HomeMy WebLinkAboutGUARDIAN SELF STORAGE - PDP190020 - - UTILITY PLANS (6)IS THERE PROPOSED GRADING OVER THE EXISTING SSMH? ADJUST TO GRADE? WHAT IS 100-YR FLOOD ELEVATION IN THIS WETLAND? WOULD OUR LID BE UNDER WATER? IF SO, PROPOSE AN INFLOW SHEILD. PLEASE CALL OUT ALL NEW BENDS,FITTINGS, ETC TO ACCOMPLISH THE PROPOSED RELOCATION. SPECIFY 8" PVC FOR MATERIAL. ALL DEFLECTIONS TO BE MECHANICALLY RESTRAINED. USE EXISTING TEE WITH A BEND TO THE SOUTH? SEE EXISTING SYSTEM IMAGE ABANDON THE LATERAL AT THE MAIN PROPOSE A VALVE DIRECTLY OFF THE WET TAP (WEST OF THE VALVE THE LINE IS CONSIDERED PRIVATE) REPEAT COMMENT: CALL OUT TAPS AND SIZES CALL OUT MIN 2% SLOPE ON SEWER LINE CALL OUT VALVE DIRECTLY WEST OF THE TAP. CALL OUT THE 6" WET TAP. JR Response: Comments will be addressed at time of final per comments from Nate Ensley JR Response: Comments will be addressed at time of final per comments from Nate Ensley JR Response: Comments will be addressed at time of final per comments from Nate Ensley JR Response: Comments will be addressed at time of final per comments from Nate Ensley JR Response: Comments will be addressed at time of final per comments from Nate Ensley JR Response: Comments will be addressed at time of final per comments from Nate Ensley