HomeMy WebLinkAboutALPINE BANK - FDP210009 - SUBMITTAL DOCUMENTS - ROUND 3 - SUPPLEMENTAL INFORMATION WORD\DATA\FORMS\C-1.DOC REV.August 14, 2020
CUSTOMER OWNED SERVICE INFORMATION FORM (C-1)
City of Ft. Collins Electric Utility 700 Wood St. P.O. Box 580 Ft. Collins, CO 80522
(970)221-6700 or fax (970)221-6619
Service voltages available are (not all voltages are available at all locations):
120/240 V. 1 phase, 3 wire 120/208 V. 3 phase, 4 wire
120/208 V. 1 phase, 3 wire (network) 277/480 V. 3 phase, 4 wire
Primary 13,200 V. Grd Y /7620 120/240 V. 3 phase, 4 wire (special utility permission required)
For CT’d meters, Light and Power will provide the meter socket and CT’s to the electrical contractor. CT’s cannot be
placed in the transformer, but may be located in a building mounted cabinet (provided by owner) or in the owner’s
switchgear. In no case, can meters be mounted on the transformer.
· Cold sequencing is required for all commercial services that are direct metered.
· If CT’d metering, the owner must provide and install a - 1” conduit from the CT location to the electric meter.
Please complete the following completely and legibly:
Date Submitted: _____________________________________
Voltage Requested: _____/_____ 1 phase OR 3 phase
Building Main (not fuse) Size: ____________________ Amps
Number of Conduits: _______ Size of Conduits:_________
Number of Cables: ________ Size of Cables: ___________
Electric Heat: Yes _________kW No
Business Name: ____________________________________
Site Address: ______________________________________
Owners Name: _____________________________________
Mail Address: ______________________________________
City: ______________________________________________
State & Zip: ________________________________________
Phone: ____________________________________________
Email: ____________________________________________
General Contractor: _________________________________
Individual: _________________________________________
Mail Address: ______________________________________
City: ______________________________________________
State & Zip: ________________________________________
Phone: ____________________________________________
Email: ____________________________________________
Electrical Contractor: ________________________________
Mail Address: ______________________________________
City: ______________________________________________
State & Zip: ________________________________________
Phone: ____________________________________________
Firm: ______________________________________________
Email: _____________________________________________
Number of CT’d meters: __________ at ___________Amps each
Number of Self-Contained meters: _____ at ________Amps each
Largest Motor: ________ H.P. 1 Phase __________ H.P. 3 Phase
Will any generating system (including photo-voltaics) be installed?
Yes (contact utility for requirements) No
If Yes, this will be for: emergency service
parallel generation
Will a fire pump be installed? Yes No
Form Completed by:
Name: ________________________________________________
Company:_____________________________________________
Mail Address: _________________________________________
City: _________________________________________________
State & Zip: ___________________________________________
Phone: _______________________________________________
Email: ________________________________________________
For Office Use Only
Transformer Size: _________________________________kVA
Fault Current at Transformer: _______________________Amps
100% Construction - Cont. # ____________ Paid: ____________
A.T.E. Date: _____________________
Engineering Approval by: ______________ Date: _____________
Metering Approval by: _________________ Date: _____________
ONE-LINE GENERAL NOTES:
A. CONTRACTOR SHALL OBTAIN THE SITE SPECIFIC AVAILABLE FAULT CURRENT AT THE UTILITY
TRANSFORMER. IF THIS VALUE EXCEEDS XXAIC THE CONTRACTOR SHALL NOTIFY THE ENGINEER
IMMEDIATELY TO REVISE THE FAULT CURRENT CALCULATIONS.
T
F
X2
X1
X0
UTILITY TRANSFORMER,
COORDINATE PAD AND
RACEWAY REQUIREMENTS
PANEL
"L1"
3
E400
400A CT ENCLOSURE AND
REMOTE METER PER UTILITY
REQUIREMENTS
ELECTRICAL CONTRACTOR TO CONFIRM
POWER UTILITY COMPANY EQUIPMENT
MEETS REQUIREMENTS PRIOR TO
PURCHASE OF GEAR.
M
LIGHTING
RELAY
PANEL
20F2
400S4
X3
400F4
6162 S. Willow Drive, Suite 320
Greenwood Village, CO 80111
303.770.8884
Checked By:
Project No:
Drawn By:
COPYRIGHT
THESE PLANS ARE AN INSTRUMENT OF SERVICE
STAMP
#Date Issue/Description
AND ARE THE PROPERTY OF GALLOWAY, AND MAY
NOT BE DUPLICATED, DISCLOSED, OR
REPRODUCED WITHOUT THE WRITTEN CONSENT
OF GALLOWAY. COPYRIGHTS AND INFRINGEMENTS
WILL BE ENFORCED AND PROSECUTED.
6/18/2021 8:19:12 AMBIM 360://ALB01 - Ft Collins/ALB01_Ft Collins_MEP_R20.rvtONE-LINE DIAGRAM
E500
ALB000001
MJD
RMRS. COLLEGE AVEN. &PROSPECT ROADFORT COLLINS, COLORADOALPINE BANKALPINE BANKSCALE: NO SCALE1ELECTRICAL ONE-LINE DIAGRAM
NONCONC. 0 0 0 29025 C-PHASE LOAD
MISC 0 1 0 32136 B-PHASE LOAD
KITCHEN 0 0.65 0 32512 A-PHASE LOAD
EQUIP 71024 1 71024 273 MIN. FEEDER AMPS
LIGHTING 8020 1 8020 98234 TOTAL VA
RECEPT 24620 NEC 17310 0 0% SPARE
LOAD TYPE LOAD IN VA FACTOR DIV LOAD 96354 EMD
SPACE 125 C 126
SPACE
SPACE 123 B 124
SPACE
SPACE 121 A 122
SPACE
SPACE 119 C 120
SPACE
SPACE 117 B 118
SPACE
SPACE 115 A 116
SPACE
SPACE 113 C 114
SPACE
SPACE 111 B 112
SPACE
SPACE 109 A 110
SPACE
SPARE 20/1 107 C 108
20/1 1250 E-ZD4-4
SPARE 20/1 105 B 106
20/1 1250 E-ZD4-3
SPARE 20/1 103 A 104
20/1 1250 E-ZD4-2
SPARE 20/1 101 C 102
20/1 1250 E-ZD4-1
R-TELLERS 1080 20/1 99 B 100
20/1 1250 E-ZD1-3
R-TELLERS 720 20/1 97 A 98
20/1 1250 E-ZD1-2
R-PRINTERS 360 20/1 95 C 96
20/1 625 E-ZD1-1
R-OFFICES 720 20/1 93 B 94
20/1 76 E-TF-1
R-OFFICES 720 20/1 91 A 92
20/1 250 E-ATM LOW VOLTAGE
R-ELEVATOR PIT 180 20/1 89 C 90
20/1 250 E-TRANSACTION WINDOW
E-ELECTRIC WATER COOLER 500 GFCI 20/1 87 B 88
20/1 1200 L-BUILDING SIGNAGE
R-EXTERIOR CONVENIENCE RECEPTS 900 20/1 85 A 86
20/1 1200 L-MONUMENT SIGN
E-FUR-5 1000 20/1 83 C 84
20/1 500 E-MOTORIZED WINDOW SHADE
R-LOBBY FLOOR RECEPTS 720 20/1 81 B 82
20/1 500 E-MOTORIZED WINDOW SHADE
L-RELAY PANEL 500 LOCKABLE 20/1 79 A 80
20/1 864 E-SP (ELEV. PIT)
R-SECURITY SYSTEM 720 20/1 77 C 78
20/1 1500 E-ELEVATOR CAR
R-MECHANICAL CONVIENCE RECEPTS 360 20/1 75 B 76
* 2810 *
R-CUSTOMER SERVICE RECEPTS 540 20/1 73 A 74
* 2810 *
E-CUSTOMER SERVICE COMPUTERS 700 20/1 71 C 72
50/3 2810 E-ELEVATOR
E-TELLER/CUSOMER SERV. COMPUTERS 880 20/1 69 B 70
20/1 560 E-KS-1 (GARBAGE DISPOSAL)
R-SECOND FLR RR 360 20/1 67 A 68
20/1 93 E-CP-1
E-SERVER UPS 1500 20/1 65 C 66
20/1 750 E-GWH-1
E-SERVER UPS 1500 20/1 63 B 64
20/1 373 E-ESP-1
R-TTB QUADPLEX 360 20/1 61 A 62
* 1125 *
R-TTB QUADPLEX 360 20/1 59 C 60
20/2 1125 E-EWH-2
R-BREAK 209/IT 210/OFFICE 200 RECEPTS 1080 20/1 57 B 58
* 1125 *
R-BREAK 209 DISHWASHER 1200 GFCI 20/1 55 A 56
20/2 1125 E-EWH-1
E-BREAK 209 FRIDGE 800 GFCI 20/1 53 C 54
* 1650 E-EUH-1
R-FUTURE OFFICES 201 540 20/1 51 B 52
40/2 1650 E-EUH-1
R-HALL 204/RESTROOMS 205,206 REC 900 20/1 49 A 50
20/1 94 E-EF-2
SPARE 20/1 47 C 48
20/1 79 E-EF-1
SPARE 20/1 45 B 46
* 2496 *
E-DRIVE-UP TELLER 500 20/1 43 A 44
30/2 2496 E-CU-5
E-DRIVE-UP TELLER 500 20/1 41 C 42
* 3328 *
E-DRIVE-UP ATM 1200 20/1 39 B 40
40/2 3328 E-CU-4
E-DRIVE-UP TELLER 500 20/1 37 A 38
* 1872 *
E-UNDER COUNTER FRIDGE 750 GFCI 20/1 35 C 36
40/2 1872 E-CU-3
R-COFFEE MAKER 1200 20/1 33 B 34
* 3328 *
R-REFRESHMENT 104 RECEPTS 540 20/1 31 A 32
40/2 3328 E-CU-2
E-ATM 1200 20/1 29 C 30
* 2496 *
E-GAS FIRE PLACE 150 20/1 27 B 28
30/2 2496 E-CU-1
SPARE 20/1 25 A 26
20/1 1000 E-FUR-4
R-TELLER COMPUTERS 1060 20/1 23 C 24
20/1 560 E-FUR-3
R-TELLER COMPUTERS 1060 20/1 21 B 22
20/1 1000 E-FUR-2
R-WORK ROOM 107 RECEPTS 540 20/1 19 A 20
20/1 1000 E-FUR-1
E-PAPER SHREDDER 1000 20/1 17 C 18
20/1 1200 L-MONUMENT SIGN
R--LIVING AREA 101/LOBBY 100 REC 720 20/1 15 B 16
20/1 195 L-SITE LIGHTING
R-HALL 116/OFFICE 117 RECEPTS 900 20/1 13 A 14
20/1 442 L-EXTERIOR LIGHTING
E-ELECTRIC WATER COOLER 500 GFCI 20/1 11 C 12
20/1 216 L-SECOND FLOOR RESTROOM SHOWER
R-OFFICE 117/MECH 120/ELEC 121 REC 540 20/1 9 B 10
20/1 244 L-LOBBY
R-OFFICE 111,112 RECEPTS 720 20/1 7 A 8
20/1 1245 L-SECOND FLOOR GENERAL AREA
R-OFFICE 113,114 RECEPTS 720 20/1 5 C 6
20/1 129 L-MECH, ELEC
R-CONFERENCE 119/OFFICE 118 REC 1080 20/1 3 B 4
20/1 1001 L-OFFICE SPACES
R-CONFERENCE 119 RECEPTS 720 20/1 1 A 2
20/1 448 L-GENERAL AREA LIGHTING
DESCRIPTION LOAD VA REMARKS O/C CKT # PH CKT # O/C REMARKS LOAD VA DESCRIPTION
126 POLES THREE SECTION
18,000 AIC
400 AMP MCB
208/120V 3 PHASE 4 WIRE W/ GND BAR SURFACE MOUNTED
PANELL1
X3 RELAY PANEL 15 208 12 C S 1 10,890 3,398 X3
X2 PANEL "L1" 20 208 250 C S 2 11,524 10,890 X2
X1 CT CABINET 44 208 250 C N 2 13,000 11,524 X1
X0 TRANSFORMER SECONDARY 13,000 X0
DESCRIPTION
UPSTREAM
CIRCUIT
LENGTH
VOLTAGE
(PH-PH)
WIRE SIZE/
XFRMR KVA
RATING
WIRE MATERIAL/
TRANSFORMER (C OR A)
T=XFMR
CONDUIT
(S-STEEL OR
N-NON-MAGNETIC)
# OF
PARALLEL
RUNS
Isc AVAILABLE
UPSTREAM I(sc Fault)
SHORT CIRCUIT SCHEDULE
1 06/18/2021 1ST PERMIT
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC 2017, ARTICLE 310.15.B.3.a.
1. AMPACITY BASED UPON NEC 2017, TABLE 301.15.B.16. (100% OF 75 DEGREE THWN OR THHN)
NOTES:
60 60F2 1 1" (2#)6 (1)#10
50 50F2 1 1" (2#)8 (1)#10
40 40F2 1 1" (2)#8 (1)#10
30 30F2 1 3/4" (2)#10 (1)#10
20 20F2 1 1/2" (2)#12 (1)#12
OCPD
RATING
FEEDER
TYPE SETS CONDUIT PHASE GND
COPPER
2-WIRE FEEDER SCHEDULE
5. THE GROUND CONDUCTOR SHALL BE COPPER UNLESS NOTED OTHERWISE.
4. FEEDER CALLOUTS DENOTED WITH AN 'S' AT THE END ARE SERVICE FEEDERS AND DO NOT INCLUDE A GROUND WIRE.
3. NEUTRAL IS CONSIDERED CURRENT CARRYING CONDUCTOR
2. 3 PHASE, 4 WIRE CIRCUITS DERATED TO 80% PER NEC 2017, ARTICLE 310.15.B.3.a.
1. AMPACITY BASED UPON NEC 2017, TABLE 301.15.B.16
NOTES:
400 400F4 2 2-1/2" (4)250 KCM (1)#3 400 400F4 2 3" (4)350 KCM (1)#3
OCPD
RATING
FEEDER
TYPE SETS CONDUIT
PHASE &
NEUTRAL GND OCPD
RATING
FEEDER
TYPE SETS CONDUIT
PHASE &
NEUTRAL GND
COPPER ALUMINUM
4-WIRE FEEDER SCHEDULE
LOICDEA
NR
SOL
EDOCK MC I RROE
CD
HOER39638
06/18/2021