January 11, 2019
Tom Johnson
31878 Del Obispo St # 118-454
San Juan Capistrano, CA 92675
RE: Summit View Church - WTF, PDP180016, Round Number 1
Please see the following summary of comments from City staff and outside reviewing
agencies for your submittal of Summit View Church, WTF. If you have questions about
any comments, you may contact the individual commenter or direct your questions through
your Development Review Coordinator, Brandy Bethurem Harras, at 970.416.2744 or bbethuremharras@fcgov.com.
UComment Summary:
Department: Planning Services
Contact: Kai Kleer, 970-416-4284, Ukkleer@fcgov.com
Topic: General
Comment Number: 1
12/27/2018 BEFORE HEARING: Please include a landscape plan that
includes landscaping around the base of the enclosure. Landscape plan should
include plant material on the east west and south side of the structure.
Landscaping bed should be a minimum of 7-9 feet wide and contain a
combination of shrubs both coniferous and deciduous. The plan should also
indicate the installation of four trees that are missing from the two landscape
islands on the east portion of the site.
Response: See attached Sheet ZD1.3 for the landscape plan.
See section 3.2.1 and 3.8.13(C)(4) for reference information.
Comment Number: 2
12/27/2018 BEFORE HEARING:
Please include detailed drawings of branch density and tree bark. Include on
sheet ZD-3.1. We are looking for the following:
Antenna socks that help camouflage the antennas with tufts of evergreen material.
2
Tower to have simulated bark finish, painted brown.
Branch density of 3 branches per foot
Response: Please see notations on elevation sheets that delineate the items noted above.
Comment Number: 3
12/27/2018 BEFORE HEARING:
Because this proposal does not meet the 1:1 setback requirements of
3.8.13(C)(1) either provide a demonstration that the structure will collapse rather
than topple or provide justification that addressed the following:
Response: Please see attached letter as requested.
the plan as submitted will not diverge from the standards of the Land Use Code
that are authorized by this Division to be modified except in a nominal,
inconsequential way when considered from the perspective of the entire
development plan, and will continue to advance the purposes of the Land Use
Code as contained in Section 1.2.2.
Comment Number: 4
12/27/2018 BEFORE HEARING:
Please include photosimulations after the title sheet of the plan set.
Response: Please see attached revised plans with Simulations included.
Comment Number: 5
12/27/2018 BEFORE HEARING:
Sheet SV-1 indicates 'slimline pole lease area', please correct.
Response: This has been corrected, see attached.
Department: Light And Power
Contact: Austin Kreager, 970-224-6152, Uakreager@fcgov.com
Topic: General
Comment Number: 1
01/08/2019: INFORMATION ONLY:
There is a small single phase transformer near the entrance to the parking lot.
Depending on your power requirements, you can either come to that
transformer or we will need to do significant system modifications to service this
new structure with power. We look forward to working out these issues with you.
Response: Please see attached utility plan included within the ZD’s.
Comment Number: 2
01/08/2019: FOR HEARING:
Your site plan has a callout naming two pieces of equipment transformers. They
are indeed our facilities, but they are switch cabinets, not transformers. They will
not be useful to your project. Please correct this note for the next round.
3
Response: This has been removed.
Comment Number: 3
01/08/2019: FOR HEARING:
Once it is determined where your power source will be located, we will need all
of our facilities to be located in a utility easement. If a new transformer is
installed, 100% of our primary line as well as our transformer will need to be in
an easement. If you go to the existing transformer, all of that primary line and
transformer will need to be in an easement.
Response: See attached utility design included with the ZD’s.
Comment Number: 4
01/08/2019: FOR FINAL:
Please provide a one line diagram and a C-1 form to Light and Power
Engineering. The C-1 form can be found at:
http://zeus.fcgov.com/utils-procedures/files/EngWiki/WikiPdfs/C/C-1Form.pdf
Response: see attached revised plans with one-line diagram included.
Comment Number: 5
01/08/2019: INFORMATION ONLY:
Transformer locations shall be within 10' of a paved surface and must have a
minimum of an 8' clearance from the front side and a 3' clearance around the
sides and rear. (1000 kVA up to 2500 kVA requires 4' around the sides and rear.)
Comment Number: 6
01/08/2019: INFORMATION ONLY:
Electric Capacity Fee, Building Site charges and any system modification
charges necessary will apply to this development.
Comment Number: 7
01/08/2019: INFORMATION ONLY:
You may contact FCU Light & Power, project engineering if you have questions.
(970) 221-6700. You may reference Light & Power’s Electric Service Standards at
http://www.fcgov.com/utilities/img/site_specific/uploads/ElectricServiceStandar
ds_FINAL_18November2016_Amendment.pdf
You may reference our policies, development charge processes, and use our fee estimator at
http://www.fcgov.com/utilities/business/builders-and-developers.
Department: Stormwater Engineering
Contact: Dan Mogen, 970-305-5989, Udmogen@fcgov.com
Topic: General
Comment Number: 1
12/27/2018: The proposed site changes shown in this submittal are not
substantial enough to trigger Stormwater detention and water quality
requirements; however, a grading plan is required. Please show proposed
4
grading for the project area or include a note stating the final grading will
maintain existing drainage patterns.
If future submittals include site changes that are not shown on these plans,
please contact Dan Mogen at (970)305-5989 or dmogen@fcgov.com to
coordinate and determine what requirements, if any, will apply.
Response: There is no grading required for this project.
Department: Engineering Development Review
Contact: Katie Andrews, 970-221-6501, Ukandrews@fcgov.com
Topic: General
Comment Number: 1
01/04/2019: BY HEARING:
Larimer County Urban Area Street Standards (Appendix E-4) require that most
public improvements, including handicap ramps, be shown on the plans at time
of Project Development Plan, prior to public hearing. Please indicate on the site
plan that the ramps will be updated - construction level detail can be submitted
with Final Development Plan documents post hearing.
Response: Please see attached revised plans with notations on ZD-1.0
Department: PFA
Contact: Andrew Rosen, 970-416-2599, Uarosen@poudre-fire.org
Topic: General
Comment Number: 1
12/31/2018: INFORMATION ONLY:
2018 IFC CODE ADOPTION: Poudre Fire Authority and the City of Fort Collins (Town of Timnath, Larimer
County) are in the process of adopting the 2018 International Fire Code. Code
adoption is anticipated in early 2019. Building plan reviews shall be subject to
the adopted version of the fire code in place at the time of plan review submittal
and permit application.
Comment Number: 2
12/31/2018: FOR HEARING:
ACCESS:
>Access is required to within 150ft of all portions of the exterior perimeter of the
structure. This cannot be measured from Drake Avenue because it is classified
as an arterial street therefore a Fire Lane will be established in the drive aisle of
the parking area closest to Drake Avenue to provide this access. It can extend
from the main entrance from Drake Rd, along the south drive aisle and exit onto
Drake Rd at the west end of the parking lot.
>This Fire Lane shall be shown on the Plat as an Emergency Access Easement
or dedicated by separate legal document.
Response: Please see attached revised plans with those notations addressed.
5
Comment Number: 3
12/31/2018: FOR FINAL:
To assist with prompt emergency response the address should be clearly
visible from the street on the new facility.
Comment Number: 4
12/31/2018: INFORMATION ONLY:
GATING: A Master brand padlock is shown on the plans for the facility gate which is
appropriate for this location. Should the Applicant require greater security, then
an approved Knox brand padlock should be used.
Department: Environmental Planning
Contact: Kelly Smith, Uksmith@fcgov.com
Topic: General
Comment Number: 1
01/07/2019: INFORMATION ONLY:
This comment reflects the requirement found within the ECS memo to conduct a raptor survey along
Spring Creek if construction is to occur
any time during the nesting season (February 15 through July 15). If construction
is scheduled to coincide with the nesting season, the survey should be
conducted two weeks prior to the start date of the project. The primary concern
for the timing of development is protection of nesting birds adjacent to the
Property. If construction does not coincide with the nesting season, a raptor
survey is unnecessary.
Department: Forestry
Contact: Molly Roche, 224-616-1992, Umroche@fcgov.com
Topic: Landscape Plans
Comment Number: 1
01/10/2019: BEFORE HEARING:
City Forestry visited the site on 1/9/19 to obtain existing tree inventory and
mitigation information (see attached). We are having a hard time picturing the
monopine fitting in this tight space between the two Ash trees without some
potentially extensive pruning done to both trees. We would like the applicant to
consult a local, licensed, and certified arborist to evaluate if the two Ash trees
can be sufficiently pruned in order to accommodate the monopine structure and
installation. Another point to consider is that this species is susceptible to the
invasive pest, Emerald Ash Borer (EAB). Although EAB has not yet been
detected in Fort Collins, the threat is imminent and all Fraxinus species will
quickly die if left untreated. Has the property owner expressed interest in
treating these trees for EAB (which would be every 2-3 years for the life of the tree)?
- If the arborist is confident that pruning can be achieved while protecting the
health of the trees and if the property owner plans to treat these trees for
Emerald Ash Borer, then City Forestry will support these recommendations.
Please provide a written evaluation from the arborist to the Project Planner, Kai
6
Kleer, and City Forestry Specialist, Molly Roche for review.
- If the arborist does not recommend pruning and EAB treatment on these
trees, please provide a written evaluation from the arborist to the Project
Planner, Kai Kleer, and City Forestry Specialist, Molly Roche for review.
Removal of these two trees qualifies for a total of 3 mitigation trees to be
planted back on-site and in the same location to provide screening around the
monopine. The mitigation trees shall be evergreen trees upsized to 8 ft height.
The following species are acceptable: Southwestern White Pine, White
Spruce/Black Hills Spruce, or Ponderosa Pine.
Response: Please see the attached from the Arborist with suggestions on options. Further direction from
City staff will be pending.
01/08/2019: BEFORE HEARING:
An on-site meeting occurred on 10/26/2017 with project planner Kai Kleer. At
this time, the location of the wireless device was in a different location. On this
proposal, the wireless device is proposed between two existing trees. Please
schedule an on-site visit with City Forestry to obtain existing tree inventory and
mitigation information for the trees in close proximity to the wireless device. This
meeting should occur prior to next submittal. Tree inventory and mitigation
information should be displayed in a table on the landscape plan. All existing
trees should be labeled as “EXISTING TREE TO REMAIN AND BE
PROTECTED”. In addition, please include the City of Fort Collins Tree
Protection Notes to the landscape plan, which are available from City Forestry
(Molly Roche, 30TUmroche@fcgov.comU30T).
Comment Number: 2
01/08/2019: BEFORE HEARING:
There are two existing landscape islands that used to be landscaped but no
longer have trees. As a part of this submittal, these landscape island will need
to be re-landscaped with canopy shade trees. Currently, Lindens are shown in
most of the parking lot islands, but this species does not typically survive or
thrive well in this type of environment. Please show a total of (4) Kentucky
Coffeetrees 'Espresso' in the 2 islands identified on the redlines (east portion of
the site). Please verify that these trees will receive irrigation. Provide a plant list
on the landscape plans that details species, quantity, caliper size (2 inch balled and burlapped).
Response: These trees have been added to the plans ZD-1.2
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcounty@fcgov.com
Topic: General
Comment Number: 1
01/07/2019: FOR FINAL:
All plan sheets must be 24"x36".
Comment Number: 2
01/07/2019: FOR FINAL:
7
Please revise the legal description as marked. See redlines.
Comment Number: 3
01/07/2019: FOR FINAL:
There are line over text issues. See redlines.
Response: These have been adjusted.