I have again reviewed this project and my original comments still apply. If
the access situation unfolds as you described, the only new issue is that the
parking lot turning radius in the area of the west fire hydrant does not pro-
vide the required 20' inside and 40' outside turning radius. This would be
required if the north access point is abandoned.
As we discussed, it would be helpful if the developer will indicate if the
building is to have a fire sprinkler system. Given the size and configuration
of the building, I expect it will be. The fire hydrant locations are okay as
shown but must be connected to the 14" main to provide adequate fire flow.
Approved "NO PARKING - FIRE LANE" signs must be posted at each end of the
parking islands on the west side.