HomeMy WebLinkAboutWILLOW STREET RESIDENCES - FDP180027 - SUBMITTAL DOCUMENTS - ROUND 3 - CITY STAFFWORD\DATA\FORMS\C-1.DOC REV.October 29, 2018
COMMERCIAL SERVICE INFORMATION FORM (C-1) (10/25/18 Preliminary)
City of Ft. Collins Electric Utility 700 Wood St. P.O. Box 580 Ft. Collins, CO 80522
(970)221-6700 or fax (970)221-6619
Service voltages available are (not all voltages are available at all locations):
120/240 V. 1 phase, 3 wire 120/208 V. 3 phase, 4 wire
120/208 V. 1 phase, 3 wire (network) 277/480 V. 3 phase, 4 wire
Primary 13,200 V. Grd Y /7620 120/240 V. 3 phase, 4 wire (special utility permission required)
For CT’d meters, Light and Power will provide the meter socket and CT’s to the electrical contractor. CT’s cannot be
placed in the transformer, but may be located in a building mounted cabinet (provided by owner) or in the owner’s
switchgear. In no case, can meters be mounted on the transformer.
• Cold sequencing is required for all commercial services that are direct metered.
• If CT’d metering, the owner must provide and install a - 1” conduit from the CT location to the electric meter.
☞☞☞☞Please complete the following completely and legibly:
Date Submitted: October 31, 2018______________
Voltage Requested: __208/120__ 1 phase OR X 3 phase
Building Main (not fuse) Size: ___2500___________ Amps
Number of Conduits: _10____ Size of Conduits:_3”_
Number of Cables: _4____ Size of Cables: _350Kcml AL_
Electric Heat: Yes _________kW No
Business Name: _Willow Street Residences Building A_
Site Address: ___223 Willow Street____________________
Owners Name: ____CA Ventures______________________
Mail Address: ____130 East Randolph Suite 2100________
City: ____Chicago, IL 60601__________________________
State & Zip:_____IL 60601____________________________
Phone: ____312-800-5368____________________________
General Contractor: ____Dohn Construction_____________
Individual: ____Doug Dohn____________________________
Mail Address: ____2642 Midpoint Drive__________________
City: ____Fort Collins_________________________________
State & Zip: ____CO 80424____________________________
Phone: ___(970) 490-1855_____________________________
Electrical Contractor: ___Bret’s Electric, LLC_____________
Mail Address: ____8312 Raspberry Way, Suite A__________
City: ___Frederick___________________________________
State & Zip: ____CO 80530____________________________
Phone: ____(720) 378-6497____________________________
Firm: ____Bret’s Electric, LLC_________________________
Number of CT’d meters: ___1__ at ___800________Amps each
Number of Self-Contained meters: _102_ at _100__Amps each
Largest Motor: __3/4____ H.P. 1 Phase ____30___ H.P. 3 Phase
Will any generating system (including photo-voltaics) be
installed? Yes (contact utility for requirements) X No
If Yes, this will be for: emergency service
parallel generation
Will a fire pump be installed? X Yes □ No
Form Completed by:
Name: _____________Lawrence Smith, P.E.________________
Company:______Electricon, LLC_________________________
Mail Address: ___37127 Cullison Ridge Rd__________________
City: ___________Severance______________________________
State & Zip: _____CO 80550______________________________
Phone: _________970-310-0775___________________________
For Office Use Only
Transformer Size: _________________________________kVA
Fault Current at Transformer: _______________________Amps
100% Construction - Cont. # ____________ Paid: ____________
A.T.E. Date: _____________________
Engineering Approval by: ______________ Date: _____________
Metering Approval by: _________________ Date: _____________