HomeMy WebLinkAboutDUTCH BROS - FDP190017 - DOCUMENT MARKUPS - ROUND 2 - DRAINAGE REPORTFINAL DRAINAGE REPORT
Dutch Bros Coffee
Kensington Commons
Prepared for:
M Squared, LLC
7303 S. Timberline Road
Fort Collins, CO 80525
Prepared by:
Interwest Consulting Group
1218 West Ash, Suite A
Windsor, Colorado 80550
(970) 674-3300
August 21, 2019
Job Number 1380-165-00
1218 W. ASH, STE. A, WINDSOR, COLORADO 80550
TEL. 970.674.3300 – FAX 970.674.3303
August 21, 2019
Mr. Matt Simpson
City of Fort Collins Stormwater
700 Wood Street
Fort Collins, CO 80522-0580
RE: Final Drainage for Dutch Bros Coffee – Kensington Commons
Dear Matt,
I am pleased to submit for your review and approval, this Final Drainage Report for the Dutch
Bros Coffee development. I certify that this report for the drainage design was prepared in
accordance with the criteria in the Fort Collins Stormwater Criteria Manual.
I appreciate your time and consideration in reviewing this submittal. Please call if you have any
questions.
Sincerely,
Michael Oberlander, P.E., LEED AP
Colorado Professional
Engineer No. 34288
7
Basin D is 0.05 acres and is located on the east side of the property. The basin maintains
existing conditions and sheets to the curb and gutter of South College Avenue.
The water quality capture volume for the site was sized based on a 12-hour drain time and
is 775 cf. Please refer to Appendix D for water quality information.
The allowable detention release rate is 0.4 cfs; therefore, the required 100-year storage
volume for the site is 6,261 cf. The Stormtec system will provide 6,499 cf of total
storage. The total is reduced by 460 cf of volume in the bottom 12 inches of isolator row
used for water quality. Therefore, the system provides a 6,039 cf of detention storage.
There will be some parking lot detention that will pond to an elevation of 5036.2 with a
volume of 110 cf. Therefore, the total volume provided for detention is 6,149 cf.
Detained flow will be released via a restrictor plate into the existing inlet and existing
storm system in College Avenue and ultimately to the Mail Creek and then the Fossil
Creek channel. A 10-foot wide emergency overflow spillway is located in the southeast
portion of the site. Please refer to Appendix E for detention information.
The underground storage system will contain a structure with a design bypass to split
flows for treatment and detention. Water quality will be achieved in an isolator row. A
second outlet pipe 12 inches above the invert of the isolator row will convey larger storms
to the system. The remainder will be detained in the chambers and aggregate volume
surrounding and under the chambers. The system proposed for treatment and detention is
the Stormtech MC3500 Chamber System and will be located within the Blanket Utility,
Drainage and Access Easement. Inspection ports will be provided for inspection and
maintenance. Please refer to Appendix E for underground storage information.
5. CONCLUSIONS
5.1 Compliance with Standards
All computations that have been completed within this report are in compliance with the
City of Fort Collins Storm Drainage Design Criteria Manual. A separate Erosion Control
Report and Plan have been submitted to the City of Fort Collins.
Interwest Consulting Group
1218 W. Ash, Suite C
Windsor, CO 80550
Inlet Flow Calculation for Nyloplast 2'x3' Road and Highway Grate
Project: Dutch Bros Kensington
Job Number : 1339-178-00
Calculations by : es
Date : 7/23/2019
Objective: to find the number of grates required for area inlets in grassy areas
Geometry at inlet :
Square Feet Open (A): 2.6813 sf
Reduction Factor (F): 50%
Grate Flow:
Use the orifice equation Qi = C*A*SQRT(2*g*H) to find the ideal inlet capacity.*
*See Hydraulic Design Handbook by McGraw-Hill for verificaiton of equation use and C value
C = Orifice discharge coefficient= 0.67
A = Orifice area (ft2) - open area of grate
g = gravitational constant = 32.2 ft/s2
H = head on grate centroid, ponding depth (feet)
Then multiply by the reduction factor for the allowable capacity.
QG = Qi * (1-F)
DP a DP b
Q = 1.8 cfs Q100 Q = 4.9 cfs Q100
H = 0.35 ft H = 0.5 ft
A= 2.68 ft2 A= 2.68 ft2
Qi = C*A*SQRT(2*g*H) Qi = C*A*SQRT(2*g*H)
= 8.53 cfs = 10.19 cfs
QG = Qi * F QG = Qi * F
= 4.26 cfs OK = 5.10 cfs OK
Grate Open Area and information:
WSEL
Page1
LOCATION: Dutch Bros. Kensington
PROJECT NO: 1380-165-00
COMPUTATIONS BY: es
DATE: 7/10/2019
A B C D E F G H I J K
WQCV (12
Hr.)
WQ Flow
(1/2 Q2)
Chamber
Type
Single
Chamber
Release Rate
Through
Fabric*
Volume in
bottom 12"
of one
Chamber
Min
Chambers
for WQ Flow
Through
Fabric
Chambers
Provided
Actual
Release Rate
Thru Fabric
Required
Storage
Volume by
FAA Method
with Qin=B
and Q out=H
Min Number
of Chambers
(Bottom 12")
for FAA
Release
Volume in
Bottom 12"
of Isolator
Rows to be
Removed
from
Detention
Volume
cf cfs cfs cf (B/D) (G*D) cfs CF (I/E) (G*E)
775 0.7 MC3500 0.036 46 19 10 0.36 152 3 460
* - Single Chamber = 77"x86" = 46 SF FABRIC
Fabric Release @ 0.35 gal/min/SF = 16 gal/min/chamber
16 gal/min = 0.036 cfs
Isolator Row Volume Check
00 10' 20'
SHEET
OF
DATE:
PROJECT #:
DRAWN:
CHECKED:
THIS DRAWING HAS BEEN PREPARED BASED ON INFORMATION PROVIDED TO ADS UNDER THE DIRECTION OF THE SITE DESIGN ENGINEER OR OTHER PROJECT REPRESENTATIVE. THE SITE DESIGN ENGINEER SHALL REVIEW
THIS DRAWING PRIOR TO CONSTRUCTION. IT IS THE ULTIMATE
RESPONSIBILITY OF THE SITE DESIGN ENGINEER TO ENSURE THAT THE PRODUCT(S) DEPICTED AND ALL ASSOCIATED DETAILS MEET ALL APPLICABLE LAWS, REGULATIONS, AND PROJECT REQUIREMENTS.
4640 TRUEMAN BLVD
HILLIARD, OH 43026
ADVANCED DRAINAGE SYSTEMS, INC.
R
2 6
08/06/19
S145040
SDM
AMD
FORT COLLINS, CO
DUTCH BROS
DATE DRWN CHKD DESCRIPTION
08/13/19 SDM DAF REVISED PER ENGINEER'S MARK UPS
PLACE MINIMUM 17.5' OF ADS GEOSYNTHETICS 315WTM WOVEN
GEOTEXTILE OVER BEDDING STONE AND UNDERNEATH CHAMBER
FEET FOR SCOUR PROTECTION AT ALL CHAMBER INLET ROWS
24" CORED END CAP, PART# MC3500IEPP24BC OR MC3500IEPP24BW
TYP OF ALL MC-3500 24" BOTTOM CONNECTIONS AND ISOLATOR ROWS
PROPOSED LAYOUT
29 STORMTECH MC-3500 CHAMBERS
8 STORMTECH MC-3500 END CAPS
12 STONE ABOVE (in)
15 STONE BELOW (in)
40 % STONE VOID
6,499 INSTALLED SYSTEM VOLUME (CF) (PERIMETER STONE INCLUDED)
1,881 SYSTEM AREA (ft²)
210 SYSTEM PERIMETER (ft)
PROPOSED ELEVATIONS
5041.80 MAXIMUM ALLOWABLE GRADE (TOP OF PAVEMENT/UNPAVED)
5035.80 MINIMUM ALLOWABLE GRADE (UNPAVED WITH TRAFFIC)
5035.30 MINIMUM ALLOWABLE GRADE (UNPAVED NO TRAFFIC)
5035.30 MINIMUM ALLOWABLE GRADE (BASE OF FLEXIBLE PAVEMENT)
5035.30 MINIMUM ALLOWABLE GRADE (TOP OF RIGID PAVEMENT)
5034.80 TOP OF STONE
5033.80 TOP OF MC-3500 CHAMBER
5031.05 15" MANIFOLD INVERT
5030.22 24" ISOLATOR ROW CONNECTION INVERT
5030.18 15" BOTTOM MANIFOLD INVERT
5030.05 BOTTOM OF MC-3500 CHAMBER
5028.80 UNDERDRAIN INVERT
5028.80 BOTTOM OF STONE
NOTES
· MANIFOLD SIZE TO BE DETERMINED BY SITE DESIGN ENGINEER. SEE TECH SHEET #7 FOR MANIFOLD SIZING GUIDANCE.
· DUE TO THE ADAPTATION OF THIS CHAMBER SYSTEM TO SPECIFIC SITE AND DESIGN CONSTRAINTS, IT MAY BE
NECESSARY TO CUT AND COUPLE ADDITIONAL PIPE TO STANDARD MANIFOLD COMPONENTS IN THE FIELD.
· THE SITE DESIGN ENGINEER MUST REVIEW ELEVATIONS AND IF NECESSARY ADJUST GRADING TO ENSURE THE CHAMBER
COVER REQUIREMENTS ARE MET.
· THIS CHAMBER SYSTEM WAS DESIGNED WITHOUT SITE-SPECIFIC INFORMATION ON SOIL CONDITIONS OR BEARING
CAPACITY. THE SITE DESIGN ENGINEER IS RESPONSIBLE FOR DETERMINING THE SUITABILITY OF THE SOIL AND
PROVIDING THE BEARING CAPACITY OF THE INSITU SOILS. THE BASE STONE DEPTH MAY BE INCREASED OR DECREASED
ONCE THIS INFORMATION IS PROVIDED.
· THE SITE DESIGN ENGINEER MUST REVIEW THE PROXIMITY OF THE CHAMBERS TO THE BUILDING/STRUCTURE. NO
FOUNDATION LOADS SHALL BE TRANSMITTED TO THE CHAMBERS. THE SITE DESIGN ENGINEER MUST CONSIDER EFFECTS
OF POSSIBLE SATURATED SOILS ON BEARING CAPACITY OF SOILS AND SEEPAGE INTO BASEMENTS.
15" X 15" ADS N-12 CUSTOM INVERT MANIFOLD
INVERT 12.00" ABOVE CHAMBER BASE
(SEE NOTES)
6" ADS N-12 DUAL WALL PERFORATED HDPE UNDERDRAIN
(SIZE TBD BY ENGINEER)
INSPECTION PORT (TYP 2 PLACES)
ISOLATOR ROW
(SEE DETAIL / TYP 2PLACES)
15" X 15" ADS N-12 BOTTOM MANIFOLD
MAXIMUM OUTLET FLOW 2.7 CFS
INVERT 1.5" ABOVE CHAMBER BASE
(SEE NOTES)
STRUCTURE PER PLAN W/ELEVATED BYPASS MANIFOLD
SHOWN AS 36" NYLOPLAST
MAXIMUM INLET FLOW 3.5 CFS
(24" SUMP MIN)
70 NIWOOD ROAD, SUTIE 3 | ROCKY HLIL | CT | 06067
860-529-8188 |888-892-2694 | WWW.STORMTECH.COM
Detention Retention Water Quality
20.25'
22.85'
39.60' 32.44'
75.44'
81.95'
CUSTOM CORED END CAP
15" INVERT 12.00" ABOVE CHAMBER BASE