN ARE INDICATED ACCORDING TO THE BEST
INFORMATION AVAILABLE TO THE ENGINEER. THE ENGINEER DOES
NOT GUARANTEE THE ACCURACY OF SUCH INFORMATION. EXISTING
UTILITY MAINS AND SERVICES MAY NOT BE STRAIGHT LINES OR AS
INDICATED ON THESE DRAWINGS. THE CONTRACTOR SHALL BE
RESPONSIBLE TO CALL ALL UTILITY COMPANIES (PUBLIC AND
PRIVATE) PRIOR TO ANY CONSTRUCTION TO VERIFY EXACT UTILITY
LOCATIONS.
2. THE CONTRACTOR SHALL PROTECT ALL EXISTING FEATURES THAT
ARE NOT TO BE REMOVED ADJACENT TO THE CONSTRUCTION AREA
INCLUDING, BUT NOT LIMITED TO, PAVEMENT, PRIVATE FENCES,
ABOVE GROUND OR UNDERGROUND UTILITIES, STRUCTURES, AND
UNDERGROUND FOUNDATIONS. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY DAMAGE THAT SHOULD OCCUR TO ANY
ON-SITE, OFF-SITE, PUBLIC OR PRIVATE FACILITY OR FEATURE AS A
RESULT OF THE CONSTRUCTION PROCESS FOR THIS PROJECT.
3. THE PLUMBING CONTRACTOR SHALL TERMINATE UTILITY SERVICES
5' OUTSIDE OF BUILDING UNLESS NOTED OTHERWISE. EXACT
LOCATIONS (HORIZONTAL AND VERTICAL) OF ALL UTILITY
CONNECTIONS INTO THE PROPOSED BUILDINGS SHALL BE
COORDINATED WITH APPROVED ARCHITECTURAL DRAWINGS.
4. ALL WATERLINE CONSTRUCTION SHALL BE PER FORT COLLINS
LOVELAND WATER DISTRICT STANDARD CONSTRUCTION
SPECIFICATIONS, LATEST EDITION.
5. MINIMUM DEPTH OF COVER OVER WATER MAINS SHALL BE 5'.
MAXIMUM COVER SHALL BE 6' UNLESS OTHERWISE NOTED ON THESE
DRAWINGS.
6. WATER MAINS AND FIRE SERVICES SHALL BE AWWA C-900 DR14 PVC.
WATER SERVICES UP TO 2" SHALL BE TYPE K COPPER.
7. MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION
BETWEEN ALL SANITARY SEWER & WATER MAINS & SERVICES.
SHOULD THE WATER LINE CROSS UNDER EITHER STORM DRAIN OR
SANITARY SEWER, THE STORM OR SANITARY SHALL BE CONCRETE
ENCASED FOR 10' ON EITHER SIDE OF THE CROSSING.
8. BENDS AND FITTINGS ON ALL NEW WATER MAIN (EXCEPT WHERE
CONNECTING TO EXISTING MAINS) SHALL USE MECHANICALLY
RESTRAINED JOINTS PER FORT COLLINS-LOVELAND WATER DISTRICT
STANDARDS AND LENGTHS PER THE JOINT RESTRAINT LENGTHS
TABLE AND VERTICAL PROFILES PROVIDED ON THIS DRAWING. ALL
FIRE HYDRANT LEADS AND FIRE SERVICES TO BUILDINGS SHALL BE
INSTALLED WITH JOINT RESTRAINTS PER THE SAME REQUIREMENTS.
WET TAP LOCATIONS SHALL BE INSTALLED WITH THRUST BLOCKS.
9. WHERE RESTRAINED JOINTS FOR HORIZONTAL AND VERTICAL
FITTINGS OVERLAP RESTRAINTS SHALL BE EXTENDED USING THE
LONGEST LENGTH.
10. BACKFLOW PREVENTION FOR WATER SERVICES SHALL BE PROVIDED
WITHIN EACH BUILDING AND NO CONNECTIONS TO THE WATER
SERVICES (INCLUDING IRRIGATION TAPS) SHALL BE MADE PRIOR TO
THE BACKFLOW PREVENTION DEVICE.
0 50'100'
SCALE: 1" = 50'
25'NORTHHORIZONTAL JOINT RESTRAINT LENGTHS
FITTING TYPE 6" PIPE 8" PIPE
11.25 DEGREE 2'3'
22.5 DEGREE 4'5'
45 DEGREE 8'10'
90 DEGREE 18' 24'
VALVES, FIRE HYDRANTS, DEAD-ENDS, TEES 60' 80'
(1) JOINT RESTRAINT SHALL BE PLACED ON EACH BRANCH OF EACH FITTING AT THE
LENGTHS SHOWN.
(2) JOINT RESTRAINT LENGTHS ARE CALCULATED USING FCLWD SPECIFICATIONS.
(3) LENGTHS SHOWN IN TABLE ARE FOR HORIZONTAL FITTINGS. REFER TO THE PROFILES
FOR JOINT RESTRAINT REQUIREMENTS ON VERTICAL FITTINGS.
(4) REFER TO NOTES 8 AND 9.