Re:
FTC EAST DALE
Dated: 10/02/2018
Project: Cell site Rooftop Cupola
Job Address: 901 Riverside Ave., Ft. Collins, CO. 80524
To: Brandy Bethurem Harras
Development Review Coordinator
City of Fort Collins Community Development & Neighborhood Services
281 N. College Ave. Fort Collins, CO 80524
Hello Brandy,
We are sending you this narrative pertaining to the Drawing Revisions you requested below:
As Noted:
RE: FTC EAST DALE, BDR180016, Round Number 1
Department: Engineering Development Review
Contact: Spencer Smith, 970-221-6603, smsmith@fcgov.com
Topic: General
Comment Number: 1
07/09/2018: Please contact Spencer Smith (smsmith@fcgov.com or (970)-221-6603) if you
have further questions regarding these conceptual engineering comments or requirements.
Comment Number: 2
07/09/2018: This project is responsible for dedicating any right-of-way and easements that are
necessary or required by the City for this project. There should be dedication of ROW along
Riverside to match the ROW width of the adjacent Houska South lot. Information on the
dedication process can be found at:
http://www.fcgov.com/engineering/devrev.php
[RESPONSE] No Easements are required in the Right-of-way. All Easements shown are on the
subject property and private between the Property owner and Verizon only.
Comment Number: 3
07/09/2018: All necessary permitting will be required of any proposed work/improvements
within the public right-of-way, prior to construction. From the site plan, it appears that a portion
of the proposed utilities are being installed within existing road ROW. Please provide more
detail to clarify extend of utility work proposed. Utility plans may be required for the project if
any public improvements are proposed (to be determined by City staff).
[RESPONSE] All utility work shown is on the Private Property. The Utilities Providers will bring
services to the property boundary.
Comment Number: 4
07/09/2018: Larimer County Road Impact Fees and Transportation Expansion Fees are due at
the time of building permit. Please contact Kyle Lambrecht at (970) -221-6566 if you have any
questions.
[RESPONSE] At the time of Application for Building Permit we will contact Larimer County for all
necessary Permits.
Comment Number: 5
07/09/2018: The City's Transportation Development Review Fee (TDRF) is due at the time of
submittal. For additional information on these fees, please see:
http://www.fcgov.com/engineering/dev-review.php
[RESPONSE] Fee being paid at time of submittal
16035 Table Mountain Pkwy
Golden, CO 80403
P: 303-993-3293 / F: 303-993-3019
Comment Number: 6
07/09/2018: Any damaged curb, gutter and sidewalk existing prior to construction, as well as
streets, sidewalks, curbs and gutters, destroyed, damaged or removed due to construction of
this project, shall be replaced or restored to City of Fort Collins standards at the Developer's
expense prior to the acceptance of completed improvements and/or prior to the issuance of the
first Certificate of Occupancy.
[RESPONSE] Any damaged curb, gutter and sidewalk will be restored to the City of Fort Collins
standards.
Comment Number: 7
07/09/2018: All public sidewalk, driveways and ramps, existing or proposed, adjacent or within
the site, need to meet ADA standards.
[RESPONSE] All sidewalks, driveways and ramps will meet ADA standards
Comment Number: 8
07/09/2018: Any public improvements must be designed and built in accordance with the
Larimer County Urban Area Street Standards (LCUASS). They are available online at:
http://www.larimer.org/engineering/GMARdStds/UrbanSt.htm
[RESPONSE] No Public improvements are included in this Plan
Comment Number: 9
07/09/2018: A utility coordination meeting on this site is suggested. Utility coordination
meetings, if requested, are typically scheduled after the preliminary submittal of the project, but
can be scheduled prior to submittal upon request. Please provide a site plan with a preliminary
utility layout for routing with the meeting notice. If you are interested in having a utility
coordination meeting, please contact the development review engineer for scheduling.
[RESPONSE] A utility Coordination Meeting will be scheduled
Comment Number: 10
07/09/2018: All fences, barriers, posts or other encroachments within the public right-of-way are
only permitted upon approval of an encroachment permit. Applications for encroachment
permits shall be made to the Engineering Department for review and approval prior to
installation. Encroachment items shall not be shown on the site plan as they may not be
approved, need to be modified or moved, or if the permit is revoked then the site/ landscape
plan is in non-compliance.
[RESPONSE] No improvements are planned within the Right-of-Way
Comment Number: 11
07/09/2018: With regards to construction of this site, the public right-of-way shall not be used
for staging or storage of materials or equipment associated with the Development, nor shall it be
used for parking by any contractors, subcontractors, or other personnel working for or hired by
the Developer to construct the Development. The Developer will need to find a location(s) on
private property to accommodate any necessary staging and/or parking needs associated with
the completion of the Development. Information on the location(s) of these areas will be
required to be provided to the City as a part of the Development Construction Permit
application.
[RESPONSE] All construction Staging, and Parking will be done on the Private Property.
Comment Number: 12
07/09/2018: See redlines from Engineering Development Review for additional comments
and/or clarification of these written comments.
[RESPONSE] Corrections included.
16035 Table Mountain Pkwy
Golden, CO 80403
P: 303-993-3293 / F: 303-993-3019
Department: Environmental Planning
Contact: Stephanie Blochowiak, 970-416-4290, sblochowiak@fcgov.com
Topic: General
Comment Number: 1
07/06/2018: Generally, an Ecological Characterization Study (ECS) is required by City of Fort
Collins Land Use Code (LUC) Section 3.4.1 as the site is within 500 feet of LUC defined natural
habitats and features (Springer Natural Area). However, as there is an intervening parcel and a
road between the pond and this property, and the standard buffer would not extend to this
proposed project’s parcel, the ECS is waived for this site. However, please consider the use of
native plants to complement the natural feature, if landscape updates are necessary per code.
[RESPONSE] The ECS is waived for this site.
Comment Number: 2
07/06/2018: If landscape updates are required note City of Fort Collins Land Use Code [Section
3.2.1 (E)(3)], requires that to the extent reasonably feasible, all plans be designed to incorporate
water conservation materials and techniques. This includes use of low-water-use plants and
grasses in landscaping or re-landscaping and reducing bluegrass lawns as much as possible.
Native plants and wildlife-friendly (ex: pollinators, butterflies, songbirds) landscaping and
maintenance are also encouraged. Please refer to the Fort Collins Native Plants document
available online and published by the City of Fort Collins Natural Areas Department for guidance
on native plants is: http://www.fcgov.com/naturalareas/pdf/nativeplants2013.pdf. Also see the
City of Fort Collins Plant List: https://www.fcgov.com/forestry/plant_list.pdf.
[RESPONSE] If Landscape Updates are Required, Low Water Use Plants will be incorporated
Comment Number: 3
07/06/2018: It does not appear trees would be impacted, however, if they may be note LUC
Section 3.2.1(C) requires developments to submit a landscape and tree protection plan, and if
receiving water service from the City, an irrigation plan, that: "... (4) protects significant trees,
natural systems, and habitat, and (5) enhances the pedestrian environment. " Note that a
significant tree is defined as one having DBH (Diameter at Breast Height) of six inches or more.
If trees may be impacted then a review of trees shall be conducted with Ralph Zentz, Senior
Urban Forester (970-221-6302 or rzentz@fcgov.com) to determine the status of existing trees
and any mitigation requirements that could result from the proposed development.
[RESPONSE] No DBH Trees of 6” will be impacted
Comment Number: 4
07/06/2018: If lighting updates occur note that for LED light fixtures, cooler color temperatures
are harsher at night and cause more disruption to circadian (biological) rhythms for both
humans and wildlife. Warmer color temperature (warm white, 3000K or less) for any LED light
fixtures is preferred. Please also consider fixtures with motion-sensing or dimming capabilities
so that light levels can be adjusted as needed. Site light sources shall be fully shielded and
down-directional to minimize up-light, light spillage and glare [see LUC 3.2.4(D)(3)]. Thank you
in advance for supporting City of Fort Collins Night Sky Objectives. For further information
regarding health effects please see: http://darksky.org/ama-report-affirms-human-health-
impacts-from-leds/
[RESPONSE] Only Emergency Service, Downcast Lights are planned. They will be on a 60 Min.
Timer
16035 Table Mountain Pkwy
Golden, CO 80403
P: 303-993-3293 / F: 303-993-3019
Department: Forestry
Contact: Molly Roche, mroche@fcgov.com
Topic: Landscape Plans
Comment Number: 1
7/9/2018: There appears to be existing trees on-site, and a few that are in close proximity to the
proposed wireless communications device. Please include the City of Fort Collins tree
protection notes to the site plan, which are available from City Forestry or the project planner. In
addition, please schedule an on-site meeting to obtain tree inventory and mitigation information
if there are any proposed or expected impacts to existing trees.
[RESPONSE] No DBH Trees of 6” will be impacted, however Contractor will provide Protection
for any trees in close proximity
Department: PFA
Contact: Andrew Rosen, arosen@fcgov.com
Topic: General
Comment Number: 1
07/05/2018: GATEWAY/FENCE ACCESS
The supplied documents state that this new facility may be behind a fence with a 5ft gate.
Should the applicant require this gate to be locked, a simple lock and chain which can be easily
cut by emergency crews is appropriate. Higher security may require a Knox padlock.
[RESPONSE] Knox Padlocks will be provided for the Equipment Enclosure Gate and Access
Ladders Security Panels
Comment Number: 2
07/05/2018: SIGNAGE
Signage is required at the access ladder indication the appropriate route to the new facility.
[RESPONSE] Signage denoting the direction to the Equipment located on the roof will be
provided
Comment Number: 3
07/05/2018: A hydrant is required within 300ft of this facility. This criteria is met by the hydrant at
951 Riverside Ave.
No further action required.
Comment Number: 4
07/05/2018: ACCESS
Access is required to within 150ft of all external portions of this facility. This cannot be measured
from Riverside Avenue since it is classified as an arterial street. However, the pre-existing Fire
Lanes on this site will satisfy this requirement.
No further action required.
Department: Planning Services
Contact: Kai Kleer, 970-416-4284, kkleer@fcgov.com
Topic: Building Elevations
Comment Number: 1
06/26/2018: Detail view of ground mounted equipment enclosure is required. Detail view should
include but is not limited to the following:
Details about how design elements from the existing building are incorporated into the proposed
enclosure.
Detailed elevation view of all sides.
Material specifications
Dimensional specifications
The fencing/enclosure should be consistent with what exists on site with a heavy emphasis on
landscaping to screen equipment enclosure.
[RESPONSE] The Equipment Enclosure has been redesigned to be screened on all sides by a
fluted CMU wall, with a Green Flashing Cap to match the existing building
16035 Table Mountain Pkwy
Golden, CO 80403
P: 303-993-3293 / F: 303-993-3019
Comment Number: 2
06/26/2018: Greater design detail of the RF screen is required. How will the structure be
textured to match the buildings CMU? The facility will need to incorporate a design that imitates
the existing CMU banding. The design detail should show how screen wall texturing will create
depth. Please also include flashing that is consistent with what exists on the site.
[RESPONSE] The concealment screen has been designed to match the existing banding
courses
Comment Number: 3
06/26/2018: Please provide greater specification of the cable tray that runs along the front of the
building. It is preferred that the cable tray be ran back and parallel to the existing downspout.
The color of the cable tray should match the color of the wall.
[RESPONSE] The vertical cable tray has been designed to run adjacent to an existing
downspout on the West side of the building and will be painted to match the downspout
Topic: General
Comment Number: 1
06/26/2018: Please indicate in all instances where the addition of a ladder is indicated that the
ladder will be painted to match the green color of the building's awnings/trim. It would be best to
determine the color and indicate the specification on the plan set.
[RESPONSE] All ladders included in the plan will be painted to match the Hunter Green color of
existing awnings and Trim.
Comment Number: 2
06/26/2018: Please indicate that the ground mounted equipment cabinets and anything
accessory to the installation of the antennas will be painted to match existing bollard color.
Specifications of bollard color are required.
[RESPONSE] The equipment cabinets will be painted to match the Brown Color of the existing
Bollards
Comment Number: 3
Is any lighting proposed as part of this project?
[RESPONSE] Only Emergency Service, Downcast Lights are planned, screened within the
equipment enclosure and the concealment screen. They will be on a 60 Min. Timer
Topic: Landscape Plans
Comment Number: 1
06/26/2018: A Landscape Plan is required and will need to show the following:
What species and how many shrubs will be impacted by the proposed equipment enclosure.
How the equipment enclosure will be screened by additional landscape. Keep in mind that a
total screening affect at the base of the enclosure is required. Heavy emphasis should be
placed on the use of coniferous plants. General landscape plan notes are required. Please visit
our website at fcgov.com/developmentreview/applications and find 'PDP Standard Notes' for
more information. This project will bring the existing landscape peninsula out of compliance with
3.2.1(E)(5). Please think about how the impacted shrubs can be mitigated. Alternative
compliance for this standard should demonstrate innovative design and use of plant materials
and other landscape elements where the shrubs are proposed to be removed.
[RESPONSE] The equipment enclosure has been designed to screen the equipment and match
the existing architectural design of the existing building. Minimal existing Landscaping will be
impacted.
16035 Table Mountain Pkwy
Golden, CO 80403
P: 303-993-3293 / F: 303-993-3019
Topic: Site Plan
Comment Number: 2
06/26/2018: To comply with 3.8.13(B), this project will need to demonstrate how future providers
can co-locate on the proposed antenna array. This can be achieved by showing outlines of
where antenna locations for future co-location can fit and where an additional equipment cabinet
can be located within the enclosure.
[RESPONSE] This design is such that any future carriers will need to work with the landlord for
future lease space.
Department: Stormwater Engineering
Contact: Heather McDowell, 970-224-6065, hmcdowell@fcgov.com
Topic: General
Comment Number: 1
07/09/2018: There is an existing 6-inch PVC drain line located through the proposed lease area
that needs to be located and shown on the plans. The depth will also need to be verified and
shown on the plans to ensure that any surface or subsurface improvements (i.e. conduit runs)
don't impact or damage the existing drain line.
[RESPONSE] The existing storm drain has been added to the plans and is below the proposed
work area of the equipment enclosure. Contractor will be instructed to hand dig at this location
to prevent any damage to the existing pipe.
Comment Number: 2
07/09/2018: The lease area is called out as 91 sf, 250 sf, and measured at 17.17 feet x 7.13
feet on another page. Please reconcile these labels. Also, please show the amount of
impervious area that you are adding to the Houska site.
[RESPONSE] Lease area has been reconfigured, proper labels have been added.
Approximately 130 s.f. of impervious area will be added.
Comment Number: 3
07/09/2018: There is a stormwater quality swale located along the property frontage along
Riverside (where your plans show riprap). This area needs to be protected from construction
activities and in specific, not driven on. Construction fencing or some sort of barrier needs to be
shown on the plans to keep contractors out of the drainage area. In addition, some form of
erosion control should be placed along the top of bank between the drainage area and the
construction area to protect the swale from sediment and runoff during construction
activities.
[RESPONSE] Contractor will be responsible to provide fencing protection and erosion control
measures as specified by the City of Ft. Collins Erosion Control Practices.
Contact: Mark Taylor, 970-416-2494, mtaylor@fcgov.com
Topic: Floodplain
Comment Number: 4
07/09/2018: This property is in the Old Town 100-year Flood Fringe. A Floodplain Use Permit
must be submitted and approved before any construction can begin on the ground level
equipment and the enclosure associated with it. Please add notes indicating this to the FTC
East Dale plan set.
[RESPONSE] A Floodplain Use Permit will be completed by the Contractor Prior to beginning
any construction. An elevation Certificate has already been filed with FEMA by the Surveyor.
16035 Table Mountain Pkwy
Golden, CO 80403
P: 303-993-3293 / F: 303-993-3019
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcounty@fcgov.com
Topic: General
Comment Number: 1
07/10/2018: Please revise the legal description as marked. See redlines.
[RESPONSE] Revised as specified
Comment Number: 2
07/10/2018: Some of the sheet titles in the sheet index do not match the sheet titles on the
noted sheets. See redlines.
[RESPONSE] Revised as specified
Comment Number: 3
07/10/2018: All plan sheets must be 24"x36".
[RESPONSE] Revised as specified
Department: Traffic Operation
Contact: Tim Tuttle, TTUTTLE@fcgov.com
Topic: General
Comment Number: 1
07/10/2018: No Comments.
Department: Water-Wastewater Engineering
Contact: Heather McDowell, 970-224-6065, hmcdowell@fcgov.com
Topic: General
Comment Number: 1
07/09/2018: There is an existing water service with a curb stop and meter located in the vicinity
of the proposed lease area. The service needs to be located and shown on the plans. The lease
area cannot overlap the service line.
[RESPONSE] Existing Water Service is to the North and East of the Lease Arean and will not
be overlapped or impacted.
Brad Bryant
A & E PROJECT MANAGER
CENTERLINE SOLUTIONS
16035 Table Mountain Parkway
Golden, CO 80403
Phone: 303.993.3293 x1383
Mobile: 720.284.8628