HomeMy WebLinkAboutMULBERRY CONNECTION - FDP200030 - SUBMITTAL DOCUMENTS - ROUND 3 - SUPPLEMENTAL INFORMATION (2)Defined Variables
H =Depth of Bury
Sf =Safety Factor
P =Internal Pressure
Pipe Derived Variables
A =Cross Sec. Area (Main)
Ab =Cross Sec. Area (Branch)
D =Outside Pipe Diameter
Db =Outside Diameter Branch
WP =Weight of Pipe
WW =Weight of Water in Pipe
Lr =Min. restrained Length
either side of Tee
Defined Variables
fC =Cohesion Modifier Coefficient
c =Cohesion of Soil
fΦ =Friction Angle Modifier
Φ =Internal Friction Angle of Soil
γ =Soil Density
Calculations for Tee
WE = γ • D • H =Normal Force Due to Soil
W = 2WE + WP + WW =Normal Force Acting on Pipeline
KP = tan^2((π / 180) • (45 + (Φ / 2))) =Rankin Passive Pressure Coeff.
HC = H + (D / 2) =Depth From Surface to Pipe Center
σh = γ • HC • KP + 2c√KP =Horizontal Passive Soil Pressure
AP = π • (D / 2) = Area Based on Half of Circumference
(Ap)b = π • Db =Area Based on Full Branch Circumference
RS = KN • σh • D =Bearing Resistance of Pipelines
Fsb = (Ap)b • fC • c + W • tan((π / 180) fΦ • Φ) =Frictional Resistance
Lb = Sf(P • Ab - RS • Lr) / Fsb =Minimum Restrained Length Branch
MEGALUG®
Fitting Type Pipe
Material
Soil
Type
Safety
Factor
Trench
Type
Depth
of Bury
Test
Pressure
Nominal
Size
Bend
Angle
Branch
Size
Length
Along Run
Reduced
Size
Lowside
Depth
Restraint
Length
Restraint
Length 2
Site Name:
Site Notes:
ALL JOINTS WITHIN THE CALCULATED LENGTH MUST BE RESTRAINED
IF YOUR DISTANCE BETWEEN FITTINGS IS LESS THAN OR EQUAL TO THE CALCULATED RESTRAINT LENGTH, RESTRAIN ALL JOINTS BETWEEN THOSE FITTINGS.
Project Name:
Project Notes:
www.ebaa.com • contact@ebaa.com • 800.433.1716
RESTRAINT LENGTH VALUES
Mulberry Connection
8x8 Tee
Tee PVC ML 2.0 5 4.5 Ft.200 PSI 8 In.8 In.5 Ft.69 Ft.
69 Ft.
4.5
2.0
200
64.33
64.33
0.75
0.75
5.72
23.75
5
0.00
0
0.60
29
100
337.500
704.470
2.882
4.875
1404.975
1.178
2.356
1053.731
220.768
68.827
Created by EBAA Iron's Restraint Length Calculator v7.1.3 on March 3, 2021
Defined Variables
H =Depth of Bury
Sf =Safety Factor
P =Internal Pressure
θ =Bend Angle
Pipe Derived Variables
A =Cross Sec. Area of Pipe
D =Outside Pipe Diameter
WP =Weight of Pipe
WW =Weight of Water in Pipe
Defined Variables
fC =Cohesion Modifier Coefficient
c =Cohesion of Soil
fΦ =Friction Angle Modifier
Φ =Internal Friction Angle of Soil
γ =Soil Density
KN =Trench Compaction Modifier
Calculations for Vertical Offset Sym.Lower Upper
WE = γ • D • H =Normal Force Due to Soil
W = 2WE + WP + WW =Normal Force Acting on Pipeline
KP = tan^2((π / 180) • (45 + (Φ / 2))) =Rankin Passive Pressure Coeff.
HC = H + (D / 2) =Depth From Surface to Pipe Center
σh = γ • HC • KP + 2c√KP =Horizontal Passive Soil Pressure
AP = π • (D / 2) = Area Based on Half of Circumference
RS = KN • σh • D =Bearing Resistance of Pipelines
FS = AP • fC • c + W • tan((π / 180) • fΦ • Φ) =Frictional Resitance
L = (SF • P • A • tan((π / 180) • (θ / 2))) / (FS + (RS / 2)) =Minimum Restrained Length Lower
L = (SF • P • A • tan((π / 180) • (θ / 2))) / FS =Minimum Restrained Length Upper
MEGALUG®
Fitting Type Pipe
Material
Soil
Type
Safety
Factor
Trench
Type
Depth
of Bury
Test
Pressure
Nominal
Size
Bend
Angle
Branch
Size
Length
Along Run
Reduced
Size
Lowside
Depth
Restraint
Length
Restraint
Length 2
Site Name:
Site Notes:
ALL JOINTS WITHIN THE CALCULATED LENGTH MUST BE RESTRAINED
IF YOUR DISTANCE BETWEEN FITTINGS IS LESS THAN OR EQUAL TO THE CALCULATED RESTRAINT LENGTH, RESTRAIN ALL JOINTS BETWEEN THOSE FITTINGS.
Project Name:
Project Notes:
www.ebaa.com • contact@ebaa.com • 800.433.1716
RESTRAINT LENGTH VALUES
Mulberry Connection
45 Deg Vertical Bend
Vertical Offset
Sym Return PVC ML 2.0 5 4.5 Ft.200 PSI 8 In.45°6 Ft.49 Ft.11 Ft.
49 Ft.
49 Ft.
11 Ft.
11 Ft.11 Ft.
11 Ft.
49 Ft.
49 Ft.
4.5
2.0
200
45
64.33
0.75
5.72
23.75
0.00
0
0.60
29
100
1.00
337.500
704.470
2.882
4.875
1.178
1377.956
220.768
48.279
450.000
929.470
2.882
6.375
1837.275
1.178
1377.956
291.278
10.873
Created by EBAA Iron's Restraint Length Calculator v7.1.3 on March 3, 2021
Defined Variables
H =Depth of Bury
Sf =Safety Factor
P =Internal Pressure
Pipe Derived Variables
A =Cross Sec. Area of Pipe
D =Outside Pipe Diameter
WP =Weight of Pipe
WW =Weight of Water in Pipe
Defined Variables
fC =Cohesion Modifier Coefficient
c =Cohesion of Soil
fΦ =Friction Angle Modifier
Φ =Internal Friction Angle of Soil
γ =Soil Density
Calculations for Dead End
WE = γ • D • H =Normal Force Due to Soil
W = 2WE + WP + WW =Normal Force Acting on Pipeline
(Ap)b = π • D =Area Based on Full Pipe Circumference
Fsb = (Ap)b • fC • c + W • tan((π / 180) fΦ • Φ) =Frictional Resistance
L = SF • P • A / Fsb =Minimum Restrained Length of Dead End
MEGALUG®
Fitting Type Pipe
Material
Soil
Type
Safety
Factor
Trench
Type
Depth
of Bury
Test
Pressure
Nominal
Size
Bend
Angle
Branch
Size
Length
Along Run
Reduced
Size
Lowside
Depth
Restraint
Length
Restraint
Length 2
Site Name:
Site Notes:
ALL JOINTS WITHIN THE CALCULATED LENGTH MUST BE RESTRAINED
IF YOUR DISTANCE BETWEEN FITTINGS IS LESS THAN OR EQUAL TO THE CALCULATED RESTRAINT LENGTH, RESTRAIN ALL JOINTS BETWEEN THOSE FITTINGS.
Project Name:
Project Notes:
www.ebaa.com • contact@ebaa.com • 800.433.1716
RESTRAINT LENGTH VALUES
Mulberry Connection
8" Gate Valve
Dead End PVC ML 2.0 5 4.5 Ft.200 PSI 8 In.117 Ft.
117 Ft.
4.5
2.0
200
64.33
0.75
5.72
23.75
0.00
0
0.60
29
100
337.500
704.470
2.356
220.768
116.557
Created by EBAA Iron's Restraint Length Calculator v7.1.3 on March 3, 2021
Defined Variables
H =Depth of Bury
Sf =Safety Factor
P =Internal Pressure
θ =Bend Angle
Pipe Derived Variables
A =Cross Sec. Area of Pipe
D =Outside Pipe Diameter
WP =Weight of Pipe
WW =Weight of Water in Pipe
Defined Variables
fC =Cohesion Modifier Coefficient
c =Cohesion of Soil
fΦ =Friction Angle Modifier
Φ =Internal Friction Angle of Soil
γ =Soil Density
KN =Trench Compaction Modifier
Calculations for Horizontal Bend
WE = γ • D • H =Normal Force Due to Soil
W = 2WE + WP + WW =Normal Force Acting on Pipeline
KP = tan^2((π / 180) • (45 + (Φ / 2))) =Rankin Passive Pressure Coeff.
HC = H + (D / 2) =Depth From Surface to Pipe Center
σh = γ • HC • KP + 2c√KP =Horizontal Passive Soil Pressure
AP = π • (D / 2) = Area Based on Half of Circumference
RS = KN • σh • D =Bearing Resistance of Pipelines
FS = AP • fC • c + W • tan((π / 180) • fΦ • Φ) =Frictional Resitance
L = (SF • P • A • tan((π / 180) • (θ / 2))) / (FS + (RS / 2)) =Minimum Restrained Length
MEGALUG®
Fitting Type Pipe
Material
Soil
Type
Safety
Factor
Trench
Type
Depth
of Bury
Test
Pressure
Nominal
Size
Bend
Angle
Branch
Size
Length
Along Run
Reduced
Size
Lowside
Depth
Restraint
Length
Restraint
Length 2
Site Name:
Site Notes:
ALL JOINTS WITHIN THE CALCULATED LENGTH MUST BE RESTRAINED
IF YOUR DISTANCE BETWEEN FITTINGS IS LESS THAN OR EQUAL TO THE CALCULATED RESTRAINT LENGTH, RESTRAIN ALL JOINTS BETWEEN THOSE FITTINGS.
Project Name:
Project Notes:
www.ebaa.com • contact@ebaa.com • 800.433.1716
RESTRAINT LENGTH VALUES
Mulberry Connection
90 Deg Horizontal Bend
Horizontal Bend PVC ML 2.0 5 4.5 Ft.200 PSI 8 In.90°35 Ft.
35 Ft.35 Ft.
4.5
2.0
200
90
64.33
0.75
5.72
23.75
0.00
0
0.60
29
100
1.00
337.500
704.470
2.882
4.875
1404.975
1.178
1053.731
220.768
34.418
Created by EBAA Iron's Restraint Length Calculator v7.1.3 on March 3, 2021