Page 1 of 1
January 26, 2022
Marcus Glasgow
Fire Safety Inspector – plan review
102 Remington St.
Fort Collins, CO 80524
Dear Marcus,
The Fort Collins Bucking Horse Park project is seeking approval of alternative method to comply
with the required access of 150 feet from all exterior portions of the restroom. The design is
proposing a fire access lane that extends 150 feet into the property. See the attached site plan.
This access would consist of two 6’ wide concrete paths designed to support the necessary weight,
with a 4’ path of grass-crete or cobble mulch between. Giving the fire access lane a total width of
16’. The path will terminate at large boulders as to identify where the lane ends.
From the fire access lane, the furthest portion of the building is 150’. The proposed construction
type is IV with an occupancy count of 6 people. There is proposed heavy timber wood on the
exterior of the building. These external heavy timber wood beams and columns are connected to
the one side of the building and projecting away from the building to create an exterior open-air
space. These heavy timbers would be no less than 6” wide and 8” deep per (Table 2304.11). All
other materials to be non-combustible. These columns are not structural to the building’s walls
or roof. The walls would be made from a non-combustible steel stud assembly. The roof uses a
metal decking and a non-combustible assembly for its support.
Building Construction Type: IV
Building Occupancy: Business (100 SF gross)
Gross Square footage: 556 SF
Occupancy Count: 6
Note: There are no immediate adjacent structures to this restroom.
Please let us know if the proposed alternative method to comply are acceptable. We are available
for further discussion as needed.
Thank you,
Casey Roberts, AIA