HomeMy WebLinkAboutTHE UNION ON ELIZABETH (FORMERLY 1208 W. ELIZABETH STREET) - FDP - FDP170024 - SUBMITTAL DOCUMENTS - ROUND 3 - PHOTOMETRIC PLAN (3)UG Unit Quan. 2 5 4 4 3 7 47 16 14 5 Sq Ft 1619 516 594 846 1175 1198 1382 1574 1679 1679 Total Sq Ft 3238 2580 2376 3384 3525 8386 64954 25184 23506 8395 220.82(B)(1) General Lighting & Receptacles - 3VA/sq.ft. 4857 1548 1782 2538 3525 3594 4146 4722 5037 5037 220.82(B)(2) Small Appliances 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 220.82(B)(2) Laundry 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 Subtotal (VA) 9357 6048 6282 7038 8025 8094 8646 9222 9537 9537 200.82(B)(3)(a) Appliances Kitchen, [1], [2] FOR ADA 3794 3794 3794 3794 3794 4194 3794 3794 3794 4194 Other Appliance Subtotal 3794 3794 3794 3794 3794 4194 3794 3794 3794 4194 200.82(B)(3)(b) Cooking Appliance(Elec.) 9700 9700 9700 9700 9700 9700 9700 9700 9700 9700 200.82(B)(3)(c.) Dryer 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 200.82(B)(3)(d.) Water Heater Ignighter 372 372 372 372 372 372 372 372 372 372 220.82(B)(4) Misc. Equipment [2] 27 55 55 82 82 82 109 109 109 109 220.82(B)(4) General LoadSubtotal (VA) 28250 24969 25203 25986 26973 27442 27621 28197 28512 28912 220.82(B) General Lighting & Recptacles Demand <10kVA 100& D.F. 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 > 10kVA 40% D. F. 7300 5987 6081 6394 6789 6977 7048 7279 7405 7565 Demand Subtotal (VA) 17300 15987 16081 16394 16789 16977 17048 17279 17405 17565 220.82(C.)(3) Heating, NA 220.60 Air Conditioning, CU & FCU 1700 1700 1700 1700 1700 1700 1700 1700 1860 1860 NOTES: [1] Microwave 1200VA, Disposal 1130VA, Refrigerator 720VA, Dishwasher 744 VA. [2] EF:27.3 VA EACH [3] Microwave 1200VA, Disposal 1130VA, Refrigerator 720VA, Hood Fan 400VA, Dishwasher 744 VA. Load Calculations Dwelling Units per NEC 220.82 (UNIT FEEDER CALCULATION) UNIT T4 S1 S2 B1 C1 C2 D1 D2 E1 E2 TOTAL CONNECTED (VA) 29950 26669 26903 27686 28673 29142 29321 29897 30372 30772 TOTAL DEMAND (VA) 17300 15987 16081 16394 16789 16977 17048 17279 17405 17565 TOTAL (Amps@208V, 1PH) 83 77 77 79 81 82 82 83 84 84 FEEDER/PANEL UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT T4 S1 S2 B1 C1 C2 D1 D2 E1 E2 QUANTITY 5 16 14 5 UNIT LOAD 30.0 26.7 26.9 27.7 28.7 29.1 29.3 29.9 30.4 30.8 TOTAL LOAD 146.6 478.4 425.2 153.9 CONNECTED KVA D.F. DEMAND KVA TOTAL LOAD 1204.0 0.23 276.9 1000 AMP 120 / 208 VOLT 3 PHASE TABLE 220.84 ___ AIC 4 WIRE SERVICE 1000 A MAIN CB 100% NEUTRAL BUS GROUND BUS TOTAL CONNECTED LOAD 1204.0 KVA = 3342.1 AMPS TOTAL DEMAND LOAD 276.9 KVA = 768.7 AMPS TOTAL DESIGN CAPACITY 360.3 KVA = 1000.0 AMPS SPARE 83.3 KVA = 231.3 AMPS NOTES: LOAD SUMMARY RDB1 (1000A SECTION) FEEDER/PANEL UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT T4 S1 S2 B1 C1 C2 D1 D2 E1 E2 QUANTITY 2 5 4 4 3 7 47 16 14 5 UNIT LOAD 30.0 26.7 26.9 27.7 28.7 29.1 29.3 29.9 30.4 30.8 TOTAL LOAD 59.9 133.3 107.6 110.7 86.0 204.0 1378.1 478.4 425.2 153.9 CONNECTED KVA D.F. DEMAND KVA TOTAL LOAD 3137.1 0.23 721.5 2000 AMP 120 / 240 VOLT 3 PHASE TABLE 220.84 ___ AIC 4 WIRE SERVICE 2000 A MAIN CB 100% NEUTRAL BUS GROUND BUS TOTAL CONNECTED LOAD 3137.1 KVA = 7546.8 AMPS TOTAL DEMAND LOAD 721.5 KVA = 1735.8 AMPS TOTAL DESIGN CAPACITY 831.4 KVA = 2000.0 AMPS SPARE 109.8 KVA = 264.2 AMPS NOTES: LOAD SUMMARY RDB (2500A) FEEDER/PANEL UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT UNIT T4 S1 S2 B1 C1 C2 D1 D2 E1 E2 QUANTITY 3 5 UNIT LOAD 30.0 26.7 26.9 27.7 28.7 29.1 29.9 30.8 30.4 30.8 TOTAL LOAD 91.1 153.9 CONNECTED KVA D.F. DEMAND KVA TOTAL LOAD 245.0 0.44 107.8 400 AMP 120 / 208 VOLT 3 PHASE TABLE 220.84 ___ AIC 4 WIRE SERVICE 400 A MAIN CB 100% NEUTRAL BUS GROUND BUS TOTAL CONNECTED LOAD 245.0 KVA = 680.0 AMPS TOTAL DEMAND LOAD 107.8 KVA = 299.2 AMPS TOTAL DESIGN CAPACITY 144.1 KVA = 400.0 AMPS SPARE 36.3 KVA = 100.8 AMPS NOTES: LOAD SUMMARY 400 AMP SECTION (WORST CASE) 1000A3P 1000AF TYPICAL OF 3 400A3P CLASS "T" PULL-OUT (TYP.) LIMIT METER AIC TO 10K 400A3P CLASS "T" PULL-OUT (TYP.) LIMIT METER AIC TO 10K UTILITY CO. PAD MOUNTED TRANSFORMER 120/208V, 3P, 4W FLAG NOTES (THIS SHEET): 1. 2. LEGALLY REQUIRED STANDBY POWER SYSTEM PER NEC 701.12(E) IN LIEU OF GENERATOR AS APPROVED BY FORT COLLINS BUILDING DEPARTMENT AND FIRE DEPARTMENT. 3. PROVIDE BUSSMANN SERIES QUIK-SPEC POWER MODULE SWITCH ELEVATOR DISCONNECT WITH SHUNT TRIP OPERATOR TO INTERFACE WITH FIRE ALARM SYSTEM . #3/0 CU TO COLD WATER PIPE #3/0 CU TO BUILDING STEEL #6 CU TO SERVICE ENTRANCE GROUND ROD #4 CU TO CONCRETE ENCASED ELECTRODE COORDINATE EXACT SIZE AND REQUIREMENTS WITH FIRE PROTECTION CONTRACTOR PRIOR TO INSTALLING CONDUIT AND FEEDERS. PROVIDE ARC FLASH MITIGATION PER 240.87. 4. 5. GENERAL NOTES: A. UTILITY COMPANY TO PROVIDE EACH INDIVIDUAL METER. THE ELECTRICAL CONTRACTOR SHALL PROVIDE INDIVIDUAL METER SOCKETS WITH A PERMANENT BRASS TAG SHOWING WHICH APARTMENT, OFFICE OR ROOM IS METERED BY EACH METER. BRASS TAG REQUIREMENTS ARE AS FOLLOWS: A.A. THE TAG WILL BE ROUND AND A MINIMUM OF ONE INCH IN DIAMETER. A.B. THE TAG WILL HAVE A THREE-SIXTEENTHS HOLE NEAR THE EDGE. A.C. LETTERS AND NUMBERS MUST BE AN ETCHED IMPRESSION IN THE TAG AND BE AT LEAST THREE-SIXTEENTHS INCH IN HEIGHT. B. ELECTRICAL METER CENTERS AND MAIN DISTRIBUTION BOARD BASED OFF OF AMERICAN MIDWEST POWER LAYOUT. ANY SUBSTITUTION WILL NEED TO VERIFY GEAR WILL FIT IN ELECTRICAL ROOM WITH CODE CLEARANCES. C. VERIFY THAT ALL BREAKERS ARE SERIES RATED FOR THE FAULT CURRENTS SHOWN. PROVIDE SERIES RATING SUMMARY IN SHOP DRAWING SUBMITTAL. D. THE FAULT VALUE AT THE MAIN SERVICE DISCONNECT SHALL BE LABELED AND DATED PER CALCULATION IN ACCORDANCE WITH NEC 110.24(A). E. UPSIZE CONDUCTOR SIZE FOR ALL RUNS OVER 200' TO ACCOMMODATE VOLTAGE DROP. F. FOR RDB: SERIES RATED TO 40KAIC W/EATON MAIN SWITCH CLASS T-FUSE 600A MAXIMUM, TYPE BRH METER MODULE TENANT BRANCH BREAKERS, AND TYPE BD,BR,BRD,BQ,BQC & GFCB LOAD CENTER BREAKERS. W/GE MAIN SWITCH 300V CLASS T-FUSE 400A MAXIMUM, TYPE THQP3, THQL, THHQL, TQD5, THQD5, TMQD, AND TMQL BRANCH CIRCUIT BREAKERS. UTILITY METER EMERGENCY DISTRIBUTION BOARD "EDB" 400A, 120/208V, 3P, 4W, NEMA 1, 65K AIC FEEDER SCHEDULE 300U U 400Y 400Y 6 8 400Y 400Y 2500U 125S 125S 1 U 2000U 400Y 10 125S 125S 125S 2500U 400Y 600U 225Y 2[(3#4/0)2-1/2"C (4#4/0+#4G)2-1/2"C (4-600KCMIL+#3G)3-1/2"C WIRE AND CONDUIT SIZE 125S (3#1+#6G)1-1/2"C 1200U 2 225Y 11 80D (3#4+#6G)1-1/4"C 6[(4-600KCMIL)4"C] 3[(4-600KCMIL)4"C] 13 400Y 14 300U (4#4/0)2-1/2"C 125S 125S 125S U U 13 225Y 11 600U 60 SPD SPD SPD RESIDENTIAL DISTRIBUTION BOARD "RDB" 2500A, 120/208V, 3P, 4W, NEMA 1, 65K AIC 107 APARTMENTS, LEVELS 1-5 SECTION 6 FIRE PUMP FIRE PUMP CONTROLLER 400A 3P 400A 3P G 60A 3P MAIN DISTRIBUTION BOARD "MDB" 2000A, 120/208V, 3P, 4W, NEMA 1, 65K AIC N G LEVEL 1 125A2P (TYPICAL) LEVEL 2 LEVEL 3 LEVEL 4 LEVEL 5 ROOF 400A 3P N 225A 3P SECTION 2 SECTION 3 SECTION 4 SECTION 7 SECTION 8 SECTION 9 400A 3P 400A 3P 400A 3P 400A 3P 400A 3P SECTION 1 SECTION 5 SECTION 10 SECTION 11 SECTION 12 SECTION 13 SECTION 14 SECTION 15 110A 3P 110A 3P 400A3P 2000A 3P 225A 3P 400A SPACE G N 600A 3P 400A SPACE 200A SPACE 200A SPACE RETAIL DISTRIBUTION BOARD "RTDB" 600A, 120/208V, 3P, 4W, NEMA 1, 65K AIC M 400A3P 400AF HOUSE H1 HOUSE H3 ELEVATOR 1 100A3P 80AF M HOUSE H5 T M M M M TYP UNIT 125A2P TYP UNIT 125A2P M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M TYP UNIT 125A2P TYP UNIT 125A2P TYP UNIT 125A2P HOUSE HR M M M M M M M M M M HOUSE M1 M M M M M M M M M M M M M M M M M M M M M M TYP UNIT 125A2P TYP UNIT 125A2P M M M M M M M M M M M M M M TYP UNIT 125A2P M M M M M M M M M T ELEVATOR 2 100A3P 80AF POOL P1 42 CRT 1 2 3 1 4 4 4 5 3 7600 E. Orchard Road, Suite 250-S Greenwood Village, CO 80111-2518 tel: 303.796.6000 • fax: 303.796.6099 www.mkkeng.com Mechanical, Electrical & Energy Consultants Drawn by: Architect of Record: The architectural works depicted herein are the sole property of Humphreys & Partners Architects, L.P. and may not be constructed or used without its express written permission. No permission to modify or reproduce any of the architectural works, including without limitation the construction of any building, is expressed or should be implied from delivery of preliminary drawings or unsealed construction drawings. Permission to construct the building depicted in sealed construction drawings is expressly conditioned on the full and timely payment of all fees otherwise due Humphreys & Partners Architects, L.P. and, in the absence of any written agreement to the contrary, is limited to a one-time use on the site indicated on these plans. HUMPHREYS & PARTNERS 5339 ALPHA ROAD • SUITE 300 • DALLAS, TX 75240 (972) 701-9636 • (972) 701-9639 FAX DALLAS • CHARLOTTE • CHICAGO • DENVER • NEW ORLEANS • NEW YORK • NEWPORT BEACH • ORLANDO • SCOTTSDALE • CHENNAI • DUBAI • HANOI • LONDON • MONDEVIDEO • MEXICO CITY • TORONTO www.humphreys.com © 2017 by Humphreys & Partners Architects, L.P. All Rights Reserved Issue for 60% CD's: Designed by: Date Plotted: SHEET CONTENTS SHEET NO. Issue for Progress Set: 12-13-2018 Issue for Permit Submittal: ARCHITECTS, L.P. These drawings are for preliminary coordination only and not to be used for regulatory approval or construction DD SUBMITTAL 12-15-2017 SCALE: DATE / TIME: MKK Project Number: 2017.01.0171 • © Copyright 2017 12/13/2017 2:33:18 PM 12" = 1'-0" 12/13/2017 2:33:18 PM E5.01 ELECTRICAL ONE-LINE DIAGRAM EdR THE UNION ON ELIZABETH ARD 16471 ARD FORT COLLINS, CO Revisions # DATE COMMENTS