Loading...
HomeMy WebLinkAbout2900 S COLLEGE AVE AT&T - PDP210007 - SUBMITTAL DOCUMENTS - ROUND 2 - FIRE AUTHORITY REQUIREMENTSFrom:Marcus Glasgow To:Jaclyn Levine Subject:RE: 2900 S College Ave - AT&T, PDP Rd1 Date:Friday, May 21, 2021 7:45:21 AM Attachments:image001.png image002.png image003.png image005.png CAUTION: This email originated from outside of the organization. Do not click on links or open attachments unless you recognize the sender and know that the content is safe. Hello Jaclyn, Thanks for providing the access doors. This should be sufficient for access. Thank you Marcus Glasgow Fire Safety Inspector | Plan Reveiw Poudre Fire Authority | http://www.poudre-fire.org 102 Remington St., Fort Collins, CO 80524 marcus.glasgow@poudre-fire.org | C 970.732.1701 | O 970.416.2869 From: Jaclyn Levine <jaclyn.levine@nexius.com> Sent: Thursday, May 20, 2021 2:58 PM To: Marcus Glasgow <Marcus.Glasgow@poudre-fire.org> Subject: [EXTERNAL] RE: 2900 S College Ave - AT&T, PDP Rd1 [NOTICE: This message originated outside of Poudre Fire Authority -- DO NOT CLICK on links or open attachments unless you are sure the content is safe.] Marcus, We’ve revised our plans to include 6 access doors. I’ve highlighted the locations below and attached updated plans. Please let me know if this is sufficient. Best Regards, JACLYN LEVINE Site Acquisition Manager nexius.com 773 870 5221 The information contained in this e-mail is confidential and/or proprietary to Nexius and is intended only for use by the parties to which it is addressed. If you are not the intended recipient, you are hereby notified that any review, retransmission, dissemination, distribution, copying or other use of, or taking of any action in reliance upon this information is strictly prohibited. From: Jaclyn Levine Sent: Monday, May 17, 2021 10:17 AM To: Marcus Glasgow <Marcus.Glasgow@poudre-fire.org> Subject: RE: 2900 S College Ave - AT&T, PDP Rd1 Good Morning Marcus, Hope you had a nice weekend. We are removing the existing mechanical screen panels (shown below). Do you need an access door on each side or just one on the exterior side? JACLYN LEVINE Site Acquisition Manager nexius.com 773 870 5221 The information contained in this e-mail is confidential and/or proprietary to Nexius and is intended only for use by the parties to which it is addressed. If you are not the intended recipient, you are hereby notified that any review, retransmission, dissemination, distribution, copying or other use of, or taking of any action in reliance upon this information is strictly prohibited. From: Marcus Glasgow <Marcus.Glasgow@poudre-fire.org> Sent: Friday, May 14, 2021 10:36 AM To: Jaclyn Levine <jaclyn.levine@nexius.com> Subject: RE: 2900 S College Ave - AT&T, PDP Rd1 CAUTION: This email originated from outside of the organization. Do not click on links or open attachments unless you recognize the sender and know that the content is safe. Jaclyn, Thanks for the clarification. The screen wall will need some type of identified access gate or door in order to get to any equipment from the edge of the roof. When we access the roof by ladder for a fire in the roof top units, we need to be able to get to it. Thanks Marcus Glasgow Fire Safety Inspector | Plan Reveiw Poudre Fire Authority | http://www.poudre-fire.org 102 Remington St., Fort Collins, CO 80524 marcus.glasgow@poudre-fire.org | C 970.732.1701 | O 970.416.2869 From: Jaclyn Levine <jaclyn.levine@nexius.com> Sent: Wednesday, May 12, 2021 3:23 PM To: Marcus Glasgow <Marcus.Glasgow@poudre-fire.org> Cc: Michael Zaimes <michael.zaimes@nexius.com> Subject: [EXTERNAL] RE: 2900 S College Ave - AT&T, PDP Rd1 [NOTICE: This message originated outside of Poudre Fire Authority -- DO NOT CLICK on links or open attachments unless you are sure the content is safe.] Marcus, See below for a photo of the roof, the parapet is virtually non-existent. There is no access being proposed through the screen wall. JACLYN LEVINE Site Acquisition Manager nexius.com 773 870 5221 The information contained in this e-mail is confidential and/or proprietary to Nexius and is intended only for use by the parties to which it is addressed. If you are not the intended recipient, you are hereby notified that any review, retransmission, dissemination, distribution, copying or other use of, or taking of any action in reliance upon this information is strictly prohibited. From: Marcus Glasgow <Marcus.Glasgow@poudre-fire.org> Sent: Wednesday, May 12, 2021 2:26 PM To: Jaclyn Levine <jaclyn.levine@nexius.com> Subject: RE: 2900 S College Ave - AT&T, PDP Rd1 CAUTION: This email originated from outside of the organization. Do not click on links or open attachments unless you recognize the sender and know that the content is safe. Thanks for the updated plans. I can run this by the team on Friday and will let you know. Can you tell me how tall the parapet is on this building? Also is there any access through the screen wall such as doors or gates? Thanks Marcus Glasgow Fire Safety Inspector | Plan Reveiw Poudre Fire Authority | http://www.poudre-fire.org 102 Remington St., Fort Collins, CO 80524 marcus.glasgow@poudre-fire.org | C 970.732.1701 | O 970.416.2869 From: Jaclyn Levine <jaclyn.levine@nexius.com> Sent: Wednesday, May 12, 2021 2:13 PM To: Marcus Glasgow <Marcus.Glasgow@poudre-fire.org> Cc: Michael Zaimes <michael.zaimes@nexius.com> Subject: [EXTERNAL] RE: 2900 S College Ave - AT&T, PDP Rd1 [NOTICE: This message originated outside of Poudre Fire Authority -- DO NOT CLICK on links or open attachments unless you are sure the content is safe.] Marcus, Please see attached updated plans showing a 6-foot setback from the roof edge. Can you and your team review to see if this is sufficient? Best Regards, JACLYN LEVINE Site Acquisition Manager nexius.com 773 870 5221 The information contained in this e-mail is confidential and/or proprietary to Nexius and is intended only for use by the parties to which it is addressed. If you are not the intended recipient, you are hereby notified that any review, retransmission, dissemination, distribution, copying or other use of, or taking of any action in reliance upon this information is strictly prohibited. From: Jaclyn Levine Sent: Tuesday, May 11, 2021 11:57 AM To: Marcus Glasgow <Marcus.Glasgow@poudre-fire.org> Subject: RE: 2900 S College Ave - AT&T, PDP Rd1 Hi Marcus, I appreciate the quick response. I’ll touch base with AT&T on this and try to work with the 6-foot set-back. Best Regards, JACLYN LEVINE Site Acquisition Manager nexius.com 773 870 5221 The information contained in this e-mail is confidential and/or proprietary to Nexius and is intended only for use by the parties to which it is addressed. If you are not the intended recipient, you are hereby notified that any review, retransmission, dissemination, distribution, copying or other use of, or taking of any action in reliance upon this information is strictly prohibited. From: Marcus Glasgow <Marcus.Glasgow@poudre-fire.org> Sent: Tuesday, May 11, 2021 11:45 AM To: Jaclyn Levine <jaclyn.levine@nexius.com> Subject: RE: 2900 S College Ave - AT&T, PDP Rd1 CAUTION: This email originated from outside of the organization. Do not click on links or open attachments unless you recognize the sender and know that the content is safe. Hello Jaclyn, We spoke very briefly about this during the meeting and although there is no code that applies to this, we must determine what is allowable for aerial access. The 4 foot was not determined but an idea as part of solar access and pathways that we would need to review further. I have discussed this requirement on a different project with the Assistant Fire Marshall and determined that 6 feet would be required for aerial access on that specific project. The intent of this code is to provide adequate space for the firefighter to place a ladder or bucket on the roof, safely exit the ladder/bucket with equipment/tanks and be able to maneuver around the edge of the roof safely. The 4 feet of space would not allow enough room for the firefighter to safely do this. I would suggest starting with a 6 ft pathway and we can review it from there. Marcus Glasgow Fire Safety Inspector | Plan Reveiw Poudre Fire Authority | http://www.poudre-fire.org 102 Remington St., Fort Collins, CO 80524 marcus.glasgow@poudre-fire.org | C 970.732.1701 | O 970.416.2869 From: Jaclyn Levine <jaclyn.levine@nexius.com> Sent: Tuesday, May 11, 2021 11:15 AM To: Marcus Glasgow <Marcus.Glasgow@poudre-fire.org> Cc: Murphy Johnson <murphy.johnson@nexius.com> Subject: [EXTERNAL] RE: 2900 S College Ave - AT&T, PDP Rd1 [NOTICE: This message originated outside of Poudre Fire Authority -- DO NOT CLICK on links or open attachments unless you are sure the content is safe.] Hi Marcus, During our meeting you had mentioned that typically a 4-foot setback is acceptable in allowing the required access to the roof in case of emergency. AT&T reviewed this option and determined the 4-foot setback would have minimal impact to the function of the site. I went ahead and updated the plans to reflect this and wanted to see if you could take a look and see if this update addresses your concerns. Best Regards, JACLYN LEVINE Site Acquisition Manager nexius.com 773 870 5221 The information contained in this e-mail is confidential and/or proprietary to Nexius and is intended only for use by the parties to which it is addressed. If you are not the intended recipient, you are hereby notified that any review, retransmission, dissemination, distribution, copying or other use of, or taking of any action in reliance upon this information is strictly prohibited. From: Brandy Bethurem Harras <BBethuremHarras@fcgov.com> Sent: Friday, May 7, 2021 8:46 AM To: Jaclyn Levine <jaclyn.levine@nexius.com>; Marcus Glasgow-Contact <Marcus.Glasgow@poudre-fire.org> Cc: Murphy Johnson <murphy.johnson@nexius.com> Subject: RE: 2900 S College Ave - AT&T, PDP Rd1 CAUTION: This email originated from outside of the organization. Do not click on links or open attachments unless you recognize the sender and know that the content is safe. @Marcus Glasgow – Marcus.Glasgow@poudre-fire.org or 970.416.2869, is your contact for Poudre Fire Authority. – Thanks! Brandy Bethurem Harras Development Review Coordinator City of Fort Collins Planning & Development Services 281 N. College Ave. Fort Collins, CO 80524 970.416.2744 BBethuremHarras@fcgov.com From: Jaclyn Levine <jaclyn.levine@nexius.com> Sent: Friday, May 07, 2021 8:04 AM To: Brandy Bethurem Harras <BBethuremHarras@fcgov.com> Cc: Kai Kleer <kkleer@fcgov.com>; Marc Virata <MVIRATA@fcgov.com>; Murphy Johnson <murphy.johnson@nexius.com> Subject: [EXTERNAL] RE: 2900 S College Ave - AT&T, PDP Rd1 Good Morning Brandy, We’re working on changing the design to accommodate the needs of the fire dept. Can you provide me contact info with the representative that attended our meeting? I’d like to get their input before we resubmit. Thanks! Best Regards, JACLYN LEVINE Site Acquisition Manager nexius.com 773 870 5221 The information contained in this e-mail is confidential and/or proprietary to Nexius and is intended only for use by the parties to which it is addressed. If you are not the intended recipient, you are hereby notified that any review, retransmission, dissemination, distribution, copying or other use of, or taking of any action in reliance upon this information is strictly prohibited. From: Brandy Bethurem Harras <BBethuremHarras@fcgov.com> Sent: Friday, April 23, 2021 4:53 PM To: Jaclyn Levine <jaclyn.levine@nexius.com> Cc: Kai Kleer <kkleer@fcgov.com>; Marc Virata <MVIRATA@fcgov.com> Subject: RE: 2900 S College Ave - AT&T, PDP Rd1 CAUTION: This email originated from outside of the organization. Do not click on links or open attachments unless you recognize the sender and know that the content is safe. Good Afternoon! Please find attached the finalized comments for Project Development Plan, 2900 S College Ave – AT&T, round 1. There were no additional redlines. As you progress forward with this project, if you need additional meetings with the project planner or any of the department reviewers please let me know and I can assist in those arrangements. I do ask if you are reaching out to the reviewers individually, just keep me in the loop! When you are ready to submit for round 2, let me know – Just a reminder that Wednesday at noon is the cut-off for routing each week. Thanks, have an excellent weekend! Brandy Bethurem Harras Development Review Coordinator City of Fort Collins Planning & Development Services 281 N. College Ave. Fort Collins, CO 80524 970.416.2744 BBethuremHarras@fcgov.com From: Brandy Bethurem Harras Sent: Tuesday, April 20, 2021 12:25 PM To: jaclyn.levine@nexius.com Cc: Kai Kleer <kkleer@fcgov.com>; Marc Virata <MVIRATA@fcgov.com> Subject: 2900 S College Ave - AT&T, PDP Rd1 Good Afternoon! Please find attached the draft comments and electronic redlines for Project Development Plan, 2900 S College Ave – AT&T, round 1. I will send a finalized comment letter and any additional redlines Friday afternoon. See you tomorrow! Join Zoom – 10:30A https://fcgov.zoom.us/j/94902180703 Brandy Bethurem Harras Development Review Coordinator City of Fort Collins Planning & Development Services 281 N. College Ave. Fort Collins, CO 80524 970.416.2744 BBethuremHarras@fcgov.com Building hours for 281 N. College Avenue are Monday – Thursday, 9:00AM – 12:00PM and 1:00PM – 4:00PM COVID19 Resources For all residents: https://www.fcgov.com/eps/coronavirus For businesses: https://www.fcgov.com/business/ Want to help: https://www.fcgov.com/volunteer/ This message contains confidential information and is intended only for the individual(s) addressed in the message. If you are not the named addressee, you should not disseminate, distribute, or copy this e-mail. If you are not the intended recipient, you are notified that disclosing, distributing, or copying this e-mail is strictly prohibited.