RE: 622 W Laurel, BDR180040, Round Number 2
Please see the following summary of comments from City staff and outside reviewing
agencies for your submittal of the above referenced project. If you have questions about
any comments, you may contact the individual commenter or direct your questions through
the Development Review Coordinator, Tenae Beane, at 970-224-6119 or tbeane@fcgov.com.
Comment Summary:
Department: Planning Services
Contact: Clay Frickey, 970-224-6045, cfrickey@fcgov.com
Topic: General
Comment Number: 6 Comment Originated: 04/01/2019
04/01/2019: For approval:
Thank you for adding information about the parking required on the site plan.
We need the table to look a little bit different than shown. The table should
indicate the number of bedrooms in each unit, the minimum parking required
per the Land Use Code, and the amount of parking you're providing for each
unit. The revised parking table (Site Data Summary) has been added to the Site Plan.
Department: Engineering Development Review
Contact: Morgan Uhlman, 970-416-4344, muhlman@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 01/14/2019
01/14/2019 For Approval:
Laurel Street is identified as a 4-lane arterial on the Master Street Plan, this
requires a 15' utility easement behind the right-of-way. Please work with me and
technical services on dedicating that easement by separate document. For
more information on the process of the easement dedication process the link
2
following will have more information:
https://www.fcgov.com/engineering/devrev.php
Included in this resubmittal is the requested utility easement legal description.
Comment Number: 3 Comment Originated: 03/25/2019
03/25/2019: For Approval:
Please place the following note on your site plan: "Damaged curb, gutter and
sidewalk existing prior to construction, as well as existing fences, trees, streets,
sidewalks, curbs and gutters, landscaping, structures, and improvements
destroyed, damaged or removed due to construction of this project, shall be
replaced or restored in like kind at the developer’s expense, unless otherwise
indicated on these plans, prior to the acceptance of completed improvements
and/or prior to the issuance of the first Certificate of Occupancy. "
This note has been added to the Site Plan.
Department: PFA
Contact: Andrew Rosen, 970-416-2599, arosen@poudre-fire.org
Topic: General
Comment Number: 4 Comment Originated: 01/09/2019
01/09/2019: FOR NEXT ROUND
RESIDENTIAL FIRE SPRINKLER SYSTEM
Duplex residences require an approved residential fire sprinkler system or an
approved method of fire separation.
Per the email to Josh Horner on 4/11/19 PRA it stated that “sprinklers
will not be required, but there will need to be a 1 hour fire separation between the units”.
A note has been added to the Site Plan that states “the project shall comply with the requirement for a 1
hour fire separation between the units.” Also noted in your email to Josh Horner it stated “it was
determined that an Emergency Access Easement will not be required”.
Please contact the Building department for information regarding P2904
systems.
Please contact Assistant Fire Marshal, Jerry Howell with NFPA 13D questions
at 970-416-2868.
Comment Number: 6 Comment Originated: 01/09/2019
01/09/2019: FOR APPROVAL
HYDRANT
A fire hydrant is required within 400' of the building as measured along an
approved path of vehicle travel. The hydrant at the NW corner of Laurel and
Loomis meets this distance requirement however it is the applicant's
responsibility to verify the flow. Please contact the water department for
information.
We have requested a flow test for the above mentioned fire hydrant from Jim Carder in Utilities.
It is scheduled for the week on May 6th and we will forward the results as soon as they are available.
Department: Light And Power
Contact: Luke Unruh, 9704162724, lunruh@fcgov.com
Topic: General
Comment Number: 2 Comment Originated: 01/14/2019
01/14/2019: The current service to the existing single family is only capable of
3
handling 150 amps without an upgrade charge and a new service conductor
installed.
The existing 150 amp service is currently sized to handle all loads for both units. We do not believe an
upgrade is needed but actual loads will be determined at the time of building renovation by a licensed
electrican.
Comment Number: 1 Comment Originated: 01/14/2019
01/14/2019: The new dwelling must be metered separately from the existing
dwelling. There are currently two separate meters on the building, one servicing the main floor (existing
dwelling) and the other servicing the lower level (new dwelling).
Comment Number: 3 Comment Originated: 01/14/2019
01/14/2019: Please contact Luke Unruh at 970-416-2724 to discuss power
requirements so I can provide an estimate if needed.
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcounty@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 01/14/2019
04/03/2019: FOR APPROVAL:
We have no comments, but will need to see any future submittals.
01/14/2019: FOR APPROVAL:
We have no comments, but will need to see any future submittals.
Department: Traffic Operation
Contact: Martina Wilkinson, 970-221-6887, mwilkinson@fcgov.com
Topic: General
Comment Number: 2 Comment Originated: 04/01/2019
04/01/2019: No new comments from Traffic Operations as long as they are not
proposing any changes to the driveway access onto Laurel.
No new driveway access onto Laurel is requested.
Department: Environmental Planning
Contact: Stephanie Blochowiak, 970-416-4290, sblochowiak@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 04/01/2019
04/01/2019: No comments. Thank you.