HomeMy WebLinkAboutENCLAVE AT REDWOOD - PDP210004 - SUBMITTAL DOCUMENTS - ROUND 4 - SUPPORTING DOCUMENTATION (3) BELFAY ENGINEERING Mechanical & Electrical Consulting Engineers 2811 West 9th Ave. TEL: (303) 892-5980 Denver, CO 80204 FAX: (303) 892-5979 email: belfay@belfay.com 12/16/2021 Matt Simpson Water/Wastewater Engineering 222 Laporte Ave Fort Collins, CO 80524 Project: Enclave at Redwood Subject: Utility Sizing For the Enclave at Redwood project, we will need to use the AWWA criteria to size the tap based on Fort Collins Water District’s standards. Based on this calculation and the preliminary building layouts, we will need a 4” sanitary sewer connection for each building type. The leasing center will need a 6” sewer connection for pool backwash. Please see the table below for domestic water tap/meter size as well as sanitary size for each building type. These tap sizes do not include any fire protection load. Building type Domestic water tap/ meter size Sanitary connection 4-plex 1” 4” 6-plex 1-1/2” 4” 8-plex 1-1/2” 4” Leasing center and maintenance 1” 6” Total if 1 tap for the whole complex 2” -- Respectfully Submitted, David Bellefeuille, PE President 22795 IG E E F VCAF E SDOPR NSIOA LLROOERODABT.DIELLE LDLENN GIERES ERE T I U 12/16/21 enclave at redwood all buildings TOTAL NO. OF FIXTURES AWWA FIXTURE VALUE TOTAL WC (tank)96 4 384 WC (flush valve)0 35 0 Urinal (wall or stall) 0 16 0 Urinal (flush valve) 1 35 35 Bidet 0 2 0 Shower 66 2.5 165 Lavatory 97 1.5 145.5 Kitchen sink 42 2.2 92.4 Service sink 2 4 8 Dishwasher 42 2 84 Bathtub 0 8 0 Clothes washer 41 6 246 Hose (1/2")1 5 5 Hose (5/8")0 9 0 Hose (3/4")0 12 0 Bedpan washer 0 10 0 Drinking Fountain 1 2 2 Dental unit 0 2 0 Total Fixture Values 1166.9 From Table 4-1 (Pressure Adj Factor) 1.25 From Figure 4-1 (GPM Demand per Fixture Values) 1458.625 Total 65 GPM 2" Fixture Values Figures from AWWA, Manual M22, Second Edition total, ENCLAVE - AWWA.xls LEASING 1 buildings TOTAL NO. OF FIXTURES AWWA FIXTURE VALUE TOTAL WC (tank) 5 4 20 WC (flush valve) 0 35 0 Urinal (wall or stall) 0 16 0 Urinal (flush valve) 1 35 35 Bidet 0 2 0 Shower 0 2.5 0 Lavatory 6 1.5 9 Kitchen sink 1 2.2 2.2 Service sink 2 4 8 Dishwasher 1 2 2 Bathtub 0 8 0 Clothes washer 0 6 0 Hose (1/2") 1 5 5 Hose (5/8") 0 9 0 Hose (3/4") 0 12 0 Bedpan washer 0 10 0 Drinking Fountain 1 2 2 Dental unit 0 2 0 Total Fixture Values 83.2 From Table 4-1 (Pressure Adj Factor) 1.25 From Figure 4-1 (GPM Demand per Fixture Values) 104 Total 25 GPM 1" Fixture Values Figures from AWWA, Manual M22, Second Edition leasing center & maintenance, ENCLAVE - AWWA.xls 8 units/ building 8-plex 14 buildings no fixtures/unit TOTAL NO. OF FIXTURES AWWA FIXTURE VALUE TOTAL WC (tank) 3 24 4 96 WC (flush valve)0 35 0 Urinal (wall or stall)0 16 0 Urinal (flush valve)0 35 0 Bidet 0 2 0 Shower 2 16 2.5 40 Lavatory 3 24 1.5 36 Kitchen sink 1 8 2.2 17.6 Service sink 0 4 0 Dishwasher 1 8 2 16 Bathtub 0 8 0 Clothes washer 1 8 6 48 Hose (1/2")0 5 0 Hose (5/8")0 9 0 Hose (3/4")0 12 0 Bedpan washer 0 10 0 Drinking Fountain 0 2 0 Dental unit 0 2 0 Total Fixture Values 253.6 From Table 4-1 (Pressure Adj Factor) 1.25 From Figure 4-1 (GPM Demand per Fixture Values) 317 Total 38 GPM 1-1/2" Fixture Values Figures from AWWA, Manual M22, Second Edition 8-plex (8C.6), ENCLAVE - AWWA.xls 6 units/building 6-plex 11 buildings no. fixtures/unit TOTAL NO. OF FIXTURES AWWA FIXTURE VALUE TOTAL WC (tank) 3 18 4 72 WC (flush valve)0 35 0 Urinal (wall or stall)0 16 0 Urinal (flush valve)0 35 0 Bidet 0 2 0 Shower 2 12 2.5 30 Lavatory 3 18 1.5 27 Kitchen sink 1 6 2.2 13.2 Service sink 0 4 0 Dishwasher 1 6 2 12 Bathtub 0 8 0 Clothes washer 1 6 6 36 Hose (1/2")0 5 0 Hose (5/8")0 9 0 Hose (3/4")0 12 0 Bedpan washer 0 10 0 Drinking Fountain 0 2 0 Dental unit 0 2 0 Total Fixture Values 190.2 From Table 4-1 (Pressure Adj Factor) 1.25 From Figure 4-1 (GPM Demand per Fixture Values) 237.75 Total 31 GPM 1-1/2 Fixture Values Figures from AWWA, Manual M22, Second Edition 6-plex (6b.3), ENCLAVE - AWWA.xls 4 units/building 4-plex 16 buildings no. fixtures per unit TOTAL NO. OF FIXTURES AWWA FIXTURE VALUE TOTAL WC (tank) 1 4 4 16 WC (flush valve)0 35 0 Urinal (wall or stall)0 16 0 Urinal (flush valve)0 35 0 Bidet 0 2 0 Shower 1 4 2.5 10 Lavatory 1 4 1.5 6 Kitchen sink 1 4 2.2 8.8 Service sink 0 4 0 Dishwasher 1 4 2 8 Bathtub 0 8 0 Clothes washer 1 4 6 24 Hose (1/2")0 5 0 Hose (5/8")0 9 0 Hose (3/4")0 12 0 Bedpan washer 0 10 0 Drinking Fountain 0 2 0 Dental unit 0 2 0 Total Fixture Values 72.8 From Table 4-1 (Pressure Adj Factor) 1.25 From Figure 4-1 (GPM Demand per Fixture Values) 91 Total 22 GPM 1" Fixture Values Figures from AWWA, Manual M22, Second Edition 4-plex (A4.1), ENCLAVE - AWWA.xls