Loading...
HomeMy WebLinkAboutTHE HUB ON CAMPUS - PDP - PDP160038 - SUBMITTAL DOCUMENTS - ROUND 4 - (3)HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 1 Section Requirement Provided? Comment 403.1 Applicability. High-rise buildings shall comply with Sections 403.2 through 403.6. Exception: The provisions of Sections 403.2 through 403.6 shall not apply to the following buildings and structures: 1. Airport traffic control towers in accordance with Section 412.3. 2. Open parking garages in accordance with Section 406.5. 3. The portion of a building containing a Group A-5 occupancy in accordance with Section 303.6. 4. Special industrial occupancies in accordance with Section 503.1.1. 5. Buildings with: 5.1. A Group H-1 occupancy; 5.2. A Group H-2 occupancy in accordance with Section 415.8, 415.9.2, 415.9.3 or 426.1; or, 5.3. A Group H-3 occupancy in accordance with Section 415.8. YES NO YES NO NO NO NO NO SUBJECT PROJECT INCLUDES NO CONTROL TOWERS SUBJECT PROJECT INCLUDES OPEN PARKING GARAGES, BUT PROJECT SHALL COMPLY SUBJECT PROJECT INCLUDES NO GROUP A-5 OCCUPANCIES SUBJECT PROJECT INCLUDES NO INDUSTRIAL OCCUPANCIES SUBJECT PROJECT INCLUDES NO H-1 OCCUPANCIES SUBJECT PROJECT INCLUDES NO H-2 OCCUPANCIES SUBJECT PROJECT INCLUDES NO H-3 OCCUPANCIES 403.2 Construction. The construction of high-rise buildings shall comply with the provisions of Sections 403.2.1 through 403.2.4. YES 403.2.1 Reduction in fire-resistance rating. The fire-resistance-rating reductions listed in Sections 403.2.1.1 and 403.2.1.2 shall be allowed in buildings that have sprinkler control valves equipped with supervisory initiating devices and water-flow initiating devices for each floor. (SEE RESPONSES TO SECTION 403.2.1.1, BELOW) 403.2.1.1 Type of construction. The following reductions in the minimum fire- resistance rating of the building elements in Table 601 shall be permitted as follows: HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 2 Section Requirement Provided? Comment 1. For buildings not greater than 420 feet (128 000 mm) in building height, the fire-resistance rating of the building elements in Type IA construction shall be permitted to be reduced to the minimum fire- resistance ratings for the building elements in Type IB. Exception: The required fire-resistance rating of columns supporting floors shall not be reduced. 2. In other than Group F-1, M and S-1 occupancies, the fire-resistance rating of the building elements in Type IB construction shall be permitted to be reduced to the fire-resistance ratings in Type IIA. 3. The building height and building area limitations of a building containing building elements with reduced fire-resistance ratings shall be permitted to be the same as the building without such reductions. NO NO NO SUBJECT PROJECT INCLUDES NO TYPE 1A CONSTRUCTION SUBJECT PROJECT INCLUDES “M” and “S-1” OCCUPANCY GROUPS, SO REDUCTION CANNOT BE APPLIED NO REDUCTIONS AVAILABLE 403.2.1.2 Shaft enclosures. For buildings not greater than 420 feet (128 000 mm) in building height, the required fire-resistance rating of the fire barriers enclosing vertical shafts, other than interior exit stairway and elevator hoistway enclosures, is permitted to be reduced to 1 hour where automatic sprinklers are installed within the shaftsat the top and at alternate floor levels. YES SUBJECT PROJECT IS LESS THAN 420 FT IN BUILDING HEIGHT. AT THE SUBJECT PROJECT, FIRE BARRIERS ENCLOSING VERTICAL SHAFTS, OTHER THAN INTERIOR EXIT STAIRWAY AND ELEVATOR ENCLOSURES, WILL BE FIRE FATED 1-HOUR. 403.2.2 Seismic considerations. For seismic considerations, see Chapter 16. YES NOTED 403.2.3 Structural integrity of interior exit stairways and elevator hoistway enclosures. For high-rise buildings of Risk Category III or IV in accordance with Section 1604.5, and for all buildings that are more than 420 feet (128 000 mm) in building height, enclosures for interior exit stairways and elevator hoistway enclosures shall comply with Sections 403.2.3.1 through 403.2.3.4. NO SUBJECT PROJECT IS RISK CATEGORY II, AND LESS THAN 420 FEET HIGH SECTIONS 403.2.3.1 THROUGH 403.2.3.4 DO NOT APPLY HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 3 Section Requirement Provided? Comment 403.2.3.1 Wall assembly. The wall assemblies making up the enclosures for interior exit stairwaysand elevator hoistway enclosures shall meet or exceed Soft Body Impact Classification Level 2 as measured by the test method described in ASTM C 1629/C 1629M. NO SEE RESPONSE TO SECTION 403.2.3 403.2.3.2 Wall assembly materials. The face of the wall assemblies making up the enclosures for interior exit stairways and elevator hoistway enclosures that are not exposed to the interior of the enclosures for interior exit stairways or elevator hoistway enclosure shall be constructed in accordance with one of the following methods: 1. The wall assembly shall incorporate no fewer than two layers of impact-resistant construction board each of which meets or exceeds Hard Body Impact Classification Level 2 as measured by the test method described in ASTM C 1629/C 1629M. 2. The wall assembly shall incorporate no fewer than one layer of impact-resistant construction material that meets or exceeds Hard Body Impact Classification Level 3 as measured by the test method described in ASTM C 1629/C 1629M. 3. The wall assembly incorporates multiple layers of any material, tested in tandem, that meets or exceeds Hard Body Impact Classification Level 3 as measured by the test method described in ASTM C 1629/C 1629M. NO NO NO SEE RESPONSE TO SECTION 403.2.3 SEE RESPONSE TO SECTION 403.2.3 SEE RESPONSE TO SECTION 403.2.3 403.2.3.3 Concrete and masonry walls. Concrete or masonry walls shall be deemed to satisfy the requirements of Sections 403.2.3.1 and 403.2.3.2. NO SEE RESPONSE TO SECTION 403.2.3 403.2.3.4 Other wall assemblies. Any other wall assembly that provides impact resistance equivalent to that required by Sections 403.2.3.1 and 403.2.3.2 for Hard Body Impact Classification Level 3, as measured by the test method described in ASTM C 1629/C 1629M, shall be permitted. NO SEE RESPONSE TO SECTION 403.2.3 HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 4 Section Requirement Provided? Comment 403.2.4 Sprayed fire-resistant materials (SFRM). The bond strength of the SFRM installed throughout the building shall be in accordance with Table 403.2.4. YES SFRM PROVIDED AT THE SUBJECT PROJECT, IF ANY, WILL COMPLY WITH THE REQUIREMENT OF TABLE 403.2.4, FOR BUILDINGS LESS THAN 420 FT IN HEIGHT. (430 psf, MIN) 403.3 [F] Automatic sprinkler system. Buildings and structures shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and a secondary water supply where required by Section 403.3.3. Exception: An automatic sprinkler system shall not be required in spaces or areas of: 1. Open parking garages in accordance with Section 406.5. 2. Telecommunications equipment buildings used exclusively for telecommunications equipment, associated electrical power distribution equipment, batteries and standby engines, provided that those spaces or areas are equipped throughout with an automatic fire detection system in accordance with Section 907.2 and are separated from the remainder of the building by not less than 1-hour fire barriers constructed in accordance with Section 707 or not less than 2-hour horizontal assemblies constructed in accordance with Section 711, or both. YES YES NO THE SUBJECT PROJECT WILL BE EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1. SECONDARY WATER SUPPLY NOT REQUIRED. SEE RESPONSE TO SECTION 403.3.3 OPEN PARKING GARAGES WILL BE PROVIDED WITH SPRINKLER SYSTEM 403.3.1 [F] Number of sprinkler risers and system design. Each sprinkler system zone in buildings that are more than 420 feet (128 000 mm) in building height shall be supplied by no fewer than two risers. Each riser shall supply sprinklers on alternate floors. If more than two risers are provided for a zone, sprinklers on adjacent floors shall not be supplied from the same riser. NO SUBJECT PROJECT IS LESS THAN 420 FT IN HEIGHT 403.3.1.1 [F] Riser location. Sprinkler risers shall be placed in interior exit stairways and ramps that are remotely located in accordance with Section 1007.1. YES RISERS SHALL BE LOCATED IN INTERIOR EXIT STAIRWAYS. EXCEPTION #2 TO SECTION 1007.1.1 HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 5 Section Requirement Provided? Comment REQUIRES THAT THE SEPARATION DISTANCE BETWEEN EXITS IN BUILDINGS EQUIPPED WITH AUTOMATIC SPRINKLERS SHALL BE NO LESS THAN ONE-THIRD OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA SERVED. -AT THE SUBJECT PROJECT, THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA SERVED IS 275 FT. -THE SEPARATION DISTANCE BETWEEN THE EXIT STAIRWELLS IS 118 FT. -ONE-THIRD OF 275 FT = 92 FT. -(118 FT IS GREATER THAN 92 FT.) 403.3.2 [F] Water supply to required fire pumps. In buildings that are more than 420 feet (128 000 mm) in building height, required fire pumps shall be supplied by connections to no fewer than two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate. Exception: Two connections to the same main shall be permitted provided the main is valved such that an interruption can be isolated so that the water supply will continue without interruption through no fewer than one of the connections. NO SUBJECT PROJECT IS LESS THAN 420 FEET IN HEIGHT 403.3.3 [F] Secondary water supply. An automatic secondary on-site water supply having a capacity not less than the hydraulically calculated sprinkler demand, including the hose stream requirement, shall be provided for high- rise buildings assigned to Seismic Design Category C, D, E or F as determined by Section 1613. An additional fire pump shall not be required for the secondary water supply unless needed to provide the minimum design intake pressure at the suction side of the fire pump supplying the NO SUBJECT PROJECT IS SEISMIC DESIGN CATEGORY B. HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 6 Section Requirement Provided? Comment automatic sprinkler system. The secondary water supply shall have a duration of not less than 30 minutes. 403.3.4 [F] Fire pump room. Fire pumps shall be located in rooms protected in accordance with Section 913.2.1 YES NOTED: SECTION 913.2.1 REQUIRES THAT FIRE PUMPS SHALL BE LOCATED IN ROOMS THAT ARE SEPARATED FROM ALL OTHER AREAS OF THE BUILDING BY 2-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707, OR 2-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH. AT THE SUBJECT PROJECT, THE FIRE PUMP WILL BE ENCLOSED BY 2-HOUR FIRE BARRIERS AND 2-HOUR HORIZONTAL ASSEMBLIES. 403.4 [F] Emergency systems. The detection, alarm and emergency systems of high- rise buildings shall comply with Sections 403.4.1 through 403.4.8. (SEE RESPONSES TO SECTIONS 403.4.1 THROUGH 403.4.8, BELOW.) 403.4.1 [F] Smoke detection. Smoke detection shall be provided in accordance with Section 907.2.13.1. YES SECTION 907.2.13.1 REQUIRES SMOKE DETECTION THAT IS CONNECTED TO AN AUTOMATIC FIRE ALARM SYSTEM. ACTIVATION OF ANY DETECTOR SHALL ACTIVATE THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM IN ACCORDANCE WITH SECTION 907.5.2.2. AUTOMATIC SMOKE DETECTION THAT ACTIVATES THE OCCUPANT NOTIFICATION SYSTEM IN ACCORDANCE WITH SECTION 907.5 SHALL BE INSTALLED IN GROUP R-2 OCCUPANCIES FOR STUDENT HOUSING AT: -COMMON SPACES OUTSIDE DWELLING OR SLEEPING UNITS -LAUNDRY ROOMS, MECH ROOMS, STORAGE ROOMS -ALL INTERIOR CORRIDORS SERVING DWELLING UNITS OR SLEEPING UNITS HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 7 Section Requirement Provided? Comment -MECHANICAL, ELECTRICAL, TRANSFORMER, OR TELEPHONE ROOMS THAT ARE NOT PROVIDED WITH AUTOMATIC SPRINKLERS -IN ALL ELEVATOR MACHINE ROOMS CONTROL ROOMS AND LOBBIES DUCT SMOKE DETECTION REQUIRED AT: -IN THE MAIN RETURN AND EXHAUST AIR PLENUM OF EACH AIR-CONDITIONING SYSTEM HAVING A CAPACITY GREATER THAN 2,000 CFM. -AT EACH CONNECTION TO A VERTICAL DUCT OR RISER SERVING TWO OR MORE STORIES. -IN GROUP R-2 OCCUPANCY, A SMOKE DETECTOR IS ALLOWED TO BE USED IN EACH RETURN AIR RISER CARRYING NOT MORE THAN 5,000 CFM AND SERVING NOT MORE THAN 10 AIR INLET OPENINGS. 403.4.2 [F] Fire alarm system. A fire alarm system shall be provided in accordance with Section 907.2.13. NO SECTION 907.2.9.1 REQUIRES THAT A MANUAL FIRE ALARM SYSTEM THAT ACTIVATES THE OCCUPANT NOTIFICATION SYSTEM SHALL BE INSTALLED (SEE EXCEPTION) EXCEPTION #2 (907.2.9.1): MANUAL FIRE ALARM BOXES ARE NOT REQUIRED AT GROUP R-2 OCCUPANCIES WHERE THE BUILDING IS EQUIPPED WITH AUTOMATIC SPRINKLERS AND THE OCCUPANT NOTIFICATION APPLIANCES WILL AUTOMATICALLY ACTIVATE THROUGHOUT THE NOTIFICATION ZONES UPON A SPRINKLER WATER FLOW AT THE SUBJECT PROJECT, MANUAL FIRE ALARM BOXES ARE NOT REQUIRED IN THE R-2 PORTIONS OF THE BUILDING HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 8 Section Requirement Provided? Comment 403.4.3 [F] Standpipe system. A high-rise building shall be equipped with a standpipe system as required by Section 905.3. YES (CLASS I) CLASS I STANDPIPES ARE ALLOWED IN BUILDINGS AND BASEMENTS EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM. AT THE SUBJECT PROJECT, AUTOMATIC SPRINKLER SYSTEMS WILL BE PROVIDED. CLASS I STANDPIPES ARE ALLOWED AND WILL BE PROVIDED 403.4.4 [F] Emergency voice/alarm communication system. An emergency voice/alarm communication system shall be provided in accordance with Section 907.5.2.2 YES IN HIGH-RISE BUILDINGS, THE SYSTEM SHALL OPERATE ON AT LEAST THE ALARMING FLOOR, THE FLOOR ABOVE AND THE FLOOR BELOW. AT THE SUBJECT PROJECT, THE EMERGENCY VOICE/ALARM SYSTEM WILL BE SO CONFIGURED. 403.4.5 [F] Emergency responder radio coverage. Emergency responder radio coverage shall be provided in accordance with Section 510 of the International Fire Code. YES EMERGENCY RESPONDER RADIO COVERAGE WILL BE PROVIDED AT THE SUBJECT PROJECT 403.4.6 [F] Fire command. A fire command center complying with Section 911 shall be provided in a location approved by the fire department. YES A FIRE COMMAND CENTER WILL BE PROVIDED AT GRADE LEVEL AT THE SUBJECT PROJECT 403.4.7 Smoke removal. To facilitate smoke removal in post-fire salvage and overhaul operations, buildings and structures shall be equipped with natural or mechanical ventilation for removal of products of combustion in accordance with one of the following: 1. Easily identifiable, manually operable windows or panels shall be distributed around the perimeter of each floor at not more than 50-foot (15 240 mm) intervals. The area of operable windows or panels shall be not less than 40 square feet (3.7 m2) per 50 linear feet (15 240 mm) of perimeter. Exceptions: 1. In Group R-1 occupancies, each sleeping unit or suite having an exterior wall shall be permitted to be provided with 2 square YES YES AT THE SUBJECT PROJECT, ON THE RESIDENTIAL FLOORS, MANUALLY OPERABLE WINDOWS WILL BE DISTRIBUTED AROUND THE PERIMETER OF EACH FLOOR AT NOT MORE THAN 50 FT INTERVALS. THE HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 9 Section Requirement Provided? Comment feet (0.19 m2) of venting area in lieu of the area specified in Item 1. 2. Windows shall be permitted to be fixed provided that glazing can be cleared by fire fighters. 2. Mechanical air-handling equipment providing one exhaust air change every 15 minutes for the area involved. Return and exhaust air shall be moved directly to the outside without recirculation to other portions of the building. 3. Any other approved design that will produce equivalent results. YES AT THE FIRST FLOOR NON-GARAGE PORTIONS AND IN THE BASEMENT AT THE SUBJECT PROJECT, SMOKE EXHAUST FANS WILL BE PROVIDED THAT WILL EXHAUST THE NON-RESIDENTIAL SPACES AT A MINIMUM RATE OF ONE FULL AIR-CHANGE EVERY 15 MINUTES. FOR SMOKE REMOVAL AT THE OPEN PARKING GARAGE PORTION OF THE PROJECT EXTERIOR WALL OPENINGS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 406.5.2. 403.4.8 [F] Standby and emergency power. A standby power system complying with Section 2702 and Section 3003 shall be provided for the standby power loads specified in Section 403.4.8.3. An emergency power system complying with Section 2702 shall be provided for the emergency power loads specified in Section 403.4.8.4. YES (SEE RESPONSES TO SECTIONS 403.4.8.3 AND 403.4.8.4, BELOW.) 403.4.8.1 [F] Equipment room. If the standby or emergency power system includes a generator set inside a building, the system shall be located in a separate room enclosed with 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. System supervision with manual start and transfer features shall be provided at the fire command center. YES AT THE SUBJECT PROJECT, ALL INTERNAL GENERATORS PROVIDED WILL BE ENCLOSED BY 2- HOUR FIRE BARRIERS AND 2-HOUR HORIZONTAL ASSEMBLIES. 403.4.8.2 [F] Fuel line piping protection. Fuel lines supplying a generator set inside a building shall be separated from areas of the building other than the room the generator is located in by an approved method or assembly that has a fire-resistance rating of not less than 2 hours. Where the building is protected throughout with an automatic sprinkler system installed in YES NOTED: ALL INTERNAL GENERATOR FUEL LINE PIPING, IF REQUIRED AT THE SUBJECT PROJECT, WILL BE SEPARATED FROM THE REST OF THE BUILDING BY ASSEMBLIES THAT HAVE A FIRE RESISTANCE RATING OF NOT LESS THAN 2-HOURS HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 10 Section Requirement Provided? Comment accordance with Section 903.3.1.1 or 903.3.1.2, the required fire-resistance rating shall be reduced to 1 hour. 403.4.8.3 [F] Standby power loads. The following are classified as standby power loads: 1. Power and lighting for the fire command center required by Section 403.4.6. 2. Ventilation and automatic fire detection equipment for smokeproof enclosures. 3. Elevators. 4. Where elevators are provided in a high-rise building for accessible means of egress, fire service access or occupant self-evacuation, the standby power system shall also comply with Sections 1009.4, 3007 or 3008, as applicable. YES NO AT THE SUBJECT PROJECT, THE POWER AND LIGHTING FOR THE FIRE COMMAND CENTER, THE VENTILATION AND AUTOMATIC FIRE DETECTION EQUIPMENT FOR THE SMOKEPROOF ENCLOSURES, AND THE ELEVATORS FOR BUILDING 1 AND BUILDING 2 (OPERATION CIRCUITS), WILL BE CONNECTED TO THE STANDBY POWER SYSTEM. ELEVATORS ARE NOT BEING PROVIDED AT THE SUBJECT PROJECT FOR ACCESSIBLE MEANS OF EGRESS, FIRE SERVICE ACCESS OR OCCUPANT SELF-EVACUATION. CONDITION #4 IS NOT APPLICABLE. (SEE RESPONSES TO SECTIONS 403.6.1 AND 403.6.2, BELOW.) 403.4.8.4 [F] Emergency power loads. The following are classified as emergency power loads: 1. Exit signs and means of egress illumination required by Chapter 10. 2. Elevator car lighting. 3. Emergency voice/alarm communications systems. 4. Automatic fire detection systems. 5. Fire alarm systems. YES AT THE SUBJECT PROJECT, THE EXIT SIGNAGE, THE MEANS OF EGRESS ILLUMINATION, THE ELEVATOR CAR LIGHTING, THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM, THE AUTOMATIC FIRE DETECTION SYSTEMS, THE FIRE ALARM SYSTEMS, AND THE FIRE PUMP (IF ELECTRICALLY POWERED) WILL BE CONNECTED TO THE EMERGENCY POWER SYSTEM. HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 11 Section Requirement Provided? Comment 6. Electrically powered fire pumps. 403.5 Means of egress and evacuation. The means of egress in high-rise buildings shall comply with Sections 403.5.1 through 403.5.6. (SEE RESPONSES TO SECTIONS 403.5.1 THROUGH 403.5.6, BELOW) 403.5.1 Remoteness of interior exit stairways. Required interior exit stairways shall be separated by a distance not less than 30 feet (9144 mm) or not less than one-fourth of the length of the maximum overall diagonal dimension of the building or area to be served, whichever is less. The distance shall be measured in a straight line between the nearest points of the enclosure surrounding the interior exit stairways. In buildings with three or more interior exit stairways, no fewer than two of the interior exit stairways shall comply with this section. Interlocking or scissor stairs shall be counted as one interior exit stairway. YES THE RESIDENTIAL PORTION OF THE SUBJECT PROJECT WILL BE EGRESSED BY TWO STAIRS. -THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA SERVED AT THE SUBJECT PROJECT IS 275 FT. -ONE-FOURTH OF 275 FT = 69 FT. -THE DISTANCE BETWEEN THE MOST REMOTE TWO OF THE THREE STAIRS IS 118 FT. (145 FT IS GREATER THAN 69 FT.) 403.5.2 Additional interior exit stairway. For buildings other than Group R-2 that are more than 420 feet (128 000 mm) in building height, one additional interior exit stairway meeting the requirements of Sections 1011 and 1023 shall be provided in addition to the minimum number of exits required by Section 1006.3. The total width of any combination of remaining interior exit stairways with one interior exit stairway removed shall be not less than the total width required by Section 1005.1. Scissor stairways shall not be considered the additional interior exit stairway required by this section. NO NOT APPLICABLE: SUBJECT PROJECT IS REQUIRED TO BE EGRESSED BY TWO STAIRS ONLY (THREE EXIT STAIRS BEING PROVIDED) 403.5.3 Stairway door operation. Stairway doors other than the exit discharge doors shall be permitted to be locked from the stairway side. Stairway doors that are locked from the stairway side shall be capable of being unlocked simultaneously without unlatching upon a signal from the fire command center. YES AT THE SUBJECT PROJECT, THE THREE 5-STORY STAIR TOWERS THAT SERVE THE RESIDENTIAL AND PARKING FLOORS WILL BE LOCKED FROM THE INSIDE. ELECTRIC LATCHES THAT CAN BE SIGNALED FROM THE FIRE COMMAND CENTER WILL BE PROVIDED AT THE LOCKED OPENINGS HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 12 Section Requirement Provided? Comment 403.5.3.1 Stairway communication system. A telephone or other two-way communications system connected to an approved constantly attended station shall be provided at not less than every fifth floor in each stairway where the doors to the stairway are locked. YES A TWO-WAY COMMUNICATIONS SYSTEM WILL BE PROVIDED IN EACH LOCKED STAIR AT THE SUBJECT PROJECT, AT THE THIRD FLOOR LEVEL. THE COMMUNICATION SYSTEM WILL CONNECT TO THE LOBBY FRONT DESK WHICH WILL BE CONRINUOUSLY ATTENDED. 403.5.4 Smokeproof enclosures. Every required interior exit stairway serving floors more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access shall be a smokeproof enclosure in accordance with Sections 909.20 and 1023.10. YES AT THE SUBJECT PROJECT, THE THREE STAIR TOWERS THAT SERVE THE RESIDENTIAL AND PARKING FLOORS WILL BE DESIGNED AS SMOKEPROOF ENCLOSURES 403.5.5 Luminous egress path markings. Luminous egress path markings shall be provided in accordance with Section 1025. NO NOT APPLICABLE: SECTION 1025 REQUIRES LUMINOUS EGRESS PATH MARKINGS IN HIGH-RISE BUILDINGS OF A, B, E, I, M, AND R-1 OCCUPANCIES, ONLY. THE STAIRS AT THE SUBJECT PROJECT SERVE R-2 AND S-2 OCCUPANCIES. LUMINOUS EGRESS PATH MARKINGS ARE NOT REQUIRED. 403.5.6 Emergency escape and rescue. Emergency escape and rescue openings specified in Section 1030 are not required. NO NOT APPLICABLE: EMERGENCY ESCAPE AND RESCUE OPENINGS ARE NOT REQUIRED IN SPRINKLERED BUILDINGS ON FLOORS THAT ARE SERVED BY TWO EXIT STAIRS 403.6 Elevators. Elevator installation and operation in high-rise buildings shall comply with Chapter 30 and Sections 403.6.1 and 403.6.2 (SEE RESPONSES TO SECTIONS 403.6.1 AND 403.6.2, BELOW) 403.6.1 Fire service access elevator. In buildings with an occupied floor more than 120 feet (36 576 mm) above the lowest level of fire department vehicle access, no fewer than two fire service access elevators, or all elevators, whichever is less, shall be provided in accordance with Section 3007. Each fire service access elevator shall have a capacity of not less than 3,500 pounds (1588 kg) and shall comply with Section 3002.4. NO NOT APPLICABLE: HIGHEST OCCUPIED FLOOR AT SUBJECT PROJECT IS LESS THAN 120 FT ABOVE LOWEST LEVEL OF FIRE DEPARTMENT ACCESS FIRE SERVICE ACCESS ELEVATORS WILL NOT BE PROVIDED. HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 13 Section Requirement Provided? Comment 403.6.2 Occupant evacuation elevators. Where installed in accordance with Section 3008, passenger elevators for general public use shall be permitted to be used for occupant self-evacuation. NO NOT APPLICABLE: ELEVATORS AT THE SUBJECT PROJECT WILL NOT BE USED FOR OCCUPANT SELF- EVACUATION OCCUPANT SELF-EVACUATION ELEVATORS WILL NOT BE PROVIDED From INTERNATIONAL FIRE CODE Section Requirement Provided? Comment 508.1.2 Separation. The fire command center shall be separated from the remainder of the building by not less than a 1-hour fire barrier constructed in accordance with Section 707 of the International Building Code or horizontal assembly constructed in accordance with Section 711 of the International Building Code, or both. YES AT THE SUBJECT PROJECT, THE FIRE COMMAND CENTER WILL BE SEPARATED FROM THE REST OF THE BUILDING BY 1-HOUR FIRE BARRIER CONSTRUCTION OR BY 1-HOUR HORIZONTAL ASSEMBLIES 508.1.3 Size. The fire command center shall be not less than 200 square feet (19 m2) in area with a minimum dimension of 10 feet (3048 mm). YES AT THE SUBJECT PROJECT, THE FIRE COMMAND CENTER WILL BE A MINIMUM OF 200 SF IN AREA WITH A MINIMUM DIMENSION OF 10 FEET. 508.1.6 Required features. The fire command center shall comply with NFPA 72 and shall contain the following features: 1. The emergency voice/alarm communication system control unit. 2. The fire department communications system. 3. Fire detection and alarm system annunciator. 4. Annunciator unit visually indicating the location of the elevators and whether they are operational. 5. Status indicators and controls for air distribution systems. YES (ALL) THE FCC SHALL CONTAIN THE CITED FEATURES HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 14 Section Requirement Provided? Comment 6. The fire fighter’s control panel required by Section 909.16 for smoke control systems installed in the building. 7. Controls for unlocking stairway doors simultaneously. 8. Sprinkler valve and water-flow detector display panels. 9. Emergency and standby power status indicators. 10. A telephone for fire department use with controlled access to the public telephone system. 11. Fire pump status indicators. 15. Generator supervision devices, manual start and transfer features. 16. Public address system, where specifically required by other sections of this code. 17. Elevator fire recall switch in accordance with ASME A17.1. 18. Elevator emergency or standby power selector switch(es), where emergency or standby power is provided. 903.2.11.3 Buildings 55 feet or more in height. An automatic sprinkler system shall be installed throughout buildings that have one or more stories with an occupant load of 30 or more located 55 feet (16 764 mm) or more above the lowest level of fire department vehicle access, measured to the finished floor. Exceptions: 1. Open parking structures. 2. Occupancies in Group F-2. YES THE SUBJECT PROJECT HAS AT LEAST ONE STORY WITH AN OCCUPANT LOAD OF 30 OR MORE THAT IS AT LEAST 55 FEET ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT ACCESS. THE SUBJECT WILL BE EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM THE OPEN PARKING STRUCTURE IS PART OF THE SAME BUILDING AS THE R-2 OCCUPANCY. OPEN PARKING STRUCTURE SHALL BE PROVIDED WITH AN AUTOMATIC SPRINKLER SYSTEM HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 15 Section Requirement Provided? Comment 903.4.3 Floor control valves. Approved supervised indicating control valves shall be provided at the point of connection to the riser on each floor in high-rise buildings YES AT THE SUBJECT PROJECT, SUPERVISED INDICATING CONTROL VALVES WILL BE PROVIDED IN THE AUTOMATIC SPRINKLER SYSTEMS AT THE POINT OF CONNECTION TO THE RISER ON EACH FLOOR 907.2 FIRE ALARM AND DETECTION SYSTEMS - Where required—new buildings and structures. 907.2.9 Group R-2. Fire alarm systems and smoke alarms shall be installed in Group R-2 occupancies as required in Sections 907.2.9.1 and 907.2.9.3. 907.2.9.1 Manual fire alarm system. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group R-2 occupancies where any of the following conditions apply: 1. Any dwelling unit or sleeping unit is located three or more stories above the lowest level of exit discharge. 2. Any dwelling unit or sleeping unit is located more than one story below the highest level of exit discharge of exits serving the dwelling unit or sleeping unit. 3. The building contains more than 16 dwelling units or sleeping units. Exceptions: 1. A fire alarm system is not required in buildings not more than two stories in height where all dwelling units or sleeping units and contiguous attic and crawl spaces are separated from each other and public or common areas by not less than 1-hour fire partitions and each dwelling unit or sleeping unit has an exit directly to a public way, egress court or yard. NO REQUIRED (BUT EXCEPTED), SEE EXCEPTION #2 BELOW. MANUAL ALARMS NOT REQUIRED WHERE SPRINKLERS ARE PROVIDED AND THE SPRINKLER FLOW DETECTORS ARE CONNECTED TO THE OCCUPANT NOTIFICATION SYSTEM. HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 16 Section Requirement Provided? Comment 2. Manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 and the occupant notification appliances will automatically activate throughout the notification zones upon a sprinkler water flow. 3. A fire alarm system is not required in buildings that do not have interior corridors serving dwelling units and are protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, provided that dwelling units either have a means of egress door opening directly to an exterior exit access that leads directly to the exits or are served by open-ended corridors designed in accordance with Section 1027.6, Exception 3. APPLIES (EXCEPTION APPLIES. MANUAL FIRE ALARMS NOT REQUIRED) 907.2.9.2 Smoke alarms. Single- and multiple-station smoke alarms shall be installed in accordance with Section 907.2.11. 907.2.11.2 Groups R-2, R-3, R-4 and I-1. Single or multiple-station smoke alarms shall be installed and maintained in Groups R-2, R-3, R-4 and I-1 regardless of occupant load at all of the following locations: 1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms. 2. In each room used for sleeping purposes. 3. In each story within a dwelling unit, including basements but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level. YES SMOKE ALARMS SHALL BE INSTALLED IN R-2 OCCUPANCY SPACES IN THE CITED LOCATIONS 907.2.11.5 Interconnection. Where more than one smoke alarm is required to be installed within an individual dwelling unit or sleeping unit in Group R or I- YES ALARMS SHALL BE INTERCONNECTED HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 17 Section Requirement Provided? Comment 1 occupancies, the smoke alarms shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the individual unit. Physical interconnection of smoke alarms shall not be required where listed wireless alarms are installed and all alarms sound upon activation of one alarm. The alarm shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed. 907.2.11.6 Power source. In new construction, required smoke alarms shall receive their primary power from the building wiring where such wiring is served from a commercial source and shall be equipped with a battery backup. Smoke alarms with integral strobes that are not equipped with battery back- up shall be connected to an emergency electrical system in accordance with Section 604. Smoke alarms shall emit a signal when the batteries are low. Wiring shall be permanent and without a disconnecting switch other than as required for overcurrent protection YES ALARMS SHALL RECEIVE THEIR POWER FROM THE BUILDING PRIMARY WIRING 907.2.13 High-rise buildings. High-rise buildings shall be provided with an automatic smoke detection system in accordance with Section 907.2.13.1, a fire department communication system in accordance with Section 907.2.13.2 and an emergency voice/alarm communication system in accordance with Section 907.5.2.2. Exceptions: 1. Airport traffic control towers in accordance with Section 907.2.22 of this code and Section 412 of the International Building Code. 2. Open parking garages in accordance with Section 406.5 of the International Building Code. 4. Buildings with an occupancy in Group A-5 in accordance with Section 303.1 of the International Building Code. 3. Low-hazard special occupancies in accordance with Section 503.1.1 of the International Building Code. YES NO NOTE EXCEPTION BELOW AUTOMATIC SMOKE DETECTION NOT REQUIRED IN OPEN PARKING GARAGE SECTION OF PROJECT (NOTE: AUTOMATIC SMOKE DETECTION STILL REQUIRED IN ENCLOSED PARKING GARAGE – BASEMENT) HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 18 Section Requirement Provided? Comment 5. Buildings with an occupancy in Group H-1, H-2 or H-3 in accordance with Section 415 of the International Building Code. 6. In Group I-1 and I-2 occupancies, the alarm shall sound at a constantly attended location and occupant notification shall be broadcast by the emergency voice/alarm communication system. 907.2.13.1 Automatic smoke detection. Automatic smoke detection in high-rise buildings shall be in accordance with Sections 907.2.13.1.1 and 907.2.13.1.2. 907.2.13.1.1 Area smoke detection. Area smoke detectors shall be provided in accordance with this section. Smoke detectors shall be connected to an automatic fire alarm system. The activation of any detector required by this section shall activate the emergency voice/alarm communication system in accordance with Section 907.5.2.2. In addition to smoke detectors required by Sections 907.2.1 through 907.2.10, smoke detectors shall be located as follows: 1. In each mechanical equipment, electrical, transformer, telephone equipment or similar room that is not provided with sprinkler protection. 2. In each elevator machine room, machinery space, control room and control space and in elevator lobbies. YES YES AREA SMOKE DETECTION SHALL BE PROVIDED AT CITED AREAS NOTE: REQUIRED ONLY IN EQUIPMENT ROOMS NOT PROTECTED BY SPRINKLERS 907.2.13.1.2 [M] Duct smoke detection. Duct smoke detectors complying with Section 907.3.1 shall be located as follows: 1. In the main return air and exhaust air plenum of each air-conditioning system having a capacity greater than 2,000 cubic feet per minute (cfm) (0.94 m3/s). Such detectors shall be located in a serviceable area downstream of the last duct inlet. YES YES DUCT SMOKE DETECTION SHALL BE PROVIDED HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 19 Section Requirement Provided? Comment 2. At each connection to a vertical duct or riser serving two or more stories from a return air duct or plenum of an air-conditioning system. In Group R-1 and R-2 occupancies, a smoke detector is allowed to be used in each return air riser carrying not more than 5,000 cfm (2.4 m3/s) and serving not more than 10 air-inlet openings. 907.2.13.2 Fire department communication system. Where a wired communication system is approved in lieu of an emergency responder radio coverage system in accordance with Section 510, the wired fire department communication system shall be designed and installed in accordance with NFPA 72 and shall operate between a fire command center complying with Section 508, elevators, elevator lobbies, emergency and standby power rooms, fire pump rooms, areas of refuge and inside interior exit stairways. The fire department communication device shall be provided at each floor level within the interior exit stairway. NO AN EMERGENCY RESPONDER RADIO COVERAGE SYSTEM SHALL BE PROVIDED. A WIRED FD COMMUNICATION SYSTEM WILL NOT BE NECESSARY 907.6 FIRE ALARM AND DETECTION SYSTEMS - Installation and monitoring 907.6.4 Zones. Each floor shall be zoned separately and a zone shall not exceed 22,500 square feet (2090 m2). The length of any zone shall not exceed 300 feet (91 440 mm) in any direction YES FIRE ALARM AND DETECTON SYSTEM DESIGN SHALL COMPLY 907.6.4.2 High-rise buildings. In high-rise buildings, a separate zone by floor shall be provided for each of the following types of alarm-initiating devices where provided: 1. Smoke detectors. 2. Sprinkler waterflow devices. 3. Manual fire alarm boxes. 4. Other approved types of automatic fire detection devices or suppression systems. YES (ALL) AT THE SUBJECT PROJECT, SEPARATE ZONES IDENTIFIED BY FLOOR SHALL BE PROVIDED FOR THE SMOKE DETECTION SYSTEMS, THE SPRINKLER WATERFLOW NOTIFICATION DEVICES, AND THE MANUAL FIRE ALARM BOXES PROVIDED. HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 20 914.3 High-rise buildings 914.3.1 Automatic sprinkler system. Buildings and structures shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and a secondary water supply where required by Section 914.3.3. Exception: An automatic sprinkler system shall not be required in spaces or areas of: 1. Open parking garages in accordance with Section 406.5 of the International Building Code. 2. Telecommunications equipment buildings used exclusively for telecommunications equipment, associated electrical power distribution equipment, batteries and standby engines, provided that those spaces or areas are equipped throughout with an automatic fire detection system in accordance with Section 907.2 and are separated from the remainder of the building by not less than 1-hour fire barriers constructed in accordance with Section 707 of the International Building Code or not less than 2-hour horizontal assemblies constructed in accordance with Section 711 of the International Building Code, or both. YES YES NO OPEN PARKING GARAGES WILL BE PROVIDED WITH SPRINKLER SYSTEM 914.3.1.1 Number of sprinkler risers and system design. Each sprinkler system zone in buildings that are more than 420 feet (128 m) in height shall be supplied by no fewer than two risers. Each riser shall supply sprinklers on alternate floors. If more than two risers are provided for a zone, sprinklers on adjacent floors shall not be supplied from the same riser. NO PROJECT IS LESS THAN 420 FT IN HEIGHT 914.3.1.2] Water supply to required fire pumps. In buildings that are more than 420 feet (128 m) in building height, required fire pumps shall be supplied by connections to no fewer than two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate. NO ROJECT IS LESS THAN 420 FT IN HEIGHT HUB ON CAMPUS FORT COLLINS Fort Collins, Colorado IBC/IFC High-Rise Requirements Compliance Matrix – BUILDING 1 November 3, 2017 21 Exception: Two connections to the same main shall be permitted provided the main is valved such that an interruption can be isolated so that the water supply will continue without interruption through no fewer than one of the connections. 914.3.3 Fire alarm system. A fire alarm system shall be provided in accordance with Section 907.2.13. YES FIRE ALARM SYSTEM SHALL BE PROVIDED 914.3.4 Automatic smoke detection. Smoke detection shall be provided in accordance with Section 907.2.13.1. YES AUTOMATIC SMOKE DETECTION SHALL BE PROVIDED 914.3.5 Emergency voice/alarm communication system. An emergency voice/alarm communication system shall be provided in accordance with Section 907.5.2.2. YES EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM SHALL BE PROVIDED 914.3.6 Emergency responder radio coverage. Emergency responder radio coverage shall be provided in accordance with Section 510. YES ERRC SYSTEM COVERAGE SHALL BE PROVIDED 914.3.7 Fire command. A fire command center complying with Section 508 shall be provided in a location approved by the fire department. YES AN FCC SHALL BE PROVIDED AGGREGATE AREA OF THE WINDOWS WILL BE NOT LESS THAN 40 SF PER 50 LINEAL FEET.