January 06, 2017
Cara Scohy
CS DESIGN, INC.
2519 S. Shields St #129
Fort Collins, CO 80526
RE: 112 W. Magnolia Street Parking Lot, PDP160040, Round Number 1
Comment Summary:
Department: Engineering Development Review
Contact: Morgan Uhlman, 970-416-4334, muhlman@fcgov.com
Topic: General
12/27/2016: The Traffic Signs and Pavement Marking Construction Notes are
missing number 7:
7. Pre-formed thermo-plastic applications shall be as specified in these Plans
and/or these Standards.
Comment Number: 1 Comment Originated: 12/27/2016
12/27/2016: There needs to be a reference to two benchmarks, General Notes #40.
Comment Number: 2 Comment Originated: 12/27/2016
12/27/2016: Please add a legend to all the sheets of the plan set.
Comment Number: 3 Comment Originated: 12/27/2016
12/27/2016: Add the limits of street cut notes to sheet C2.0, C4.0.
Street Cut Note:
Limits of street cut are approximate. Final limits are to be determined in the field by
the City Engineering Inspector. All repairs to be in accordance with City street repair
standards.
Comment Number: 4 Comment Originated: 12/27/2016
12/27/2016: This project is responsible for dedicating any right-of-way and
easements that are necessary or required by the City for this project. This shall
including the standard utility easements that are to be provided behind the
right-of-way, 15 foot along an arterial, 8 foot along an alley, 9 foot along all other
street classifications. This can be done in the platting process or through separate
document if the lot will not be platted. A variance to the LCUASS standard can be
requested (LCUASS 1.9.4) but it may or may not be approved. Information on the
dedication process can be found at: http://www.fcgov.com/engineering/devrev.php
Comment Number: 5 Comment Originated: 12/27/2016
Please see the following summary of comments from City staff and outside reviewing agencies for
your submittal of the above referenced project. If you have questions about any comments, you may
contact the individual commenter or direct your questions through the Project Planner, Meaghan
Overton, at 970-416-2283 or moverton@fcgov.com.
Page 1 of 8
12/27/2016: The applicant will need to obtain access permits from CDOT for
closing the access point on S College Ave.
Comment Number: 6 Comment Originated: 12/27/2016
12/27/2016: On the Utility plans, please ghost the trees (or different visual with less
branches) and any existing sign posts.
Comment Number: 7 Comment Originated: 12/27/2016
12/27/2016: Please label the property line and easements more clearly.
Comment Number: 8 Comment Originated: 12/27/2016
12/27/2016: The driveway to alleyway flare does not meet the standards in LCUASS
Figure 7-11F.
Comment Number: 9 Comment Originated: 12/27/2016
12/27/2016: The existing alleyway adjacent to this site will need to be assessed by
the city and improvements may be necessary.
Comment Number: 10 Comment Originated: 12/27/2016
12/27/2016: The driveway/alleyway material is not specified on the plan set. The
driveway and alleyway need to be concrete up to the property line.
Comment Number: 11 Comment Originated: 12/27/2016
12/27/2016: Curves C7 and C8 do not meet LCUASS standard 8.2.9, the minimum
curb return radii is 15'.
Comment Number: 12 Comment Originated: 12/27/2016
12/27/2016: LCUASS 7.7.C.1.H states that a clay cut off wall should be provided at
the boundaries of the development.
Comment Number: 13 Comment Originated: 12/27/2016
12/27/2016: The alleyway approach will have to be re-constructed after the
installation of the underdrain system to detail 803.
Comment Number: 14 Comment Originated: 12/27/2016
12/27/2016: The chase will need to be designed per detail D-10B.
Comment Number: 15 Comment Originated: 12/27/2016
12/27/2016: On sheet C4.0, construction note 13 is too specific in dimensions. 2'
Saw cut is not allowed, please follow the patching and reconstruction requirements
in LCUASS chapter 25.
Comment Number: 16 Comment Originated: 12/27/2016
12/27/2016: Need to detail the sidewalk connection on the east side of the driveway
to show how this will meet ADA requirements.
Comment Number: 17 Comment Originated: 12/27/2016
12/27/2016: There can not be more than 750sqft of water draining over the sidewalk.
Comment Number: 18 Comment Originated: 12/27/2016
12/27/2016: On the drainage plans, where is design point E and Basin E1?
Comment Number: 19 Comment Originated: 12/27/2016
12/27/2016: On detail sheet, remove detail 708 and 709.
Comment Number: 20 Comment Originated: 12/27/2016
12/27/2016: On detail sheet, need to add 7-11F, 1601, 1602, 1607, 2201, 701, 803,
D-10B
Comment Number: 21 Comment Originated: 12/27/2016
Page 2 of 8
12/27/2016: See redlines for additional comments. Please return redlines with next
round submittal.
Comment Number: 22 Comment Originated: 12/27/2016
Contact: Sheri Langenberger, 970-221-6573, slangenberger@fcgov.com
Topic: General
01/06/2017: The project owes an additional $71 for the TDRFees. This is based on
the site being .72 acres.
Comment Number: 23 Comment Originated: 01/06/2017
Department: Environmental Planning
Contact: Rebecca Everette, 970-416-2625, reverette@fcgov.com
Topic: General
12/15/2016: The tree protection plan notes that there are 16 existing trees on the
site, but there only appear to be 9 shown on the plans. Please update/clarify.
Comment Number: 1 Comment Originated: 12/15/2016
12/15/2016: No additional comments, though I will review any updates to the tree
protection/mitigation plan as needed.
Comment Number: 2 Comment Originated: 12/15/2016
Department: Forestry
Contact: Molly Roche, , mroche@fcgov.com
Topic: Landscape Plans
01/04/2017:
Please schedule a site visit with the City Forester to obtain Tree Inventory and
Mitigation information to include on the Landscape Plans.
Comment Number: 1 Comment Originated: 01/05/2017
01/04/2017:
Please replace the existing Permit Box note with the correct Required Street Tree
note, which is placed in a bolded box. This is available from the City Forester.
Comment Number: 2 Comment Originated: 01/05/2017
01/04/2017:
Please explore widening the parking lot island widths, if at all possible. The City
Forester suggests Regal Prince Oak or Prairie Sentinel Hackberry as alternative
species that would fit better in these narrow spaces.
Comment Number: 3 Comment Originated: 01/05/2017
01/04/2017:
Please consider using Red Barron Crabapple where Adirondack Crabapples are
currently proposed. Red Barron will likely have better availability.
Comment Number: 4 Comment Originated: 01/05/2017
01/04/2016:
Please explore using Linden in place of Honeylocust, due to their adaptability to
shade.
Comment Number: 5 Comment Originated: 01/05/2017
Department: Light And Power
Contact: Coy Althoff, , CAlthoff@fcgov.com
Topic: General
Page 3 of 8
01/03/2017: Light & Power have existing facilities in this area. There is primary
3-phase power available in the alley way east of this property as well as streetlight
and flood light circuits along Magnolia St. and College Ave.
Comment Number: 1 Comment Originated: 01/03/2017
01/03/2017: The existing 400W HPS light on the north-central part of this property is
part of the Fort Collins Light & Power "floodlight" program. At this time, the monthly
fee is part of the Wells Fargo utility bill. Please contact Light & Power, Project
Engineering to have this structure removed prior to demolition.
Comment Number: 2 Comment Originated: 01/03/2017
01/03/2017: As your project begins to move forward please contact Light and
Power Engineering to coordinate the streetlight, transformer and electric meter
locations, please show the locations on the utility plans.
Comment Number: 3 Comment Originated: 01/03/2017
01/03/2017: Please provide a one line diagram and a C-1 form to Light and Power
Engineering. The C-1 form can be found at:
http://zeus.fcgov.com/utils-procedures/files/EngWiki/WikiPdfs/C/C-1Form.pdf
Comment Number: 4 Comment Originated: 01/03/2017
01/03/2017: You may contact FCU Light & Power, project engineering if you have
questions. (970) 221-6700. You may reference Light & Power’s Electric Service
Standards at
http://www.fcgov.com/utilities/img/site_specific/uploads/ElectricServiceStandards_F
INAL_17June2016.pdf
You may reference our policies, development charge processes, and use our fee
estimator at http://www.fcgov.com/utilities/business/builders-and-developers.
Comment Number: 5 Comment Originated: 01/03/2017
Department: PFA
Contact: Jim Lynxwiler, 970-416-2869, jlynxwiler@poudre-fire.org
Topic: General
12/12/2016: NO COMMENT
PFA has no comment related to improvement of the parking lot at 112 W. Magnolia.
Comment Number: 1 Comment Originated: 12/12/2016
Department: Planning Services
Contact: Meaghan Overton, 970-416-2283, moverton@fcgov.com
Topic: General
01/03/2017: It would be helpful if the site and landscape plans were larger. Right
now it’s difficult to see the detail.
Comment Number: 1 Comment Originated: 01/03/2017
01/04/2017: Per street maintenance - please remove drive on College and replace
with sod/turf or similar.
Comment Number: 7 Comment Originated: 01/04/2017
Topic: Landscape Plans
01/03/2017: Please cross-reference the legend on the landscape plan with the plant
schedule. I can’t easily tell how many of each species are shown on the landscape
plan the way it’s currently organized.
Comment Number: 2 Comment Originated: 01/03/2017
Page 4 of 8
01/03/2017: The existing trees need to be more clearly shown. The tree notes show
16 trees, but the existing landscape plan only shows 9 trees. Where are the other 7
trees? In particular, the deciduous trees are hard to see because the linework
overlaps. Any trees removed from the site should be noted as such along with detail
for mitigation.
Comment Number: 3 Comment Originated: 01/03/2017
Topic: Modification of Standard
01/03/2017: The justification for the modification of standard should focus more on
why the proposed solutions meet the general purpose of the standard in 3.2.2(J)
"equally well or better than" a plan that complied with the standard. The justification
as written emphasizes the impact to the parking lot, not how well the proposed
solution meets the purpose of the standard. Also note that the 15 foot setback
applies only to the College Avenue side of the parking lot. The setback from the alley
only needs to be a minimum of 5 feet.
Comment Number: 5 Comment Originated: 01/03/2017
01/03/2017: Staff's analysis of the requested modification of standard will consider
the consistency of the setback with the adjacent building to the north, the efficacy
and aesthetic compatibility of the materials chosen for screening, and the
movement of pedestrians around the site (e.g. the closure of the College Avenue
access point). Please address these points in your revised modification request.
Comment Number: 6 Comment Originated: 01/03/2017
Department: Stormwater Engineering
Contact: Heather McDowell, 970-224-6065, hmcdowell@fcgov.com
Topic: Construction Drawings
12/30/2016: The grading plan should be reconfigured such that runoff will infiltrate
into the paver sections and not bypass the pavers at an unknown rate into the public
street. The proposed u-channel is actually the low point for one of the paver
sections, which means that an unspecified amount of runoff is going to simply
escape through the u-channel. This channel should either be eliminated or modified
so that it is not at the low point.
Comment Number: 2 Comment Originated: 12/30/2016
12/30/2016: The underdrains don’t appear to be located at the low end of the paver
sections. This should be revised.
Comment Number: 3 Comment Originated: 12/30/2016
12/30/2016: The drainage plan includes a table for each paver section and run-on
ratios. Please label each paver section in the plan view so I know which one is
which. In addition, the run-on area for each paver section will need to be shown on
an exhibit that is included within the drainage report. Currently, the run-on areas are
not clear.
Comment Number: 4 Comment Originated: 12/30/2016
Topic: Drainage Report
12/30/2016: Please note that Table RO-11 from the FCSCM should be referenced
and utilized for runoff coefficients instead of Table RO-3 from the USDCM.
Comment Number: 5 Comment Originated: 12/30/2016
12/30/2016: The 100-year orifice calculations need to be included in the report.
Comment Number: 6 Comment Originated: 12/30/2016
Page 5 of 8
12/30/2016: The UD-Detention spreadsheet uses Denver rainfall data to calculate
runoff and therefore detention volume. We don’t allow this spreadsheet to compute
detention volume. Please put together your own mass-balance spreadsheet, using
Fort Collins rainfall data and following the requirements of Chapter 10, Section 3.2.3.
Comment Number: 7 Comment Originated: 12/30/2016
12/30/2016: The UD-Detention spreadsheet can be utilized for stage storage
computations but I can’t tell how you’re including only the void space volume in the
paver sub-grade. You should be assuming a 30% void space and this should be
stated in the report. Also, the elevations shown on this spreadsheet need to be
related back to the paver sub-grade section so I can verify that the detention volume
is within the rock layer of the sub-grade and/or verify that the 12-inch depth of this
layer is adequate.
Comment Number: 8 Comment Originated: 12/30/2016
Contact: Heidi Hansen, 970-221-6854, hhansen@fcgov.com
Topic: Floodplain
01/03/2017: Per the Floodplain Review Checklist, please add and label the 100-year
floodplain and floodway boundaries on the Site Plan.
Comment Number: 9 Comment Originated: 01/03/2017
01/03/2017: Staff will provide comments on the Floodplain Use Permit separately.
The floodplain use permit with no-rise certification must be approved prior to
construction. An as-built survey will be required after construction for no-rise
recertification.
Comment Number: 10 Comment Originated: 01/03/2017
Contact: Jesse Schlam, 970-218-2932, jschlam@fcgov.com
Topic: Erosion Control
12/20/2016: The site disturbs more than 10,000 sq. ft., therefore Erosion and
Sediment Control Materials need to be submitted for FDP. The erosion control
requirements are in the Stormwater Design Criteria under the Amendments of
Volume 3 Chapter 7 Section 1.3.3. Current Erosion Control Materials Submitted do
not meet requirements. Please submit; an Erosion Control Plan (Based upon
redlines), an Erosion Control Report, and an Escrow / Security Calculation. If you
need clarification concerning the erosion control section, or if there are any
questions please contact Jesse Schlam 970-218-2932 or email @
jschlam@fcgov.com
Comment Number: 1 Comment Originated: 12/20/2016
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcounty@fcgov.com
Topic: Construction Drawings
01/03/2017: Please change the titles so they match the other plan sets. See
redlines.
Comment Number: 9 Comment Originated: 01/03/2017
Page 6 of 8
01/03/2017: The City has moved to the NAVD88 vertical datum, and as of January
1, 2015, all projects are required to be on NAVD88 datum. Please provide the
following information for the Benchmark Statement in the EXACT format shown
below.
PROJECT DATUM: NAVD88
BENCHMARK # w/ DESCRIPTION
ELEVATION:
BENCHMARK # w/ DESCRIPTION
ELEVATION:
PLEASE NOTE: THIS PLAN SET IS USING NAVD88 FOR A VERTICAL DATUM.
SURROUNDING DEVELOPMENTS HAVE USED NGVD29 UNADJUSTED FOR
THEIR VERTICAL DATUMS.
IF NGVD29 UNADJUSTED DATUM IS REQUIRED FOR ANY PURPOSE, THE
FOLLOWING EQUATION SHOULD BE USED: NGVD29 UNADJUSTED = NAVD88
- X.XX’.
Comment Number: 10 Comment Originated: 01/03/2017
01/03/2017: Please revise the legal description as marked. See redlines.
Comment Number: 11 Comment Originated: 01/03/2017
01/03/2017: All benchmark statements must match on all sheets.
Comment Number: 12 Comment Originated: 01/03/2017
01/03/2017: There are line over text issues. See redlines.
Comment Number: 13 Comment Originated: 01/03/2017
Topic: Landscape Plans
01/03/2017: Please revise the legal description in the title block as marked. See
redlines.
Comment Number: 5 Comment Originated: 01/03/2017
01/03/2017: There are line over text issues. See redlines.
Comment Number: 6 Comment Originated: 01/03/2017
Topic: Lighting Plan
01/03/2017: Please revise the legal description in the title block as marked. See
redlines.
Comment Number: 7 Comment Originated: 01/03/2017
01/03/2017: Please change the titles so they match. See redlines.
Comment Number: 8 Comment Originated: 01/03/2017
Topic: Site Plan
01/03/2017: Some of the sheet titles in the sheet index do not match the sheet titles
on the noted sheets. See redlines.
Comment Number: 1 Comment Originated: 01/03/2017
01/03/2017: Please revise the legal description as marked. See redlines.
Comment Number: 2 Comment Originated: 01/03/2017
Page 7 of 8
01/03/2017: There are notes with missing text. See redlines.
Comment Number: 3 Comment Originated: 01/03/2017
01/03/2017: There are line over text issues. See redlines.
Comment Number: 4 Comment Originated: 01/03/2017
Department: Traffic Operation
Contact: Nicole Hahn, 970-221-6820, nhahn@fcgov.com
Topic: General
01/03/2017: Work with engineering staff to determine scope of alley improvements.
Comment Number: 1 Comment Originated: 01/03/2017
01/03/2017: Consider adding some type of connection to the College Ave. sidewalk
to improve pedestrian connectivity.
Comment Number: 2 Comment Originated: 01/03/2017
Department: Water Conservation
Contact: Eric Olson, 970-221-6704, eolson@fcgov.com
Topic: General
01/03/2017: Irrigation plans are required no later than at the time of building permit.
The irrigation plans must comply with the provisions outlined in Section 3.2.1(J) of
the Land Use Code. Direct questions concerning irrigation requirements to Eric
Olson, at 221-6704 or eolson@fcgov.com
Comment Number: 1 Comment Originated: 01/03/2017
Department: Water-Wastewater Engineering
Contact: Heather McDowell, 970-224-6065, hmcdowell@fcgov.com
Topic: Construction Drawings
12/30/2016: There is an existing 4-inch waterline in Magnolia and a 6-inch sanitary
sewer main in the alley that are not shown on your plans. Please include these and
make sure to survey the depth of the sanitary sewer main to ensure no conflict with
the proposed storm pipe that crosses it.
Comment Number: 1 Comment Originated: 12/30/2016
Topic: Landscape Plans
12/30/2016: How are you planning to irrigate the landscaping on this project? If you
plan to have an irrigation tap and meter, these need to be shown on the Landscape
Plan and Utility Plan with the tap size and location shown and any roadway
excavation limits also shown.
Comment Number: 2 Comment Originated: 12/30/2016
Department: Zoning
Contact: Marcus Glasgow, 970-416-2338, mglasgow@fcgov.com
Topic: General
12/21/2016: Site and landscape plan will to be on a larger scale.
Comment Number: 1 Comment Originated: 12/21/2016
Page 8 of 8