HomeMy WebLinkAboutSTANFORD SENIOR LIVING - FDP210017 - SUBMITTAL DOCUMENTS - ROUND 2 - SUPPORTING DOCUMENTATION Page 1 of 1 L-20-143-Water-Meter-Justification-AWWA 07-Sep-2021 Date: 7 Sept 2021 Re: Stanford Senior Living WATER METER JUSTIFICATION (AWWA) As required by the local potable water utility, Integrated Mechanical is providing justification for the water meter sizing. The American Water Works Association (AWWA) has published the Manual of Water Supply Practices – M22 with suggested guidelines on water meter and service sizing. Integrated Mechanical has followed the guideline and the results are attached. The Civil plans, by Northern Engineering, indicates a new 2” tap and meter. 5' downstream of the meter a 3” service will run into the building. An incoming static pressure of 80 psi has been measured at the site fire hydrant. Tap, meter and service losses will leave a minimum of 41 psi at the water service entry inside the building. Due to the height of the facility a booster pump will be utilized to gain an additional 35 psi of pressure. Internal losses within the building and the elevation loss will cost another 55 psi, leaving 20 psi at the top floor for proper water fixture operation. The facility will require 154 gpm of peak water flow. A 2” positive displacement meter is rated for up to 160 gpm while a turbine meter is rated for up to 190 gpm Either device will meet the facility demand. The proposed 2" water service, tap & meter, is deemed to be acceptable by this office. Thank you and please contact our office if you have any questions. Respectfully, Thomas M. Segelhorst Professional Engineer INTEGRATED MECHANICAL, LLC WSE = Water service entry 2 NPSH = Net Positive Suction Head Lb per square inch (psi) Minimum pressure available at main ............................................................................................................80 Per fire flow test revceived Aug 25th 2021 2324.4 WSFU Fixture Units ~ 154 GPM Flow Figure 4.2 or 4.3 ~ 2 Size in Meter loss ................................................................................................................................................7 2 Size in Tap fitting loss ...........................................................................................................................................2.7 58 feet Tap to Meter Pipe Length ~ 18 psi/100 Pressure drop per 100' pipe ..................................................................................................10.44 3 Size in Water Service Size ~ 58 feet Water Service Pipe Length (Meter to building)~ 2.8 psi/100 Pressure drop per 100' pipe ..................................................................................................1.624 12 feet Static elevation head loss ustream of WSE ........................................................................................................................................5.196 Special fixture loss - Backflow Preventer ...........................................................................................12 Special fixture loss - PRV ......................................................................................................................0 Special fixture loss - Other ......................................................................................................................0 Total overall losses and requirements (Sum lines B through H) .................................................................38.96 Pressure Available to overcome pipe friction (Line A minus Lines B to H) ................................41.04 < NPSH Available (Cannot be lower than 5, but check on pump literature) Water Boost Pump Pressure Boost 35 < Leave at zero if no booster is installed. Highest pressure required at fixture (setion 604.3) .............................................................................................20 < Look up plumbing fixture req 53 feet Static elevation head loss downtream of WSE ........................................................................................................................................22.949 Special fixture loss - Pressure Regulator ...................................................................................................................0 Special fixture loss - Other ......................................................................................................................0 545 feet Longest pipe run within building 50 % Add for valves and fitting 817.5 feet Total equivalent length pipe 4 feet/100'Pressure drop allowed per 100' pipe 32.7 Losses downstream of WSE -75.649 Extra pressure avaialble 0.391 < Must be greater than zero Pipe Sizing witin Building SIZING OF WATER PIPING SYSTEM AWWA MANUAL 22 1 Description Water Service Piping - up to WSE