UNIT LOAD CALC - NEC 220.82 ("A" UNITS) GENERAL LOADS - NEC 220.82 (B) 1. GENERAL LIGHTING AND GENERAL-USE RECEPTACLES 564 SQ/FT @ 3 VA = 1692 VA 2. SMALL APPLIANCE AND LAUNDRY LOADS NEC 210.11(C )(1) AND (C )(2) SMALL APPLIANCE 2 X 1,500VA 3000 VA VA 3.a APPLIANCE LOADS (NEC 250.53) DISHWASHER = 1200 VA DISPOSAL = 850 VA MICROWAVE/HOOD = 1200 VA REFRIGERATOR = 800 VA 3.b ELECTRIC RANGES AND OTHER COOKING APPLIANCES ELECTRIC COOKTOP = 1200 VA 3.c ELECTRIC CLOTHES DRYER VA 3.d WATER HEATERS VA SUB TOTAL 9942 VA FIRST 10,000VA @ 100 % - 10,000 VA = -58 VA REMAINDER @23% -58 X 23% -13.34 VA SUB TOTAL #1 9,987 HEATING AND AIR CONDITIONING LOADS - NEC 220.82© VTAC @ 100% = 1165 VA SUB TOTAL #2 1165 VA TOTAL LOAD 11,152 VA 208V, 1 PHASE 53.6 AMPS UNIT LOAD CALC - NEC 220.82 ("B" UNITS) GENERAL LOADS - NEC 220.82 (B) 1. GENERAL LIGHTING AND GENERAL-USE RECEPTACLES 627 SQ/FT @ 3 VA = 1881 VA 2. SMALL APPLIANCE AND LAUNDRY LOADS NEC 210.11(C )(1) AND (C )(2) SMALL APPLIANCE 2 X 1,500VA 3000 VA VA 3.a APPLIANCE LOADS (NEC 250.53) DISHWASHER = 1200 VA DISPOSAL = 850 VA MICROWAVE/HOOD = 1200 VA REFRIGERATOR = 800 VA 3.b ELECTRIC RANGES AND OTHER COOKING APPLIANCES ELECTRIC COOKTOP = 1200 VA 3.c ELECTRIC CLOTHES DRYER VA 3.d WATER HEATERS VA SUB TOTAL 10131 VA FIRST 10,000VA @ 100 % - 10,000 VA = 131 VA REMAINDER @23% 131 X 23% 30.13 VA SUB TOTAL #1 10,030 HEATING AND AIR CONDITIONING LOADS - NEC 220.82© VTAC @ 100% = 1165 VA SUB TOTAL #2 1165 VA TOTAL LOAD 11,195 VA 208V, 1 PHASE 53.8 AMPS UNIT LOAD CALC - NEC 220.82 ("C" UNITS) GENERAL LOADS - NEC 220.82 (B) 1. GENERAL LIGHTING AND GENERAL-USE RECEPTACLES 1026 SQ/FT @ 3 VA = 3078 VA 2. SMALL APPLIANCE AND LAUNDRY LOADS NEC 210.11(C )(1) AND (C )(2) SMALL APPLIANCE 2 X 1,500VA 3000 VA VA 3.a APPLIANCE LOADS (NEC 250.53) DISHWASHER = 1200 VA DISPOSAL = 850 VA MICROWAVE/HOOD = 1200 VA REFRIGERATOR = 800 VA 3.b ELECTRIC RANGES AND OTHER COOKING APPLIANCES ELECTRIC COOKTOP = 1200 VA 3.c ELECTRIC CLOTHES DRYER VA 3.d WATER HEATERS VA SUB TOTAL 11328 VA FIRST 10,000VA @ 100 % - 10,000 VA = 1,328 VA REMAINDER @23% 1,328 X 23% 305.44 VA SUB TOTAL #1 10,305 HEATING AND AIR CONDITIONING LOADS - NEC 220.82© VTAC @ 100% = 2527 VA SUB TOTAL #2 2527 VA TOTAL LOAD 12,832 VA 208V, 1 PHASE 61.7 AMPS UNIT LOAD CALC - NEC 220.82 ("P" UNITS) GENERAL LOADS - NEC 220.82 (B) 1. GENERAL LIGHTING AND GENERAL-USE RECEPTACLES 1187 SQ/FT @ 3 VA = 3561 VA 2. SMALL APPLIANCE AND LAUNDRY LOADS NEC 210.11(C )(1) AND (C )(2) SMALL APPLIANCE 2 X 1,500VA 3000 VA VA 3.a APPLIANCE LOADS (NEC 250.53) DISHWASHER = 1200 VA DISPOSAL = 850 VA MICROWAVE/HOOD = 1200 VA REFRIGERATOR = 800 VA 3.b ELECTRIC RANGES AND OTHER COOKING APPLIANCES ELECTRIC COOKTOP = 1200 VA 3.c ELECTRIC CLOTHES DRYER VA 3.d WATER HEATERS VA SUB TOTAL 11811 VA FIRST 10,000VA @ 100 % - 10,000 VA = 1,811 VA REMAINDER @23% 1,811 X 23% 416.53 VA SUB TOTAL #1 10,417 HEATING AND AIR CONDITIONING LOADS - NEC 220.82© FAN COIL UNIT @ 100% = 11400 VA SUB TOTAL #2 11400 VA TOTAL LOAD 21,817 VA 208V, 1 PHASE 104.9 AMPS M 3000A3P 30A3P TVSS 400A3P 800A3P 800A3P 200A3P 400A3P 400A3P 400A3P 400A3P 400A3P 200A3P 200A3P 200A3P BUSSED SPACE 52000AIC UTILITY TRANSFORMER EXTERIOR DETAIL NOTES: 1. SHUNT TRIP CIRCUIT BREAKERS. 2. 16 UNITS TOTAL 3. 20 UNITS TOTAL 4. 21 UNITS TOTAL 5. 4 UNITS TOTAL GENERAL NOTES: 1. ALL PANELBOARDS AND ELECTRICAL DISTRIBUTION EQUIPMENT SHOWN IS NEW UNLESS OTHERWISE NOTED. 2. ALL GROUNDING SHALL BE INSTALLED PER NEC ARTICLE 250. 3. PROVIDE NAMEPLATES FOR ALL SERVICE EQUIPEMENT PER NEC 705.10. FEEDER SCHEDULE ALUMINUM CONDUCTORS ACCEPTED. NOT ALL FEEDERS IN SCHEDULE USED. (4#10 CU, 1#10 CU GND, 1/2"C) - 30A (4#4 CU, 1#8 CU GND, 1 3/4"C) 70A (4#2 AL, 1#6 AL GND, 1 3/4" C) 75A (4#1 CU, 1#8 CU GND, 2"C) 110A (4#1/O AL, 1#6 AL GND, 2"C) 120A (4#3/O CU, 1#6 CU GND, 2"C) 200A (4#250 AL, 1#4 AL GND, 3"C) 205A 2 SETS(4#3/O CU, 1#3 CU GND, 2"C) 400A 2 SETS(4#250 AL, 1#1 AL GND, 3"C) 410A 2 SETS(4#350 CU, 1#1 CU GND, 3"C) 620A 2 SETS(4#500 AL, 1#2/O AL GND, 3 1/2" C) 620A 11 SETS(4#500 CU MCM, 3"C) 4180A 11 SETS(4#500 CU, 1#500 CU GND, 3 1/2"C) 4180A 1 2 3 4 5 6 7 1 7 # 8 NEW CU GND TO COLD WATER BOND AND BLDG STEEL, NEW CU GND TO DRIVERN GND ROD 200A 3P 400A 3P 400A 3P PANEL NEW MAIN DISTRIBUTION CENTER 'MDC' NEMA 1 4000A 120/208V 3PH 4W 65K AIC PANEL PANEL PANEL PANEL PANEL PANEL 800A PANEL PANEL PANEL 200A 3P TRANSITION CABINET PANEL 1ST & 2ND FLR DP1 PANEL UNITS JONNY'S RESTAURANT JDP J1 J2 J3 J4 PANEL JLCP H6 H5 H4 H3 H2 H1 PANEL HLCP JONNY'S RESTAURANT LIGHTING CONTROL PANEL HOTEL LIGHTING CONTROL PANEL 200A3P 600A3P ELV. ELV. B A ELV. C 8 EXTERIOR NEMA 3R CT/MAIN DISCONNECT PANEL DP2A PANEL DP2B PANEL UNITS PANEL UNITS 100A3P PANEL P1 800A3P 800A3P 400A3P 400A3P PANEL PANEL DP3A PANEL UNITS H8 PANEL DP3B PANEL H7 PANEL UNITS PANEL UNITS 3RD FLR 1 1 1 4 3 2 5 4 3 PRELIMIINARY SUITE PANEL SIZES PRELIMINARY PANELS AND FEEDERS SUPPLYING “A” TYPE SUITES SHALL BE SIZED AT 60A, 208 1 PHASE PRELIMINARY PANELS AND FEEDERS SUPPLYING “B” TYPE SUITES SHALL BE SIZED AT 60A, 208 1 PHASE PRELIMINARY PANELS AND FEEDERS SUPPLYING “C” TYPE SUITES SHALL BE SIZED AT 80A, 208 1 PHASE PRELIMINARY PANELS AND FEEDERS SUPPLYING “P” TYPE SUITES SHALL BE SIZED AT 125A, 208 1 PHASE 800A3P M 52000AIC UTILITY TRANSFORMER EXTERIOR 7 TRANSITION CABINET PANEL PL1 100A3P NEMA 3R DISCONNECT WITH FRN FUSES M 100A 208 3PH PANEL 3 * MAIN BONDING JUMPER SHALL BE SIZED AS FOLLOWS: SERVICE SIZE M.B.J. SIZE CU 0-1,000A #3/0 1,200A #4/0 1,600A #250MCM 2,000A #300MCM 2,500A #500MCM 3,000A #500MCM 4,000A #600MCM * GROUNDING ELECTRODE CONDUCTOR BE SIZED AS FOLLOWS: SERVICE SIZE G.E.C. SIZE CU 0-200A #4 201-400A #1/0 OVER 401A #3/0 1 #* CU GROUND TO GROUNDED CONDUCTOR PER ART.250-28 PROVIDE PERMANENT TAG TO IDENTIFY EACH GROUND. FULL WIDTH x 1/2" DEPTH x 2" HIGH BARE COPPER BUS PLATE ATTACHED TO WALL WITH 1/2" SPACERS. REMOVE PAINT AT POINT OF ATTACHMENT TO SWITCHBOARD. 1/2" PORCELAIN INSULATORS 6" O.C. BETWEEN WALL AND COPPER GROUND BAR. 1 #6 CU-3/4" C, TO MAIN TELEPHONE BOARD. FINISH FLOOR 1 # ** CU-3/4"C. TO METAL UNDERGROUND WATER PIPE PER ART. 250.52(a)(1). 1 # ** CU-3/4"C. TO EFFECTIVELY GROUNDED METAL FRAME OF THE BLDG. PER ART. 250.52(a)(2). ONE 20 FT. LENGTH OF #3/0 BARE COPPER ENCASED IN MIN. 2" OF CONCRETE ALL AROUND PER ART. 250.52(a)(3). COPYRIGHT © 2017 PAUL T. BERGNER, AIA, ARCHITECT, PC/ALL RIGHTS RESERVED SHEET NUMBER SHEET TITLE CURRENT PHASE ISSUE DATE WILLCO XIV LLLP PROJECT DEVELOPMENT PLAN JULY 14, 2017 SPIRIT AT THE RIVER FORT COLLINS, COLORADO 11/6/2017 3:28:58 PM E-400 PDP ONE LINE NO. DESCRIPTION DATE N.T.S. 1 PDP -PRELIMINARY ONE-LINE DIAGRAM N.T.S. 2 PDP - SECONDARY ONE DIAGRAM N.T.S. 3 PDP - MAIN SYSTEM GROUND DETAIL