HomeMy WebLinkAboutSALUD FAMILY HEALTH CENTER LOT 4 - FDP200011 - SUBMITTAL DOCUMENTS - ROUND 2 - SUPPLEMENTAL INFORMATION323 3rd Avenue - Suite 100, Longmont, CO 80501 Tel: 303.678.1108 Fax: 303.678.1142 PCDENGINEERING.COM March 12, 2021 Water and Wastewater Development City of Fort Collins RE: Salud Family Health Center – Water Meter Justification Letter Per table E201.1 IPC 2018, the Salud Family Health Center will require a 2” water meter and 2-1/2” distribution pipe. This is based on the required water supply fixture units and flow rate determined by the 2018 International Plumbing Code (IPC) and includes the following plumbing fixtures: Water Supply Fixture Unit (WSFU) Table Fixture Quantity Cold WSFU Each Hot WSFU Each Total WSFU Each Cold WSFU Total Hot WSFU Total Total WSFU Total Drinking Fountain, or EWC 4 0.25 0.25 1.00 0.00 1.00 Kitchen Sink 5 3.00 3.00 4.00 15.00 15.00 20.00 Lavatory/Hand Sink 78 1.50 1.50 2.00 117.00 117.00 156.00 Service (Mop) Sink (or MSB) 1 2.25 2.25 3.00 2.25 2.25 3.00 Shower head 2 3.00 3.00 4.00 6.00 6.00 8.00 Urinal, Tank, <= 1 GPF 4 3.00 3.00 12.00 0.00 12.00 Water Closet, FV, <=1.6 GPF 25 10.00 10.00 250.00 0.00 250.00 Totals: 119 403.25 140.25 450.00 This WSFU value corresponds to a peak flow of 114.5 gpm. This sizing is based on the PDP Submittal floor plans provided by TW Beck Architects, PC dated May 06, 2020. The building irrigation system will be served by the domestic water service and will only be used during off-peak hours. If you have any questions, please do not hesitate to contact us. Sincerely, PCD Engineering Design Engineer – Brian Ehle 303-912-6056 Peter D’Antonio, PE, CEM, LEEDAP President