January 06, 2017
Shelby Hinchliff
Neenan Archistruction
3325 S Timberline Suite 100
Fort Collins, CO 80525
RE: Colorado Early Colleges, SPA160003, Round Number 1
Comment Summary:
Department: Engineering Development Review
Contact: Morgan Uhlman, 970-416-4334, muhlman@fcgov.com
Topic: General
01/03/2017: Please add the following indemnification note to the cover sheet:
The engineer who has prepared these plans, by execution and/or seal hereof, does
hereby affirm responsibility to the Local Entity, as beneficiary of said engineer’s
work, for any errors and omissions contained in these plans, and approval of these
plans by the Local Entity Engineer shall not relieve the engineer who has prepared
these plans of all such responsibility. Further, to the extent permitted by law, the
engineer hereby agrees to hold harmless and indemnify the Local Entity, and its
officers and employees, from and against all liabilities, claims, and demands which
may arise from any errors and omissions contained in these plans.
Comment Number: 1 Comment Originated: 01/03/2017
01/03/2017: LCUASS 9.4.6 - Driveway on the west side of the property is currently
not concrete to the back of the right-of-way.
01/04/17: The driveway on the west side of the property off of the cul-de-sac is
currently not concrete to the right-of-way. Detail 706.2 shows the detail for the
driveway being concrete to the right-of-way, but the curb ramps must de designed to
detail 707.2 since this is a high-volume driveway and requires detectable warnings
to be installed. A variance to the LCUASS standard can be requested (LCUASS
1.9.4) but it may or may not be approved. Information on the dedication process can
be found at: http://www.fcgov.com/engineering/devrev.php
LCUASS 9.4.6.A - All areas within the right-of-way used for vehicular traffic shall be
paved with Portland cement concrete (PCC) from the edge of the pavement to the
edge of right-of-way. PCC may only be required to extend to the back of the
sidewalk if approved by the Local Entity Engineer.
Comment Number: 2 Comment Originated: 01/03/2017
Please see the following summary of comments from City staff and outside reviewing agencies for
your submittal of the above referenced project. If you have questions about any comments, you may
contact the individual commenter or direct your questions through the Project Planner, Clay Frickey, at
970-224-6045 or cfrickey@fcgov.com.
Page 1 of 4
01/03/2017: All sidewalks and ramps need to be ADA accessible in the public
right-of-way.
Comment Number: 3 Comment Originated: 01/03/2017
01/03/2017: If the current east driveway from the cul-de-sac does not meet ADA
standards it must be reconstructed to do so, detail 707.2.
Comment Number: 4 Comment Originated: 01/03/2017
01/03/2017: How are you planning on converting the access easement to an
emergency access easement? This can be done by separate document or the
platting process. Information on the process can be found at:
http://www.fcgov.com/engineering/devrev.php
Comment Number: 5 Comment Originated: 01/03/2017
01/03/2017: Please add detail 707.2 to the detail sheet.
Comment Number: 6 Comment Originated: 01/03/2017
Department: Environmental Planning
Contact: Rebecca Everette, 970-416-2625, reverette@fcgov.com
Topic: General
12/27/2016: As requested during the Conceptual Review, please delineate the
Limits of Development on the site plan so it is clear that there will be no disturbance
to the irrigation ditch on the southern portion of the site. Please also label the
irrigation ditch.
Comment Number: 1 Comment Originated: 12/27/2016
12/27/2016: Will all existing trees and other landscaping be protected on the site? If
so, please add the following note to the site and utility plans:
"All existing trees and landscaping to be retained and protected on-site."
Comment Number: 4 Comment Originated: 12/27/2016
Department: Light And Power
Contact: Coy Althoff, , CAlthoff@fcgov.com
Topic: General
01/03/2017: This property is an existing customer of Light & Power. At this time,
there does not appear to be any electrical upgrades necessary as a result of this
project. In the event of an upgrade, please consult with Light & Power Project
Engineering.
Comment Number: 1 Comment Originated: 01/03/2017
01/03/2017: You may contact FCU Light & Power, project engineering if you have
questions. (970) 221-6700. You may reference Light & Power¿s Electric Service
Standards at
http://www.fcgov.com/utilities/img/site_specific/uploads/ElectricServiceStandards_F
INAL_17June2016.pdf
You may reference our policies, development charge processes, and use our fee
estimator at http://www.fcgov.com/utilities/business/builders-and-developers.
Comment Number: 2 Comment Originated: 01/03/2017
Department: PFA
Contact: Jim Lynxwiler, 970-416-2869, jlynxwiler@poudre-fire.org
Topic: General
Page 2 of 4
01/04/2017: EMERGENCY ACCESS EASEMENT
The limits of the EAE are not entirely clear on the plans and some clarity in labeling
or line quality is requested.
Comment Number: 1 Comment Originated: 01/04/2017
01/04/2017: FIRE LANE SIGNS
The limits of the fire lane shall be fully defined. Fire lane sign locations and/or red
curbing should be indicated on future plan sets. Code language provided below.
> IFC D103.6: Where required by the fire code official, fire apparatus access roads
shall be marked with permanent NO PARKING - FIRE LANE signs complying with
Figure D103.6. Signs shall have a minimum dimension of 12 inches wide by 18
inches high and have red letters on a white reflective background. Signs shall be
posted on one or both sides of the fire apparatus road as required by Section
D103.6.1 or D103.6.2.
Comment Number: 2 Comment Originated: 01/04/2017
Department: Planning Services
Contact: Clay Frickey, 970-224-6045, cfrickey@fcgov.com
Topic: General
01/03/2017: What are the limits of the development/lot? Some of the proposed
changes to the parking area are shown on the parcel to the north, including a portion
of the proposed 24' access easement. Staff needs assurance that the property
owner to the north is on board with the changes you are proposing to their site.
Comment Number: 1 Comment Originated: 01/03/2017
01/03/2017: Upon completion of this SPAR, staff recommends dedicating the
proposed easement by a separate document and submitting a Minor Amendment
for the site to the north that documents the proposed changes to that site.
Comment Number: 2 Comment Originated: 01/03/2017
Department: Stormwater Engineering
Contact: Jesse Schlam, 970-218-2932, jschlam@fcgov.com
Topic: Erosion Control
12/28/2016: No Comment from Erosion Control. Based upon the submitted
materials it has been determined that this site; disturbs less than 10,000 sq. ft., is
not in a sensitive area, and is not in a larger development under construction.
Therefore, no submittal of erosion control material is needed at this time. However,
the site still must be swept and maintained to prevent dirt, saw cuttings, concrete
wash, trash & debris, landscape materials and other pollutants from entering the
storm sewer at all times or erosion and sediment control measures will be required
of the site. If you need; clarification concerning the erosion control section, or if at
any time the site does in fact disturb greater than 10,000 sq. ft., or if there are any
questions, please contact Jesse Schlam 970-218-2932 or email @
jschlam@fcgov.com
Comment Number: 1 Comment Originated: 12/28/2016
Contact: Shane Boyle, 970-221-6339, sboyle@fcgov.com
Topic: General
01/04/2017: The Variance Request referenced in the drainage memo was not
received. Please send this to me separately so it can be reviewed and approved.
Comment Number: 2 Comment Originated: 01/04/2017
Page 3 of 4
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcounty@fcgov.com
Topic: Construction Drawings
12/30/2016: Please make changes to the Benchmark Statement as marked. See
redlines.
Comment Number: 2 Comment Originated: 12/30/2016
12/30/2016: There are line over text issues. See redlines.
Comment Number: 3 Comment Originated: 12/30/2016
Topic: General
12/30/2016: If these plans are to be filed, the Site Plan needs to be separated from
the Utility Plans.
Comment Number: 1 Comment Originated: 12/30/2016
Department: Traffic Operation
Contact: Nicole Hahn, 970-221-6820, nhahn@fcgov.com
Topic: General
01/03/2017: Has a connection to the power train been considered? With the
number of schools in the vicinity it could be a useful bike/ped connection.
Comment Number: 1 Comment Originated: 01/03/2017
Department: Water-Wastewater Engineering
Contact: Shane Boyle, 970-221-6339, sboyle@fcgov.com
Topic: General
01/04/2017: There will be Wastewater fees associated with this project. Since
there will be no City building permit process, the fee will need to be paid prior to final
Utility Plan approval. Please call to coordinate fee payment.
Comment Number: 1 Comment Originated: 01/04/2017
Department: Zoning
Contact: Marcus Glasgow, 970-416-2338, mglasgow@fcgov.com
Topic: General
12/23/2016: LUC 3.2.2(C)(4) 1 bicycle parking space per 3,000 sq ft of building
space. 100% of the spaces must be fixed rack.
Comment Number: 1 Comment Originated: 12/23/2016
12/23/2016: LUC 3.2.1(E)(5)(c) In addition to any pedestrian refuge areas, each
landscaped island shall include one (1) or more canopy shade trees, be of length
greater than eight (8) feet in its smallest dimension, include at least eighty (80)
square feet of ground area per tree to allow for root aeration, and have raised
concrete curbs. The proposed change to the landscape island for fire access must
be landscaped accordingly.
Comment Number: 2 Comment Originated: 12/23/2016
Page 4 of 4