HomeMy WebLinkAboutVOA SENIOR HOUSING - PDP190005 - SUBMITTAL DOCUMENTS - ROUND 2 - ACCESS, UTILITY, DRAINAGE EASEMENT337' HOSE PULL
172' HOSE PULL
HOSE PULL CALCS
337' + 172' = 509'
509' / 2 = 254' HOSE PULL
26' WIDE FIRE LANE
LOADING
AMENITY
PATIO
14
6
10
48 CARS
EAST DRAKE ROAD
JOSEPH ALLEN DR
7
7
4
DROP OFF
9'-0"
32' FROM BUILDING
32' FROM BUILDING
NO PARKING 26' WIDE FIRE LANE
TURN AROUND
50' - 0"
FENCE
FENCE
ENTRY
NEW HYDRANT
FIRE DEPT
CONNECTION
STANDPIPE
STANDPIPE
3 STORY BUILDING
CODES:
ANSI A117.1- 2009
2015 IECC- CHAP 4 / ZONE 5
2015 IBC / IMC / IFGC / IPC
2017 NEC
2018 IFC WITH PFA AMENDMENTS
NFPA 13 SPRINKLER SYSTEM
FIRE LANE TO MEET SPECIFICATIONS
AERIAL APPARATUS ACCESS REQUIRED
ADDRESS VISABLE FROM EAST DRAKE &
JOSEPH ALLEN
ELEVATOR- STRETCHER COMPLIANT
RADIO AMP TESTING REQUIRED
KNOX BOX REQUIRED
NO BALCONIES OR ROOFTOP AMENITIES
PROVIDED
ALTERNATE MEANS PROPOSED TO
MEET PERIMETER ACCESS:
1. CUL-DE-SAC PROVIDED PER THE CITY
OF FORT COLLINS & POUDRE FIRE
AUTHORITY.
2. NEW HYDRANT PROPOSED WITHIN
100 FEET OF FIRE DEPARTMENT
CONNECTION.
3. STANDPIPES PROVIDED AT TWO
STAIR LOCATIONS.
4. 3' x 5' ROOF HATCH ACCESS
PROVIDED AT EACH STAIR, FINAL
DESIGN WILL BE REVIEWED DURING
BUILDING PERMIT SUBMITTAL PHASE.
5. PROVIDE AUTO-TURN DIAGRAM WITH
52' LADDER TRUCK
PROPERTY LINE
PROPERTY LINE
PROPERTY LINE
DETENTION POND
MAIN ENTRY
7' SIDEWALK
ADJACENT TO PARKING
ROOF HATCH
ACCESS
ROOF HATCH
ACCESS
ENTRY
FIRE ACCESS
ONLY- ENTRANCE
WITH KNOX BOX
PROJ.
DAT NO.
E:
17033
4/ 3/ 19
VOA- Fort Collins
East Drake Rd
1 1" = 30'-0"