TO: Mr. Mike Herzig, Development Engineering Manager
City of Fort Collins
FROM: Terry Farrill, Systems Engineer rl�z
THRU: Mike DiTullio, District Manager V_�
DATE: February 26, 1992
SUBJECT: Laurie Subdivision
The Fort Collins -Loveland Water District and the South Fort Collins
Sanitation District have reviewed the above mentioned project and
submit the following comments:
The one inch private fire lines requires the installation
of meter pits and meters. These need to be shown clearly
on the plat and in the details.
The water service and private fire line for lot 5 are to
be moved further north closer to the end of the cul-de-
sac for ease of access.
The Districts do not allow the planting of trees, shrubs,
or building of permanent structures over the water or
sanitary sewer lines as shown in the center island of the
cul-de-sac.
The water and sanitary sewer lines located in the private
easement from Hepplewhite Court north to the cul-de-sac
are to be centered in the easement, with a ten foot
separation.
Twelve inch water line valves are to be located on the
north and south side of the cross in the intersection of
Shields and Wooded Creek Court.
An eight inch water line valve is to be shown at the end
of Ashford Court.
The irrigation line on Sheet 7 is to be shown on the
profile to insure that conflicts do not exist with other
utilities.
4700 South College Avenue
Fort Collins, Colorado 80525
Telephone 226-3104 -- 669-4321
On Sheet 8, an air release valve is to be shown on the
water line approximately ten feet south of the fire
hydrant.
The dimensioning of the water and sanitary sewer lines on
Sheet 9 are not correct.
All specifications on Sheet S.D.1 that are in conflict
with District specifications are to be deleted.
On Sheet S.D.1, District details are to be used for
manholes and sewer laterals.
The meter pit detail for the private fire lines are to be
shown on Sheet S.D.I.
Due to the number and nature of the above comments, the Districts
will require another review.
If you have any questions, please feel free to call.