HomeMy WebLinkAboutGUARDIAN SELF STORAGE - FDP210018 - DOCUMENT MARKUPS - ROUND 2 - UTILITY PLANSFORT COLLINS - LOVELAND WATER DISTRICT AND SOUTH FORT COLLINS SANITATION DISTRICT
NOTES:
1. ALL WATER AND SANITARY SEWER CONSTRUCTION SHALL BE PERFORMED ACCORDING TO THE
FORT COLLINS-LOVELAND WATER DISTRICT AND THE SOUTH FORT COLLINS SANITATION DISTRICT
STANDARDS AND SPECIFICATIONS.
2. CONSTRUCTION OF WATER AND SEWER FACILITIES REQUIRE A PRECON MEETING WITH DISTRICT
INSPECTION STAFF PRIOR TO CONSTRUCTION.
3. CONTRACTOR SHALL NOTIFY DISTRICT INSPECTORS PRIOR TO STARTING WORK.
4. CONTRACTOR SHALL CONTACT THE SANITATION DISTRICT INSPECTOR FOR SEWER INSPECTION
48 HOURS PRIOR TO CONNECTING TO EXISTING SEWER STUBS.
5. IF GROUNDWATER IS ENCOUNTERED WITHIN DEPTH OF SEWER CONSTRUCTION, MANHOLES MUST
BE WATER-PROOFED.
6. CONTRACTOR SHALL CONTACT THE WATER DISTRICT FOR WATER INSPECTION 48 HOURS PRIOR
TO CONNECTING TO EXISTING INFRASTRUCTURE.
7. ALL COMMERCIAL DOMESTIC SERVICES REQUIRE A REDUCED PRESSURE PRINCIPLE BACKFLOW
PREVENTION DEVICE.
8. ALL WATER LINES SHALL BE A MINIMUM OF (5) FIVE FEET AND A MAXIMUM OF (6) SIX FEET BELOW
FINAL GRADE.
9. ALL DISTRICT VALVES SHALL ONLY BE OPERATED BY DISTRICT OPERATIONS STAFF.
10. PIPE PRESSURE AND VACUUM TESTING SHALL BE WITNESSED BY DISTRICT INSPECTORS.
WATERLINE BACTERIA TESTS SHALL ALSO BE TAKEN BY DISTRICT INSPECTORS.
11. ONCE THE SYSTEM IS OPERATIONAL AND ALL TESTS HAVE PASSED, CONTRACTOR SHALL
REQUEST SUBSTANTIAL COMPLETION WITH A LETTER TO THE DISTRICT.
12. AS-BUILTS SHALL BE SUBMITTED IN PDF AND DWG TO THE DISTRICT FOR FINAL APPROVAL.
13. ONCE ALL PUNCH LIST ITEMS ARE COMPLETE, EASEMENTS ARE RECORDED, AND AS-BUILT FILES
ARE APPROVED, THE CONTRACTOR SHALL REQUEST FINAL COMPLETION WITH A LETTER TO THE
DISTRICT THAT INCLUDES THE DOLLAR VALUE OF THE WATER AND SEWER IMPROVEMENTS LISTED
SEPARATELY.
JR Response: Addressed
CALL OUT SIZE OF
EXISTING VALVES
(8").
3/4" WATER
SERVICE TAP
6" GV
PLEASE CALL OUT ALL NEW BENDS,
FITTINGS, ETC TO ACCOMPLISH THE
PROPOSED RELOCATION. ALL FITTTINGS
TO BE MECHANICALLY RESTRAINED.
Show existing 8"
PVC Water line.
Show existing
waterline and show
where, and how, new
water line will be
rerouted (a bend will
be needed in this
location).
JR Response: Addressed
JR Response: Addressed
JR Response: Addressed
JR Response: Addressed,
noted added for fittings
JR Response: Addressed
JR Response: Addressed