HomeMy WebLinkAboutOLD TOWN NORTH FIFTH FILING REPLAT OF TRACT F - BDR190016 - SUBMITTAL DOCUMENTS - ROUND 1 - SUPPORTING DOCUMENTATION (3)\\UFP\Utilities\WEFS\WEFS-Ops-Mgr\Templates WEFS\WFO Hydrant Flow Test Form Revision Date: July 17, 2018
Water Field Operations Hydrant Flow Test
DISCLAIMER
The above hydrant flow readings and information (readings) are from a single test performed at an arbitrary point
in time and as such are not and should not be assumed to be representative of typical or any specific water system
conditions. The City of Fort Collins (City) makes no representation of the readings’ accuracy or representativeness.
The City disclaims any and all liability with respect to the readings and any use thereof. The readings are provided
for general information purposes only and are not intended to be used for any other or specific purpose, including
as the basis for the development of construction plans or any type of engineering. The readings are not guaranteed
to be accurate or suitable for any use. Any use of the readings and any conclusions drawn therefrom shall be
strictly the responsibility of the user, and not the City.
Flow Test For: Jerome St & Osiander St.
Date: 8/16/18
Time: 12:58 PM
Flow Test Hydrant: 26106 Mfg. Mueller
Flowed Nozzle Size: 4.5
Flowed at: 64 PSI
Hose Monster Conversion Chart: 2649 GMP
Side Gauge Reading During Flow Test: 73 PSI
Static and Residual Hydrant: 29289 Mfg. Mueller
Static Reading: 105 PSI
Residual Reading During Flow Test: 95 PSI
Notes: This Test was performed last year.
Shannon Elis
Scjellis@msn.com
970-988-3810