HomeMy WebLinkAboutDUTCH BROS - FDP190017 - SUBMITTAL DOCUMENTS - ROUND 1 - RESPONSE TO STAFF REVIEW COMMENTS1 Community Development and Neighborhood Services 281 North College Avenue PO Box 580 Fort Collins, CO 80522 970.221.6689 970.224.6134 - fax fcgov.com/developmentreview July 19, 2019 Cathy Mathis TB Group 444 Mountain Ave Berthoud, CO 80513 RE: Dutch Bros, PDP190008, Round Number 2 Please see the following summary of comments from City staff and outside reviewing agencies for your submittal of the above referenced project. If you have questions about any comments, please contact your Development Review Coordinator Brandy Bethurem Harras at 970.416.2744 or bbethuremharras@fcgov.com. Comment Summary: Department: Planning Services Contact: Pete Wray, 970-221-6754, pwray@fcgov.com Topic: General Comment Number: FOR HEARING: Ready for hearing. Department: Engineering Development Review Contact: Morgan Uhlman, 970-416-4344, muhlman@fcgov.com Topic: General Comment Number: 5 07/15/2019: FOR HEARING: The trash enclosure should be excluded from the blanket utility, drainage and access easement. RESPONSE: Trash enclosure is now excluded from the blanket utility, drainage and access easement. Comment Number: 6 07/17/2019: FOR HEARING: If there are going to be stairs to reach the patio area of Dutch Bros off of Kensington or College please make sure that the stairs are set back a minimum of 2' from the sidewalk. RESPONSE: Noted on the Horizontal Control and Grading Plans. 2 Comment Number: 7 07/17/2019: FOR FINAL PLAN: Please coordinate with Engineering and Traffic on the location of the push button for the College and Kensington intersection with the widening of the curb ramp. RESPONSE: It appears the proximity will be improved. Department: Water-Wastewater Engineering Contact: Matt Simpson, (970)416-2754, masimpson@fcgov.com Topic: General Comment Number: 5 07/12/2019: FOR FINAL PLAN: Please see the annotated Utility Plan and Landscape Plan PDFs for additional comments.07/16/2019: RESPONSE: Comments noted and addressed. Comment Number: 6 07/19/2019: Approved for Hearing Department: Stormwater Engineering Contact: Jesse Schlam, 970-218-2932, jschlam@fcgov.com Topic: Erosion Control Comment Number: 1 05/01/2019: FOR FINAL PLAN: Please submit an Erosion Control Plans to meet City Criteria. RESPONSE: Comment noted. Comment Number: 2 05/01/2019: FOR FINAL PLAN: Please resubmit an Erosion Control Report to meet City Criteria. RESPONSE: Project area of disturbance is between 10,000 – 43,559 sf; therefore, only an Erosion Control Plan and Escrow are required. Comment Number: 3 05/01/2019: DEVELOPMENT AGREEMENT: Please submit an Erosion Control Escrow / Security Calculation based upon the accepted Erosion Control Plans to meet City Criteria. RESPONSE: Comment noted. Contact: Matt Simpson, (970)416-2754, masimpson@fcgov.com Topic: General Comment Number: 7 07/12/2019: FOR FINAL APPROVAL: Same comment as below, for Final Approval not for Final Plans. 05/08/2019: FOR FINAL PLAN: Due to the subdivision of the parcel there will be joint stormwater facilities, a maintenance agreement will need to be filed with the County. This will need to detail the ownership, maintenance, and cost sharing of these joint facilities. RESPONSE: The agreement will be prepared. Comment Number: 11 3 05/08/2019: FOR FINAL PLAN: Please provide detail of the detention orifice plate and configuration of the outlet structure. RESPONSE: Comments noted. Comment Number: 17 07/12/2019: FOR FINAL PLAN: In the drainage report, the Rational FAA calculation for the proposed detention storage has a potential error in the "Vol. Out Vo" Column. I calculate lower values when I checked this. This would result in slightly higher storage requirements. Please double check the coding of your calculation spreadsheet for this column. See annotated Drainage Report pdf for more information. RESPONSE: Reconciled. Comment Number: 18 07/12/2019: FOR FINAL PLAN: Please see the annotated Utility Plan and Landscape Plan PDFs for additional comments. RESPONSE: Redlines addressed. Responses on PDFs. Comment Number: 20 07/19/2019: Approved for hearing Department: Environmental Planning Contact: Stephanie Blochowiak, 970-416-4290, sblochowiak@fcgov.com Topic: General Comment Number: 4 07/16/2019: READY FOR HEARING. Department: Forestry Contact: Molly Roche, 224-616-1992, mroche@fcgov.com Topic: General Comment Number: 16 7/16/2019: FOR FINAL PLAN: Please provide at least 15 ft between ornamental trees in the drive-thru median. RESPONSE: The trees were actually moved to avoid conflicts with the water services. There is at least 25’ between the trees. Comment Number: 17 7/16/2019: FOR FINAL PLAN: Please include the Street Tree Permit Note on sheet L-1 of the Landscape Plans. RESPONSE: Permit Note has been added to L-1. Comment Number: 18 7/16/2019: INFORMATION ONLY: Forestry redlines are provided on both the Site Plan Set and the Utility Plans. RESPONSE: Response to Redlined Plan: 1. As discussed, the trees in the drive thru median have been relocated. 2. The street tree on Kensington that was too close to the street light has been switched to a crabapple. 3. As discussed in our staff review meeting, the existing green ash tree along College will be shown as removed. 4. For the trees to remain along Kensington, dimensions have been added from the trunks to the 4 critical root zones. Topic: Landscape Plans Comment Number: 12 7/16/2019: FOR FINAL APPROVAL – UNRESOLVED: Thank you for updating the tree symbol for tree #11 on sheet L-3. However, on sheet L-1 this tree is shown as EXISTING TREE TO REMAIN. Since this tree is to be removed, please remove the tree symbol from this sheet. In addition, this same tree is shown to remain on the utility plans sheet 2. Please place an X over the symbol. This tree’s symbol should also be removed from sheet 3 of the utility plans. RESPONSE: The tree is being removed and the tree symbol has been grayed out on Sheet L-1. On Sheet L-3, there is now an ‘X’ placed over the tree. The tree symbol has also been corrected on the civil sheets. 05/13/2019: FOR HEARING: Tree #11 is shown to be removed in the Tree Inventory and Mitigation table, but does not have the correct symbol on sheet L-3. RESPONSE: An ‘X’ is now over the tree. Comment Number: 15 7/16/2019: FOR FINAL PLAN: The Sterling Silver Linden tree that is proposed along Kensington Drive is less than 40 ft from the existing streetlight. Since there isn’t adequate room to fit a canopy shade tree in this location, please change this tree to an upsized (mitigation) ornamental tree such as Hot Wings Maple. Update Plant List as needed. RESPONSE: The tree has been replaced with a Coralburst Crabapple. Department: Environmental Services Contact: Jonathon Nagel, 970-416-2701, jnagel@fcgov.com Topic: General Comment Number: 4 05/14/2019: FOR FINAL PLAN - UPDATED: All trash and recycling enclosures and staging areas are required to provide methods to protect the interior walls from being damaged. Please provide protections on the east and west walls adjacent to the containers. RESPONSE: Protection has been added to all sides of the trash enclosure Comment Number: 5 05/14/2019: FOR FINAL PLAN - UPDATED: The site plan and plan enlargement of the for the trash and recycling enclosure do not match (one shows two sets of service gates and no pedestrian, the other shows one set of service gates and a rear pedestrian). Please update one or the other so they match. RESPONSE: plans have been updated to show the same enclosure plan. Comment Number: 10 07/16/2019: FOR FINAL PLAN: Please update the trash and recycling enclosure elevations to reflect the door less pedestrian entrance shown on the plan enlargement. RESPONSE: Elevations have been updated to show no pedestrian gate to enclosure. Department: Light And Power 5 Contact: Austin Kreager, 970-224-6152, akreager@fcgov.com Topic: General Comment Number: 2 05/14/2019: INFORMATION ONLY: The relocation of the existing electric lines to accommodate the building envelope will be done at the expense of the applicant. This will require a lengthy outage for the Jiffy Lube, and could incur overtime costs if needed to be performed at night. Comment Number: 4 07/16/2019: FOR FINAL: Thank you for providing a preliminary C-1 form. I look forward to receiving the one-line diagram at final plan. RESPONSE: A One-line diagram is included. 05/14/2019: FOR FINAL PLAN: Please provide a one-line diagram and a C-1 form to Light and Power Engineering. The C-1 form can be found at: http://zeus.fcgov.com/utils-procedures/files/EngWiki/WikiPdfs/C/C-1Form.pdf Comment Number: 5 05/14/2019: INFORMATION ONLY: Development charges, electric Capacity Fee, Building Site charges and any system modification charges necessary will apply to this development. Comment Number: 6 05/14/2019: INFORMATION ONLY: You may contact Austin Kreager, project engineering if you have questions. (970) 224-6152. You may reference Light & Power’s Electric Service Standards at http://www.fcgov.com/utilities/img/site_specific/uploads/ElectricServiceStandar ds_FINAL_18November2016_Amendment.pdf You may reference our policies, development charge processes, and use our fee estimator at http://www.fcgov.com/utilities/business/builders-and-developers. Comment Number: 7 07/16/2019: INFORMATION ONLY: Thank you for meeting with us to discuss the concerns surrounding the utilities on site. As long as the stormwater department is okay with our line being located so near to their facilities, then we have no objections to this plan. Department: PFA Contact: Andrew Rosen, 970-416-2599, arosen@poudre-fire.org Topic: General Comment Number: 1 07/15/2019: INFORMATION ONLY: The new hydrant location is approved. Thank you. No further action required for hydrants. Comment Number: 2 07/15/2019: INFORMATION ONLY: The Fire Lane location and extent has recently been approved by PFA at an off-line meeting. 6 Comment Number: 3 05/07/2019: INFORMATION ONLY: ADDRESS - The address shall be clearly visible from the street in no less than 8" tall numerals on a contrasting background. - To assist with prompt emergency response, the full address including street name will be visible on the elevation facing College Avenue. Comment Number: 4 07/17/2019: BUILDING PERMIT: When you submit for your building permit though the City of Fort Collins please be advised Poudre Fire Authority is an additional and separate submittal. The link for Poudre Fire Authority’s plan review application can be found at https://www.poudre-fire.org/online-services/ contractors-plan-reviews-and-permits/new-building-plan-review-application. Department: Building Services Contact: Katy Hand, khand@fcgov.com Topic: Building Insp Plan Review Comment Number: 1 05/13/2019: BUILDING PERMIT: We have adopted the 2018 I-Codes. Please see our website for adopted codes and local amendments. https://www.fcgov.com/building/codes.php Department: Water Conservation Contact: Eric Olson, 970-221-6704, eolson@fcgov.com Topic: General Comment Number: 1 04/29/2019: BUILDING PERMIT: Irrigation plans are required no later than at the time of building permit. The irrigation plans must comply with the provisions outlined in Section 3.2.1(J) of the Land Use Code. Direct questions concerning irrigation requirements to Eric Olson, at 221-6704 or eolson@fcgov.com Department: Technical Services Contact: Jeff County, 970-221-6588, jcounty@fcgov.com Topic: General Comment Number: 2 07/17/2019: FOR INFORMATION: Unless required during PDP, a complete review of all plans will be done at FDP. RESPONSE: Acknowledged. Thank you. Topic: Plat Comment Number: 1 07/17/2019: FOR FINAL APPROVAL: Please make changes as marked. If changes are not made or you disagree with comments, please provide written response of why corrections were not made. Please provide any responses on redlined sheets and/or in response letter.