Department: Engineering Development Review
Contact: Morgan Uhlman, 970-416-4344, muhlman@fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 03/20/2018
03/20/2018: 03/19/2018: From Tyler Siegmund's files, the utility providers were
fine with a reduced UE along College, 9' minimum. Please dedicate a 9' utility
easement along the College Ave frontage.
08/19/2014: Per current road standards for an arterial roadway, a 15ft utility
easement should be provided along the College Ave frontage of the property. If
this utility easement is not needed by utility providers the 15ft UE requirement
may be reduced in size or waived. Coordination with utility providers (COFC
Water, COFC Light and Power, COFC Storm water, Comcast, Century Link, Public
Service Company of Colorado) is needed to determine if this easement is needed."
Response: A 9’ utility easement is now shown along College Ave.
Comment Number: 3 Comment Originated: 03/20/2018
03/20/2018: "Add the following note to the site plan:
Damaged curb, gutter and sidewalk existing prior to construction, as well as existing fences,
trees, streets, sidewalks, curbs and gutters, landscaping, structures, and improvements
destroyed, damaged or removed due to construction of this project, shall be replaced or
restored in like kind at the developer's expense, unless otherwise indicated on these plans,
prior to the acceptance of completed improvements and/or prior to the issuance of the
first Certificate of Occupancy. "
• Acknowledged and added to Site Plan as ‘Note 9’
Comment Number: 4 Comment Originated: 03/20/2018
03/20/2018: The 15' utility easement behind College Ave was not needed, but the
utility providers want a standard 9' utility easement. Please show that on all final
BHA Design Incorporated
1603 Oakridge Drive
Fort Collins, CO 80525
Page 2 of 15 voice: 970.223.7577
fax: 970.223.1827
landscape architecture | planning | urban design www.bhadesign.com
plan documents.
Response: A 9’ utility easement is now shown along College Ave.
Comment Number: 5 Comment Originated: 03/20/2018
03/20/2018: Please add cross slope and running slope labels and spot elevations
for curb ramps to show they are ADA compliant.
Response: Slopes are now shown on the grading plan and are all within ADA
requirements.
Comment Number: 6 Comment Originated: 03/20/2018
For the sidewalk widening along College Ave and Mason Street, there is some
work being proposed outside of the properties frontage for a transition. Is that
all in the right-of-way or is it on the adjacent property? If it is on the adjacent
property, a temporary construction easement will be needed between the two
owners before construction can begin.
Response: The sidewalk along Mason has been adjusted to maintain
improvements within ROW
Comment Number: 7 Comment Originated: 03/20/2018
The next steps will include drafting and finalizing the Development Agreement and
issuing a Development Construction Permit (DCP). The draft Agreement will be
assembled after comments have been resolved by the other departments, I have
received their language for the Development Agreement, and the Information for
Development Agreement sheet is returned to me from the owner/developer. For more
information on the DCP, please go to this website:
https://www.fcgov.com/engineering/devrev.php
Response: The Development Agreement application has been submitted.
Comment Number: 8 Comment Originated: 03/20/2018 03/20/2018: Please see
redlines for minor comments.
Response: The redlines have been addressed.
Topic: Site Plan
03/20/2018: Please depict the driveways off of Kensington Drive and Mason Street
as concrete in the right-of-way.
BHA Design Incorporated
1603 Oakridge Drive
Fort Collins, CO 80525
Page 3 of 15 voice: 970.223.7577
fax: 970.223.1827
landscape architecture | planning | urban design www.bhadesign.com
Response: Corrected.
Department: Environmental Planning
Contact: Stephanie Blochowiak, 970-416-4290, sblochowiak@fcgov.com
Topic: Landscape Plans
Comment Number: 1 Comment Originated: 03/20/2018
03/20/2018: Clarify both "Dryland Seed Mix" and "Wetland Seed Mix" called for on
plans. Will need: species list including scientific names, percent each species
contributes to mix in addition to pounds per acre and/or pounds per square foot
application rate for drill seed and broadcast seed. Recommend using a mix
containing both cool and warm season native and/or native-adapted species.
Minimum 15 lbs/acre drill seed rate and double that for broadcast rate.
List and mix options can be provided.
• Correction made.
Comment Number: 2 Comment Originated: 03/20/2018
03/20/2018: Add ‘NATIVE SEED MIX NOTES’
• Acknowledged and added to Sheet 4
Comment Number: 3
Lighting plan shows all 4000K CCT to be selected - please update to warmer color
temperatures (warm white). The American Medical Association (AMA) and International
Dark-Sky Association (IDA) both recommend using lighting that has a corrected color
temperature (CCT) of no more than 3000 degrees Kelvin in order to limit the amount of
blue light in the night environment. Cooler color temperatures are harsher at night and
cause more disruption to circadian (biological) rhythms for both humans and wildlife and
blue light brightens the night sky and creates more glare than any other color of light. Both
LED and metal halide fixtures contain large amounts of blue light in their spectrum, and
exposure to blue light at night has been shown to harm human health and endanger
wildlife. Therefore, use of warmer color temperature (warm white, 3000K or less) for light
fixtures is preferred in addition to fixtures with motion-sensing or dimming capabilities. Site
light sources shall be fully shielded and down-directional to minimize up-light, light spillage
and glare [see LUC 3.2.4(D)(3)].
Selecting 3000K or less luminaires supports City of Fort Collins Night Sky Objectives. For
further information regarding health effects please see: http://darksky.org/ama-report-
affirms-human-health-impacts-from-leds/
AW Comment Response: Understanding the city’s request for the warmer light levels, it is
a Toyota corporate standard for vehicle display to have a 4000K CCT fixture temperature, if
light levels are lowered to 3000K or less then the vehicle paint colors are altered. However,
the site photometric design has taken a conscious approach to the overall site lighting and
BHA Design Incorporated
1603 Oakridge Drive
Fort Collins, CO 80525
Page 4 of 15 voice: 970.223.7577
fax: 970.223.1827
landscape architecture | planning | urban design www.bhadesign.com
we have limited the number of fixtures to what will be considered a minimum for the
Toyota corporate standards. Furthermore, the site lighting has been designed not to bleed
off the property.
Department: Forestry
Contact: Molly Roche, , mroche@fcgov.com
Topic: Landscape Plans
Comment Number: 1 Comment Originated: 03/20/2018
Continued: Please address the status of this previous comment. I was not working for the
City of Fort Collins Forestry Division at this time and Tim Buchanan has since retired, so I
cannot ask him about the history of this specific question.
6/25/2014: Thank you for arranging the first tree evaluation meeting. Please set up a
second onsite meeting with the City Forester to complete the tree inventory and mitigation
plan. As part of that meeting, some further review of the north-most Ash on Mason can
occur to consider desirability of removal or retention. Initial discussion at the first meeting
indicated the tree would be removed but some further discussion could be beneficial in
making a final determination.
A second meeting was held onsite with Molly Roche and further evaluation conducted.
This resulted in the removal of additional potential hazard trees and the Green Ash along
Mason mentioned from the 6/25/2014 comment. Tree mitigation plan has been updated
to reflect these changes.
Comment Number: 2 Comment Originated: 03/21/2018
3/20/2018: Continued: Please provide tree species diversity in the plant list and list
percentages.
6/25/2014: Provide tree species diversity on the final landscape plan and list percentages in
the plant list. Identify species on final landscape plan.
Tree species diversity added to the plant list
Comment Number: 5 Comment Originated: 03/21/2018
3/20/2018: Continued:
8/19/2014: Previous comment number two provided on 6/25/2014 is continued and still
active.
Tree species diversity added to the plant list
Comment Number: 7 Comment Originated: 03/21/2018
Continued: Thank you for providing 33 mitigation trees to meet the requirement. Please
upsize mitigation trees as follows:
• Canopy shade trees: 3.0” caliper balled and burlapped
• Ornamental trees: 2.5” caliper balled and burlapped
BHA Design Incorporated
1603 Oakridge Drive
Fort Collins, CO 80525
Page 5 of 15 voice: 970.223.7577
fax: 970.223.1827
landscape architecture | planning | urban design www.bhadesign.com
• Evergreen trees: 8’ height balled and burlapped
In addition, please indicate mitigation trees with an “M” next to the trees on the
landscape plans.
8/19/2014:For final landscape plan, include 22 upsized mitigation trees. Mitigation trees
should be upsized as follows:
• Canopy shade trees: 3.0 inch caliper
• Ornamental trees: 2.5 inch caliper
• Evergreen trees: 8 feet height
Acknowledged – Mitigation trees upsized and (M)’s added to Landscape Plan labels. We
are showing 33 upsized trees.
Comment Number: 8 Comment Originated: 03/21/2018
3/20/2018:
Lindens do not typically survive or thrive in parking lot islands and medians. Please use
another species in places where Lindens are shown in the parking lot, such as Kentucky
Coffeetree or Catalpa
All but one Linden has been removed from islands, most replaced with New Horizon Elm or
Texas Red Oak.
Comment Number: 9 Comment Originated: 03/21/2018
3/20/2018:
Please use the most current City of Fort Collins General Landscape Notes, Tree
Protection Notes, and Street Tree notes on the plans, and show the street tree
permit note on all landscape sheets to emphasize importance. These notes are
available from Molly Roche in City Forestry (mroche@fcgov.com).
Acknowledged Notes added to Sheet 4 with reference to notes on Landscape plan. Street
tree permit note added to all sheets.
Comment Number: 10 Comment Originated: 03/21/2018
3/20/2018:
Show location of any stop signs and street lights. Identify these fixtures with a
Distinct symbol. Space trees if needed as follows.
Stop Signs: 20 feet from sign
Street Light: 40 feet for canopy shade trees and 15 feet for ornamental trees
Acknowledged
Comment Number: 11 Comment Originated: 03/21/2018
3/21/2018:
Please confirm that all tree-utility separations meet code. There is (1) TICO on
Mason that is less than 5 feet from a sanitary sewer line. In addition, Wes Lamarque
commented in the staff meeting on 3/21/18 that some proposed trees along the
north boundary need to be shifted or removed because they are encroaching the
sanitary sewer line. Please consider adjusting these trees further from the line or
BHA Design Incorporated
1603 Oakridge Drive
Fort Collins, CO 80525
Page 6 of 15 voice: 970.223.7577
fax: 970.223.1827
landscape architecture | planning | urban design www.bhadesign.com
finding another place on the landscape plan to incorporate these trees/shrubs.
During our field visit to inventory additional trees along the north boundary line, we
should take a look at the existing tree Wes would like removed for the same reason.
• Removed the TI CO identified above adjusted street tree spacing along Mason.
• Trees encroaching the SS line along the northern property have been removed.
Department: Internal Services
Contact: Jonathon Nagel, jnagel@fcgov.com
Topic: General
Comment Originated: 03/16/2018
Comment Number: 1
The Community Recycling Ordinance (No. 109 2016) requires that all business and
multifamily complexes subscribe to recycling service by the end of 2020 that is at minimum
1/3 of their overall service capacity (total bin capacity x number of weekly pickups, include
both trash and recycling when calculating overall service capacity). In general recycling
containers must be at least 50% the size of proposed trash containers to meet this
requirement. Please make sure proposed containers meet this requirement and that
adequate space is provided in all enclosures.
AW Comment Response: Noted. The proposed 6 cubic yard dumpsters (2 trash / 1 recycle)
should meet this requirement.
Comment Number: 2
I see a plan enlargement for a proposed trash/recycling enclosure on A4.3, but it doesn't
appear to match either enclosure on the site plan. Will both enclosures be identical? Please
provide updated elevations and plan enlargements for all proposed trash/recycling
enclosure and include the overall dimensions, widths of service gates and required
pedestrian entrance along with proposed containers and their capacities on them.
AW Comment Response: Please see revised sheet A4.3 for the revised trash enclosure and
the enclosures at the parking garage (new / used oil enclosures). The trash enclosure has a
pedestrian service entrance and (3) 6 cubic yard trash / recycling containers. The oil
enclosures are not meant to be pedestrian accessible. The oil containers are serviced from
the top only by pump trucks for environmental safety and to eliminate any potential of
spillage.
Comment Number: 3
The enclosure located behind the existing structure is not conducive to efficient pickup.
Being locating at the end of a dead end the collection truck will need to back into or out of
the isle increasing the risk of injury and property damage.
BHA Design Incorporated
1603 Oakridge Drive
Fort Collins, CO 80525
Page 7 of 15 voice: 970.223.7577
fax: 970.223.1827
landscape architecture | planning | urban design www.bhadesign.com
AW Comment Response: We have revised the trash enclosure location to aid in efficient
pick up, see the updated site plan and enlarged enclosure plan.
Comment Number: 4
03/16/2018: Curb cuts will need to be provided in front of all trash/recycling
enclosures to allow containers to be wheeled in and out if not done so already.
Response: Curb cuts have been added at the new trash enclosure location.
Comment Number: 5
The enclosure behind the parking structure will need a pedestrian entrance that is separate
from the main service gates. Consider using a door-less entry which will provide safer and
more efficient access.
AW Comment Response: The enclosures behind the parking structure are for new and used
oil tanks. The enclosures are not meant to be pedestrian accessible for safety, see
additional explanation in comment response #1 above.
Department: Light And Power
Contact: Rob Irish, 970-224-6167, rirish@fcgov.com
Topic: General
Comment Originated: 03/19/2018
Comment Number: 1
Comment Originated: 03/19/2018
03/19/2018: Light & Power has existing streetlights adjacent to the site along Mason
St. that may be in conflict with the proposed entrance off of Mason St. Please field
locate and show these facilities on the plans.
Response: There is one street light that will need to be relocated.
Comment Number: 2
Comment Originated: 03/19/2018
03/19/2018: Please field locate and show the existing primary line from College Ave. to
the existing transformer on the plans. This line most likely runs through the proposed
LID area and may need to be potholed to determine if this line will be in conflict.
Comment Number: 3
Certain building materials and or building design may require more clearance for the
proposed transformer location. Please adhere to all clearance requirements in the Electric
BHA Design Incorporated
1603 Oakridge Drive
Fort Collins, CO 80525
Page 8 of 15 voice: 970.223.7577
fax: 970.223.1827
landscape architecture | planning | urban design www.bhadesign.com
Service Standards at the following link. http://www.fcgov.com/utilities/business/builders-
and-developers/development-forms-guidelines-regulations
AW Comment Response: After discussions with the city it was deemed that a screen wall
would not be required at the transformer, it has been removed so clearance will not be an
issue.
Comment Number: 4 Comment
Originated: 03/19/2018
03/19/2018: A commercial service information form (C-1 form) and a one line diagram will
need to be submitted to Light & Power Engineering. A link to the C-1 form is below:
http://www.fcgov.com/utilities/business/builders-and-developers/development-forms
-guidelines-regulations
Response: Acknowledged
Comment Number: 5 Comment
Originated: 03/19/2018
03/19/2018: Electric Capacity Fee, Building Site charges, and any system modification
charges necessary will apply to this development. Please contact Light & Power
Engineering if you have any questions at 970-221-6700. Please reference our Electric
Service Standards, development charges and fee estimator at the following link:
http://www.fcgov.com/utilities/business/builders-and-developers
Response: Acknowledged
Comment Number: 6
What is the dark line shown in front of the proposed transformer location?
AW Comment Response: This line was the transformer screen wall, see Comment response
#3 above, the screen wall has been removed.
Department: PFA
Contact: Andrew Rosen, , arosen@fcgov.com Topic: General
Comment Number: 1 Comment
Originated: 03/20/2018
03/21/2018: UPDATE
The final site plan will reflect this change.
03/19/2018:
Per the IFC 2015, the Emergency Access Easement is now allowed to be 26ft in width
rather than the 30ft shown but it cannot be located closer than 15ft to the edge of the
building.
BHA Design Incorporated
1603 Oakridge Drive
Fort Collins, CO 80525
Page 9 of 15 voice: 970.223.7577
fax: 970.223.1827
landscape architecture | planning | urban design www.bhadesign.com
Response: The EAE along the west side of the garage is 15 ft off of the garage and labeled
on the Horizontal Control Plan.
Comment Number: 2 Comment
Originated: 03/20/2018
03/21/2018: UPDATE
Project team stated they will provided a Fire Lane signage plan for approval in PDF.
03/19/2018:
The signage plan for the Fire Lanes should be available for review by PFA before the FDP
can be approved.
Response: The fire lane signage is shown on the Horizontal Control Plan. We were limited
on the availability of where signage could be placed, so we used a combination of red
painted curb and no parking signage.
Comment Number: 3 Comment
Originated: 03/20/2018
03/21/2018: UPDATE
Project team stated they will delete the cars as shown. The inventory will always be in flux
so they need access also.
03/20/2018:
Cars are shown on the provided documents parked very closely in the new structure. PFA
requests information on how the vehicles will be stored to allow for access.
Response: We understand the needs for adequate access within the parking structure
and this has been discussed with Pederson. As this will become an operational issue,
Pedersen will continue to work with PFA once the new facility is in place to coordinate
access requirements and appropriate inventory parking to allow for this.
Department: Planning Services
Contact: Noah Beals, 970-416-2313, nbeals@fcgov.com
Comment Number: 1 Comment Originated: 03/20/2018
03/20/2018: On the Plat the signature block for Planning, "Director of" appears twice,
delete one. On the signature line edit to CDNS Director.
• Acknowledged, “Director of” removed and replaced with ‘CDNS Director’
Comment Number: 2 Comment Originated: 03/20/2018
03/20/2018: Note 8 on the site plan should include all signs, not just monument
Signs.
• Acknowledged, Changed to read ‘Any sign monument or otherwise’
BHA Design Incorporated
1603 Oakridge Drive
Fort Collins, CO 80525
Page 10 of 15 voice: 970.223.7577
fax: 970.223.1827
landscape architecture | planning | urban design www.bhadesign.com
Comment Number: 3
Comment Originated: 03/20/2018
03/20/2018: On the site plan, the Handicap spaces on the north side of the building, where
is the sidewalk ramp connection for these spaces?
Response: A ramp has been added at the HC access aisle
Comment Number: 4
Comment Originated: 03/20/2018
03/20/2018: Can there be wheels stops or something else to prevent cars parked in the
parallel spaces on the south parking area from encroaching into the accessibility route to
the entrance of the building?
Response: Wheel stops have been added and labeled on the Site Plan
Department: Stormwater Engineering
Contact: Jesse Schlam, 970-218-2932, jschlam@fcgov.com Topic: Erosion Control
Comment Number: 1 Comment
Originated: 03/12/2018
03/12/2018: Please resubmit an Erosion Control Report as the recently received materials
has comments and redlines that needed to be addressed to meet City Criteria. Please
resubmit an Erosion Control Plans as the recently received materials have comments and
redlines that needed to be addressed to meet City Criteria. Please resubmit an Erosion
Control Escrow / Security Calculation as the recently received materials has comments and
redlines, that needed to be addressed to meet City Criteria and as a result have changed
the Erosion Control Plans and would require a recalculation of the Escrow. If you need
clarification concerning the Erosion Control Material Requirements or Comments
presented above please contact myself. Jesse Schlam (970) 224-6015 jschlam@fcgov.com
Response: The erosion control plan and report have been updated and comments
addressed. There was concern about the use of erosion control log around portions of
the site exterior. The areas proposed with the erosion logs have very limited sheet flows
area and we believe these are adequate in these areas.
Contact: Wes Lamarque, 970-416-2418,
wlamarque@fcgov.com Topic: General
Comment Number: 1
Comment Originated: 03/19/2018
03/19/2018: Please make changes as marked. If changes are not made or you disagree with
comments, please provide written response of why corrections were not made. Please
BHA Design Incorporated
1603 Oakridge Drive
Fort Collins, CO 80525
Page 11 of 15 voice: 970.223.7577
fax: 970.223.1827
landscape architecture | planning | urban design www.bhadesign.com
provide any responses on redlined sheets and/or in response letter.
Response: The updated title commitment was not available in time for this submittal and
will be updated once received.
Comment Number: 2
Comment Originated: 03/20/2018
03/20/2018: The void ratio the City has for criteria is 30% in the No. 2 rock. Please revise
detention calculations.
Response: All LID calculations have been updated.
Comment Number: 3
Comment Originated: 03/20/2018
03/20/2018: An overflow inlet is required at the low point for all the porous paver
areas. This is to prevent standing water in the sump locations for the paver areas.
Response: Overflow inlets are provided at the low-points in the pavers.
Comment Number: 4
Comment Originated: 03/23/2018
03/23/2018: Please verify the run-on ratios for the porous pavers located in the table.
The ratios need to include all the impervious area draining onto the pavers including
the roofs of all the buildings.
Response: All LID calculations have been updated and includes the roof areas.
Comment Number: 5
Comment Originated: 03/23/2018 03/23/2018: Please include an orifice detail for the
quantity detention.
Response: The orifice plate is now called out in multiple locations.
Comment Number: 6
Comment Originated: 03/23/2018
03/23/2018: The porous paver detail needs some edits and the City detail can be used.
More discussion is needed .
Response: We maintained the non-woven fabric across the bottom of the pond to
limit sediment migrating up into the paver section and that would potentially cause
settling.
Comment Number: 7 Comment
Originated: 03/23/2018
03/23/2018: Is enough area draining onto porous paver area 1 to use the volume in
the aggregate as quantity detention?
BHA Design Incorporated
1603 Oakridge Drive
Fort Collins, CO 80525
Page 12 of 15 voice: 970.223.7577
fax: 970.223.1827
landscape architecture | planning | urban design www.bhadesign.com
Response: Paver area 1 has been removed and all detention is provided in the pond
for this basin
Comment Number: 8 Comment
Originated: 03/23/2018
03/23/2018: Please label scour stop mats on the grading plans and erosion control
plan. Is any riprap being proposed? A detail was provided.
Response: Scourstop is called out and details are provided.
Department: Technical Services
Contact: Jeff County, jcounty@fcgov.com
Topic: Site Plan
Comment Number: 2 Comment Originated: 03/19/2018
03/19/2018: Some of the sheet titles in the sheet index do not match the sheet titles on
the noted sheets. See redlines.
• Acknowledged and corrected
Comment Number: 3 Comment Originated: 03/19/2018
03/19/2018: Please revise the legal description as marked. See redlines.
• Acknowledged and corrected
Comment Number: 4 Comment Originated: 03/19/2018
03/19/2018: There is text that needs to be masked. Mask all text in hatched areas. See
redlines.
• Acknowledged and corrected
Comment Number: 5 Comment Originated: 03/19/2018
03/19/2018: Some of the easement descriptions shown are incorrect. If they are going to
stay on the plan, they should match what is shown on the Subdivision Plat.
• Acknowledged and corrected
Comment Number: 6 Comment Originated: 03/19/2018
03/19/2018: There are line over text issues. See redlines.
• Acknowledged and corrected
Comment Number: 7 Comment Originated: 03/19/2018
03/19/2018: There are text over text issues. See redlines.
• Acknowledged and corrected
Comment Number: 8
BHA Design Incorporated
1603 Oakridge Drive
Fort Collins, CO 80525
Page 13 of 15 voice: 970.223.7577
fax: 970.223.1827
landscape architecture | planning | urban design www.bhadesign.com
Please change the title as marked on all sheets to "Pedersen Toyota Expansion" to match
the other plan sets. See redlines.
AW Comment Response: Noted all title sheets have been updated to read Pedersen Toyota
Expansion.
Comment Number: 9
03/19/2018: There are line over text issues. See redlines.
AW Comment Response: Noted please see revised sheets A4.1 and A4.2.
Comment Number: 10
Please change the title as marked on all sheets to "Pedersen Toyota Expansion" to match
the other plan sets.
AW Comment Response: Noted all title sheets have been updated to read Pedersen Toyota
Expansion.
Comment Number: 11 Comment Originated: 03/19/2018
03/19/2018: Please revise the sub-title as marked. See redlines.
• Acknowledged, changed Sub-Title to read ‘Pedersen Toyota Expansion’
Comment Number: 12
Comment Originated: 03/19/2018 03/19/2018: Please provide the following information
in the EXACT format shown.
PROJECT DATUM: NGVD29 UNADJUSTED (OLD CITY OF FORT COLLINS DATUM)
BENCHMARK # w/ DESCRIPTION ELEVATION:
BENCHMARK # w/ DESCRIPTION ELEVATION:
NOTE: IF NAVD 88 DATUM IS REQUIRED FOR ANY PURPOSE, THE FOLLOWING EQUATION
SHOULD BE USED: NAVD88 = NGVD29 UNADJUSTED
+ X.XX’.
Response: Benchmark description has been updated.
Comment Number: 13 Comment Originated: 03/19/2018
03/19/2018: Some of the easement descriptions shown are incorrect. If they
are going to stay on the plan, they should match what is shown on the
Subdivision Plat.
• Acknowledged, Easements match the PLAT.
Comment Number: 14
BHA Design Incorporated
1603 Oakridge Drive
Fort Collins, CO 80525
Page 14 of 15 voice: 970.223.7577
fax: 970.223.1827
landscape architecture | planning | urban design www.bhadesign.com
Comment Originated: 03/19/2018
03/19/2018: Please tie the coordinate values shown to the project boundary. We would
prefer that this be done by adding property corner values to each sheet, or showing the
property corner values on the horizontal control plans and adding a note to each sheet with
coordinate values.
Response: Property corners northing-eastings are provided on the Horizontal Control Plan
Comment Number: 15
Comment Originated: 03/19/2018
03/19/2018: There is text that needs to be masked. Mask all text in hatched areas. See
redlines.
Response: Line over text issues have been corrected.
Comment Number: 16
Comment Originated: 03/20/2018
03/20/2018: Please make sure the right of way & easement descriptions shown match
what is shown on the Subdivision Plat.
Response: Descriptions have been corrected
Department: Traffic Operations
Contact: Tim Tuttle
Topic: General
Comment Number: 1 Comment Originated: 03/19/2018
03/22/2018: The TIS has been accepted per LCUASS 4.8.1.
Response: Acknowledged
Comment Number: 2 Comment Originated: 03/22/2018
03/22/2018: No comments on the final plan related to signing and striping.
Response: Acknowledged
Department: Water Conservation
Contact: Eric Olson, 970-221-6704, eolson@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 03/21/2018
03/21/2018: Irrigation plans are required no later than at the time of building permit.
The irrigation plans must comply with the provisions outlined in Section 3.2.1(J) of
the Land Use Code. Direct questions concerning irrigation requirements to Eric
Olson, at 221-6704 or eolson@fcgov.com
Response: Acknowledged. Irrigation plans will be included with the building permit
submittals for your review.
BHA Design Incorporated
1603 Oakridge Drive
Fort Collins, CO 80525
Page 15 of 15 voice: 970.223.7577
fax: 970.223.1827
landscape architecture | planning | urban design www.bhadesign.com
Department: Water-Wastewater Engineering
Contact: Wes Lamarque, 970-416-2418, wlamarque@fcgov.com Topic: General
Comment Number: 1 Comment Originated: 03/20/2018
03/20/2018: There are proposed tress located along the northern property line within the
utility easement. Please remove all the trees within the easement. See redlines.
Response: Offsite trees are not proposed to be removed though we are removing some
of the trees along the easement within the Pedersen site.
Comment Number: 2 Comment Originated: 03/20/2018
03/20/2018: Please show the existing curb stops and meter pits for the existing
water services.
Response: We believe all existing utilities are now indicated on the plans.
Comment Number: 3 Comment Originated: 03/20/2018
03/20/2018: Please label the existing water and sewer lines north of the site.
Response: Water and sewer lines are indicated on the plans.