HomeMy WebLinkAboutKECHTER FARM MIXED-USE TOWNHOMES - FDP210021 - DOCUMENT MARKUPS - ROUND 3 - UTILITY PLANSKECHTER ROAD
ZIEGLER ROADE. TRILBY ROAD
FOSSIL CREEK
RESERVOIR
12' -℄
24' -
31" ROLLOVER
CURB AND GUTTER
FLUSH TRANSITION
AT DRIVEWAYS
12' -℄
2.00%
SheetKECHTER FARM TOWNHOMESNOT FOR CONSTRUCTIONREVIEW SETof 27
CS1 COVER STEET1
Original Field Survery:
Northern Engineering
Project No. 1124-006
Date: February 2, 2021
SEPTEMBER 2021 CONTACT INFORMATION
PROJECT TEAM:
VICINITY MAP
NORTH
PROJECT DATUM: NAVD88
City of Fort Collins Benchmark A409
South and West of the intersection of Tribly Road and US Highway 287
ELEV.=5039.43
Please Note: This plan set is using NAVD88 for a vertical datum. Surrounding
developments have used NGVD29 Unadjusted for their vertical datums.
If NGVD29 Unadjusted Datum is required for any purpose, the following
equation should be used: NGVD29 Unadjusted = NAVD88 - 3.18'
PROJECT BENCHMARKS:
KECHTER FARM TOWNHOMES
PROJECT TEAM:
Northern Engineering Services, Inc.
Shane Ritchie
301 North Howes Street, Suite 100
Fort Collins, Colorado 80521
(970) 221-4158
PLANNER/
LANDSCAPE ARCHITECT
OWNER/APPLICANT
SITE ENGINEER
SHEET INDEX
FIELD SURVEY BY:
Northern Engineering Services, Inc.
Bob Tessely, PLS
301 North Howes Street, Suite 100
Fort Collins, Colorado 80521
(970) 221-4158
SITE SURVEYOR
TYPICAL SECTIONS (MULTIFAMILY)
1 CS1 COVER SHEET
2 CS2 GENERAL & CONSTRUCTION NOTES
3 EX1 EXISTING CONDITIONS & DEMOLITION PLAN
4 PV1 PAVING PLAN
UTILITY SHEETS
5 OU1 OVERALL UTILITY PLAN
6 SS1 SANITARY LINE A (W) & A3 PLAN & PROFILE
7 SS2 SANITARY LINE A (E) PLAN & PROFILE
8 ST1 STORM DRAIN A PLAN & PROFILE
9 ST2 STORM DRAIN A(S) & A(S)-1 PLAN & PROFILE
10 ST3 STORM DRAIN A2 PLAN & PROFILE
11 ST4 STORM DRAIN A2-2, A2-5 & A2-5.1 PLAN & PROFILE (PUBLIC & PRIVATE)
GRADING SHEETS
12 OG1 OVERALL GRADING PLAN
13 G1 GRADING PLAN
14 G2 GRADING PLAN
ROADWAY SHEETS
15 R1 STREET A PLAN & PROFILE
DETAIL SHEETS
16 D1 SITE DETAILS
17 D2 SITE DETAILS
18 D3 WATER DETAILS
19 D4 SANITARY SEWER DETAILS
20 D5 DRAINAGE DETAILS
21 D6 DRAINAGE DETAILS
22 D7 DRAINAGE DETAILS
23 D8 DRAINAGE DETAILS
24 EC1 EROSION CONTROL PLAN
25 EC2 EROSION CONTROL DETAILS
DRAINAGE SHEETS
26 DR1 DRAINAGE EXHIBIT
27 H-DRN HISTORICAL DRAINAGE EXHIBIT
FINAL UTILITY PLANS FOR
UTILITY CONTACT LIST: *
UTILITY COMPANY
* This list is provided as a courtesy reference only. Northern Engineering Services assumes no responsibility for
the accuracy or completeness of this list. In no way shall this list relinquish the Contractor's responsibility for
locating all utilities prior to commencing any construction activity. Please contact the Utility Notification Center of
Colorado (UNCC) at 811 for additional information.
PHONE NUMBER
GAS-----------------Xcel Energy-----------------------------Pat Kreager (970) 225-7840
ELECTRIC--------City of Fort Collins Light & Power--Rob Irish (970) 224-6167
CABLE-------------Comcast----------------------------------Don Kapperman (970) 567-0425
TELECOM.--------CenturyLink-------------------------------William Johnson (970) 377-6401
WATER------------Fort Collins-Loveland Water District--Chris Pletcher (970) 226-3104
WASTEWATER-South Fort Collins Sanitation District--Chris Pletcher (970) 226-3104
STORMWATER-City of Fort Collins Utilities-----------Wes Lamarque (970) 416-2418PROJECT
SITE
A TRACT OF LAND LOCATED IN THE NORTHEAST QUARTER OF SECTION 8, TOWNSHIP 6 NORTH,
RANGE 68 WEST OF THE 6TH P.M., COUNTY OF LARIMER, STATE OF COLORADO
Black Timber Land Company
Russell Baker
417 Jefferson Street
Fort Collins, CO 80524
(970) 267-7721
■ land planning ■ landscape architecture ■
■ urban design ■ entitlement ■
Ripley Design, Inc.
Alex Garvert
419 Canyon Avenue, Suite 200
Fort Collins, Colorado 80521
(970) 224-5828
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.
before you dig.Call
R
APPROVED:
City Engineer:Approved Sheets Date
Water & Wastewater Utility Approved Sheets Date
Stormwater Utility Approved Sheets Date
Park Planning and Development Approved Sheets Date
Traffic Operations Approved Sheets Date
Environmental Planner Approved Sheets Date
City of Fort Collins, Colorado
UTILITY PLAN APPROVAL
APPROVED:
APPROVED:
APPROVED:
APPROVED:
APPROVED:
V.P.
V.P.C.O.S
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR CONTROL
IRR
CONTROL
IRRI S
OIS
OCONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRRCONTROL
IRR
CONTROL
IRRCONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRR
CONTROL
IRRCONTROL
IRRCONTROL
IRRCONTROL
IRR
VAULT
F.O.
D
S
S FOFOFOFOFOFOIRRIRRIRRIRRIRRIRR
IRRIRRIRRIRR
IRR
IR
R
IRR
IRR
IRR IRR IRR IRR IRR IRR IRRIRRIRRIRRIRRIRRIRRIRRIRRIRRIRRIRRIRRIRRIRRIRR
X XXXXXXXXXFO
FO
FO
FO
FO
FO
FO FO FO
FO
FO
FO FO FO FO FO
FOSTSTSTSTSTSTST284.0'SSSSSSSS
SS
EAST TRILBY ROAD
ZIEGLER ROADD
D
H2O
HY DD
D
REMOVE AND REPLACE
EXISTING SANITARY MH
REMOVE AND REPLACE
EXISTING SANITARY SEWER MANHOLE
RIM = 4927.24
INV. IN = 4917.26 (NE)
INV. OUT = 4917.07 (S)
REMOVE AND REPLACE
EXISTING 6" SANITARY
LINE
REMOVE OR ABANDON
EXISTING 6" SANITARY LINE
AS NECESSARY. PLUG FOR ABANDONMENT.
(SEE DETAIL SHEET D4)
REMOVE EXISTING
STROM INLET
REMOVE & REPLACE 28' ±
EXISTING 36" RCP STORM LINE
DEMO EXISTING
IRRIGATION LINE (TYP.)
EXISTING TREE TO
BE REMOVED (TYP.)
DEMO 60'± OF ASPHALT,
CURB & GUTTER
DEMO 54'± OF ASPHALT,
CURB & GUTTER
PROJECT BOUNDARY
EXISTING UNDERGROUND
FIBER OPTICS LINE
EXISTING STREET SIGN (TYP.)
EXISTING STORM MANHOLE
RIM = 4923.71
INV. IN = 4915.26 (S)
INV. OUT = 4915.21 (N)
PIPING NORTH OF MANHOLE
INACTIVE/ABANDONED
EXISTING STORM MANHOLE
RIM = 4921.68
INV. IN = 4917.32 (S)
INV. OUT = 4917.25 (N)
EXISTING 5' SIDEWALK
EXISTING 4.5' SIDEWALKEXISTING PEDESTRIAN RAMP
EXISTING TREE
TO REMAIN (TYP.)
EXISTING CONCRETE/BRICK FENCE POST
EXISTING 6' WOOD PICKET FENCE
EXISTING SPLIT RAIL FENCE
EXISTING STORM MANHOLE
RIM = 4926.78
INV. IN = 4918.17 (E)
INV. OUT = 4918.13 (SW)
EXISTING SANITARY SEWER MANHOLE
RIM = 4923.47
INV. IN = 4910.68 (N)
INV. OUT = 4910.55 (S)
DEMO EXISTING IRRIGATION
CONTROL BOX (TYP.)
EXISTING IRRIGATION
TAP & METER PIT.
SEE IRRIGATION PLANS
FOR DETAILS
57' ± OF EXISTING
SIDEWALK
DEMO 88' ± OF
EXISTING SIDEWALK
EXISTING VERTICAL PIPE
DEMO EXISTING VERTICAL PIPE
TRILBY ROAD (ROW VARIES)
PER KINARD JUNIOR HIGH SCHOOL
MLD (05-S2463)
LOT 1
KINARD JUNIOR HIGH SCHOOL MLD
(05-S2463)ZIEGLER ROAD (ROW VARIES)PER FOSSIL LAKE PUD FIRST FILING & KECHTERFARM PLANNED LAND DIVISION - FILING 1FOSSIL LAKE PUD FIRST FILINGTRILBY ROAD (ROW VARIES)
PER FOSSIL LAKE PUD
FIRST FILING
TRILBY ROAD (ROW VARIES)
PER FOSSIL LAKE PUD
FIRST FILING
OUTLOT B
FOSSIL LAKE PUD
FIRST FILING
LOT 12
K
E
C
H
T
E
R
F
A
R
M
P
L
A
N
N
E
D
L
A
N
D
D
I
V
I
S
I
O
N
FI
L
I
N
G
1
LOT 13
LOT 14
T
R
A
C
T
N
LOT 3
KECHTER FARM MLD #13-S3150
LOT 11
EXISTING STORM MANHOLE
RIM = 4921.12
INV. IN = 4917.61 (S)
INV. OUT = 4917.45 (N)
EXISTING FIRE HYDRANT
EXISTING 24" WATER LINE
EXISTING STORM MANHOLE
RIM=4921.40
INV IN=4916.20 (NW) 6" PVC
INV IN=4916.24 (SW) 10" PLASTIC
INV OUT=4916.07 (S)
TOP=4917.38 (N) 18" RCP
CONC. PLUG AT FL (N & S);
NO MH NORTH, PIPING SOUTH
OF MH INACTIVE/ABANDONED
EXISTING 12" PVC
WATER LINE
SheetKECHTER FARM TOWNHOMESNOT FOR CONSTRUCTIONREVIEW SETof 27
EX1 DEMOLITION PLANEXISTING CONDITIONS &3
NORTH
( IN FEET )
1 inch = ft.
Feet04040
40
80 120
EXISTING ELECTRIC E
LEGEND:
G
T
EXISTING STORM SEWER
EXISTING TELEPHONE
EXISTING GAS
EXISTING IRRIGATION BOX
EXISTING GAS METER
EXISTING TELEPHONE PEDESTAL
EXISTING TREES (TO REMAIN)
FIELD SURVEY BY:
NOTES:
EXISTING SANITARY SEWER SS
EXISTING WATER W
EXISTING FENCE X
EXISTING WATER METER
EXISTING FIRE HYDRANT
EXISTING ELECTRIC VAULT
PROJECT BOUNDARY
EXISTING RIGHT-OF-WAY
EXISTING MAJOR CONTOUR
EXISTING MINOR CONTOUR
VAULT
ELEC
CONTROL
IRR
EXISTING TREES (TO BE REMOVED)
EXISTING CABLE CTV
EXISTING FIBER OPTIC FO
1. THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE
APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL
UNDERGROUND UTILITIES IN THE AREA OF THE WORK. BEFORE COMMENCING NEW
CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL
UNDERGROUND UTILITIES AND SHALL BE RESPONSIBLE FOR ALL UNKNOWN
UNDERGROUND UTILITIES.
2.CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING DEMOLITION, REMOVAL,
REPLACEMENT, AND DISPOSAL OF ALL FACILITIES AND MATERIAL.
3.CONTRACTOR IS ENCOURAGED TO PERFORM DEMOLITION IN A MANNER THAT
MAXIMIZES SALVAGE, RE-USE, AND RECYCLING OF MATERIALS. THIS INCLUDES
APPROPRIATE SORTING AND STORING. IN PARTICULAR, DEMOLISHED CONCRETE,
ASPHALT, AND BASE COURSE SHOULD BE RECYCLED IF POSSIBLE.
4.ALL SYMBOLS ARE ONLY GRAPHICALLY REPRESENTED AND ARE NOT TO SCALE.
5.CONTACT THE PROJECT SURVEYOR FOR ANY INQUIRIES RELATED TO THE EXISTING
SITE SURVEY.
EXISTING OVERHEAD UTILITY OHE
EXISTING ASPHALT TO BE REMOVED
EXISTING IRRIGATION LINE IRR
EXISTING CONCRETE TO BE REMOVED
Original Field Survery:
Northern Engineering
Project No. 1124-006
Date: February 2, 2021
EXISTING TREES (TO BE TRANSPLANTED)
TREE PROTECTION NOTES
TREE DIAMETER AT BREAST HEIGHT
(INCHES)
AUGER DISTANCE FROM FACE OF
TREE (FEET)
0-2 1
3-4 2
5-9 5
10-14 10
15-19 12
OVER 19 15
1.ALL EXISTING TREES WITHIN THE LIMITS OF THE DEVELOPMENT AND WITHIN ANY NATURAL
AREA BUFFER ZONES SHALL REMAIN AND BE PROTECTED UNLESS NOTED ON THESE PLANS
FOR REMOVAL.
2.WITHIN THE DRIP LINE OF ANY PROTECTED EXISTING TREE, THERE SHALL BE NO CUT OR FILL
OVER A FOUR-INCH DEPTH UNLESS A QUALIFIED ARBORIST OR FORESTER HAS EVALUATED
AND APPROVED THE DISTURBANCE.
3.ALL PROTECTED EXISTING TREES SHALL BE PRUNED TO THE CITY OF FORT COLLINS
FORESTRY STANDARDS. TREE PRUNING AND REMOVAL SHALL BE PERFORMED BY A
BUSINESS THAT HOLDS A CURRENT CITY OF FORT COLLINS ARBORIST LICENSE WHERE
REQUIRED BY CODE.
4.PRIOR TO AND DURING CONSTRUCTION, BARRIERS SHALL BE ERECTED AROUND ALL
PROTECTED EXISTING TREES WITH SUCH BARRIERS TO BE OF ORANGE FENCING A MINIMUM
OF FOUR (4) FEET IN HEIGHT, SECURED WITH METAL T-POSTS, NO CLOSER THAN SIX (6) FEET
FROM THE TRUNK OR ONE-HALF (½) OF THE DRIP LINE, WHICHEVER IS GREATER. THERE
SHALL BE NO STORAGE OR MOVEMENT OF EQUIPMENT, MATERIAL, DEBRIS OR FILL WITHIN
THE FENCED TREE PROTECTION ZONE.
5.DURING THE CONSTRUCTION STAGE OF DEVELOPMENT, THE APPLICANT SHALL PREVENT
THE CLEANING OF EQUIPMENT OR MATERIAL OR THE STORAGE AND DISPOSAL OF WASTE
MATERIAL SUCH AS PAINTS, OILS, SOLVENTS, ASPHALT, CONCRETE, MOTOR OIL OR ANY
OTHER MATERIAL HARMFUL TO THE LIFE OF A TREE WITHIN THE DRIP LINE OF ANY
PROTECTED TREE OR GROUP OF TREES.
6.NO DAMAGING ATTACHMENT, WIRES, SIGNS OR PERMITS MAY BE FASTENED TO ANY
PROTECTED TREE.
7.LARGE PROPERTY AREAS CONTAINING PROTECTED TREES AND SEPARATED FROM
CONSTRUCTION OR LAND CLEARING AREAS, ROAD RIGHTS-OF-WAY AND UTILITY EASEMENTS
MAY BE "RIBBONED OFF," RATHER THAN ERECTING PROTECTIVE FENCING AROUND EACH
TREE AS REQUIRED IN SUBSECTION (G)(3) ABOVE. THIS MAY BE ACCOMPLISHED BY PLACING
METAL T-POST STAKES A MAXIMUM OF FIFTY (50) FEET APART AND TYING RIBBON OR ROPE
FROM STAKE-TO-STAKE ALONG THE OUTSIDE PERIMETERS OF SUCH AREAS BEING CLEARED.
8.THE INSTALLATION OF UTILITIES, IRRIGATION LINES OR ANY UNDERGROUND FIXTURE
REQUIRING EXCAVATION DEEPER THAN SIX (6) INCHES SHALL BE ACCOMPLISHED BY BORING
UNDER THE ROOT SYSTEM OF PROTECTED EXISTING TREES AT A MINIMUM DEPTH OF
TWENTY-FOUR (24) INCHES. THE AUGER DISTANCE IS ESTABLISHED FROM THE FACE OF THE
TREE (OUTER BARK) AND IS SCALED FROM TREE DIAMETER AT BREAST HEIGHT AS
DESCRIBED IN THE CHART BELOW:
9.ALL TREE REMOVAL SHOWN SHALL BE COMPLETED OUTSIDE OF THE SONGBIRD NESTING
SEASON (FEB 1 - JULY 31) OR CONDUCT A SURVEY OF TREES ENSURING NO ACTIVE NESTS IN
THE AREA.
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.
before you dig.Call
R
VAULT
F.O.
D
S FOFOFOFOFOFOX XXXXXXXXXFO
FO
FO
FO
FO
FO
FO FO FO
FO
FO
FO FO FO FO FO
FOEAST TRILBY ROAD
ZIEGLER ROADD
H2OHYD D
DGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGEE
E
E
E
E
E
E E E
E
E
E
E E E E
E
EEEEEEEESSS
SSSSSSS
SSSSSSS
SSSSS S
SSSSEVAULT
ELEC
VAULT
ELEC
VAULT
ELEC
EEEE E E E E E
E
EE E EET
T ES
E E E
EM
E
E
E
E
E
EEEEE
E
E
E
E
E
E
E
E
E
E
E
E
EEEEE EE
EEE
SANITARY SEWER A(W) (PRIVATE)
SEE THIS SHEET
SANITARY SEWER A(E) (PRIVATE)
SEE THIS SHEET
STORM DRAIN A
SEE SHEET ST1
STORM DRAIN A
SEE SHEET ST1
STORM DRAIN A2
SEE SHEET ST3
STORM DRAIN A(S)-1
SEE SHEET ST2
STORM DRAIN A2-5.1
SEE SHEET ST4
SANITARY SEWER A3 (PRIVATE)
SEE THIS SHEET
4" SANITARY SERVICE (TYP.)
PROJECT BOUNDARY
SSMH A1
STA 11+58.06
N: 100315.46
E: 209958.74
SSMH A3
STA 13+31.82
N: 100351.70
E: 210096.46
SSMH A6
STA 17+68.86
N: 100344.86
E: 210495.56
SSMH A4
STA 14+40.59
N: 100288.62
E: 210185.07
SSMH A2
STA 12+71.80
N: 100386.51
E: 210047.56
SSMH A5
STA 15+38.40
N: 100344.86
E: 210265.09
EX_SSMH A
CONNECT TO EXISTING SSMH
STA 10+00.00
N: 100165.68
E: 210009.24 158.06 LF 8" PVC @ 0.93%113.74 LF 8" PVC @ 0.92%
60.02 LF 6" PVC @ 1.00%
108.77 LF
6" PVC
@ 1.00%
97.81 LF
6" PVC
@ 1.00%
230.46 LF 6" PVC @ 1.00%
18.72 LF
6" PVC
@ 1.00%
63.11 LF 6" PVC @ 1.00%
SAN CLEANOUT A3-2
STA 10+81.84
N: 100414.81
E: 210115.18
STORM DRAIN A(S)
SEE SHEET ST2
WATER LINE A
SEE SHEET OU1
FIRE HYDRANT ASSEMBLY
WATER LINE A
SEE SHEET OU1
BUILDING 1
BUILDING 2
BUILDING 3
BUILDING 4
BUILDING 5
BUILDING 6
STREET A
24'
-
SAN CLEANOUT A3-1
STA 10+18.72
N: 100351.70
E: 210115.18
27' UTILITY
EASEMENT
SSMH A7
STA 18+08.28
N: 100316.99
E: 210523.42
39.41 LF
6" PVC
@ 1.00%
STORM DRAIN A2-5
SEE SHEET ST4
STORM DRAIN A2-2
SEE SHEET ST4
TRACT A
PA, EA, D, & UE TRACT B
PA, EA, & DE
GROUNDWATER
BARRIER (TYP.)
4905
4910
4915
4920
4925
4930
4935
4940
4945
4905
4910
4915
4920
4925
4930
4935
4940
4945
9+50 10+00 11+00 12+00 13+00 14+00EX_SSMH ASTA 10+00.00RIM 4923.5±INV. IN 4910.68 (N)INV. OUT 4910.55 (S)158.06 LF 8" PVC @ 0.9
3
%SSMH A1STA 11+58.06RIM 4927.2±INV. IN 4912.35 (NE)INV. OUT 4912.15 (S)113.74 LF 8" PVC @ 0.9
2
%SSMH A2STA 12+71.80RIM 4925.6±INV. IN 4913.56 (SE)INV. OUT 4913.40 (SW)60.02 LF 6" PVC @ 1.00%SSMH A3STA 13+31.82RIM 4925.6±INV. IN 4914.16 (SE)INV. IN 4914.16 (E)INV. OUT 4914.16 (NW)108.77 LF 6" PVC @ 1.00%
EXISTING GROUND
PROPOSED GROUND
GROUNDWATER BARRIER (TYP.)
4905
4910
4915
4920
4925
4930
4935
4940
4945
4905
4910
4915
4920
4925
4930
4935
4940
4945
9+50 10+00 11+00 11+50
18.72 LF 6" PVC @ 1.00%
63.11 LF 6" PVC @ 1.00%SAN CLEANOUT A3-2STA 10+81.84RIM 4915.5±INV. OUT 4914.98 (S)SSMH A3STA 10+00.00RIM 4925.6±INV. IN 4914.16 (SE)INV. IN 4914.16 (E)INV. OUT 4914.16 (NW)SAN CLEANOUT A3-1STA 10+18.72RIM 4914.9±INV. IN 4914.35 (N)INV. OUT 4914.35 (W)PROPOSED GROUND
EXISTING GROUND
GROUNDWATER BARRIER (TYP.)
SheetKECHTER FARM TOWNHOMESNOT FOR CONSTRUCTIONREVIEW SETof 27
SS1 PLAN & PROFILESANITARY LINE A(W), & A36
NORTH
( IN FEET )
1 inch = ft.
Feet04040
40
80 120
PROFILE SCALE:
SANITARY LINE A(W) (PRIVATE)STAMATCH LINESEE SHEET14+00SS2KEYMAP
E. TRILBY ROAD
ZIEGLER ROADEXISTING WATER MAIN
PROPOSED WATER MAIN
PROPOSED STORM SEWER
LEGEND:
NOTES:
1.THE SIZE, TYPE AND LOCATION OF ALL KNOWN UNDERGROUND UTILITIES ARE
APPROXIMATE WHEN SHOWN ON THESE DRAWINGS. IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTENCE OF ALL
UNDERGROUND UTILITIES IN THE AREA OF THE WORK. BEFORE COMMENCING NEW
CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL
UNDERGROUND UTILITIES AND SHALL BE RESPONSIBLE FOR ALL UNKNOWN
UNDERGROUND UTILITIES.
2.ALL SANITARY CONSTRUCTION SHALL BE PER SOUTH FORT COLLINS SANITATION
DISTRICT CONSTRUCTION STANDARDS, LATEST EDITION.
3.MANHOLE RIM ELEVATIONS ARE TO BE ADJUSTED TO 1 4" BELOW FINISHED GRADE. IF
NECESSARY, CONE SECTIONS SHALL BE ROTATED TO PREVENT LIDS BEING LOCATED
WITHIN VEHICLE OR BICYCLE WHEEL PATHS.
4.UTILITY SERVICES ARE SHOWN IN A SCHEMATIC FASHION ONLY. EXACT LOCATIONS
SHALL BE PER THE REQUIREMENTS OF THE RESPECTIVE UTILITY PROVIDERS, AND
ARE SUBJECT TO CHANGE IN THE FIELD.
5.MAINTAIN 10' HORIZONTAL AND 18" VERTICAL MINIMUM SEPARATION BETWEEN ALL
STROM DRAINS, SANITARY SEWER MAINS, WATER MAINS, AND SERVICES.
6.ALL SINGLE-FAMILY SANITARY SEWER SERVICES TO BE 4" PVC.
7.ALL SANITARY MANHOLES TO BE 4'Ø UNLESS NOTED OTHERWISE.
8.REFER TO THE PLAT FOR LOT AREAS, TRACT SIZES, EASEMENTS, LOT DIMENSIONS,
UTILITY EASEMENTS, OTHER EASEMENTS, AND OTHER SURVEY INFORMATION.
W
EXISTING STORM SEWER
SPROPOSED SEWER SERVICE
EXISTING SANITARY SEWER SS
PROPOSED AREA STORM INLET
PROPOSED CURB & GUTTER
PROPOSED SANITARY SEWER
PROPOSED FIRE HYDRANT
EXISTING FIRE HYDRANT
PROPOSED LOT LINE
PROJECT BOUNDARY
EXISTING RIGHT OF WAY
W
EASEMENT LINE
PROPOSED RIGHT OF WAY
PROPOSED COMBO STORM INLET
PROPOSED TYPE-R STORM INLET
PROPOSED WATER SERVICE
SANITARY LINE A3 (PRIVATE)
PROFILE SCALE:LINEMAT
C
H STA14+00SS1 SS2
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.
before you dig.Call
R
D3 DETAILSWATER18
SheetKECHTER FARM TOWNHOMESNOT FOR CONSTRUCTIONREVIEW SETof 27ROWROWROWROWROWROWROWROWAll changes, addendums, additions, deletions and
modifications to these drawings must be approved,
in writing, by the Fort Collins-Loveland
Water District and the South Fort Collins Sanitation District.
District Engineer Date
FORT COLLINS - LOVELAND
WATER DISTRICT
SOUTH FORT COLLINS
SANITATION DISTRICT
CALL 2 BUSINESS DAYS IN ADVANCE BEFORE YOU
DIG, GRADE, OR EXCAVATE FOR THE MARKING OF
UNDERGROUND MEMBER UTILITIES.
CALL UTILITY NOTIFICATION CENTER OF
COLORADO
Know what'sbelow.
before you dig.Call
R