RE: WilMarc Medical, FDP170005, Round Number 1
Comment Summary:
Department: Engineering Development Review
Contact: Marc Virata, 970-221-6567, mvirata@fcgov.com
Topic: General
02/28/2017: Please update the civil plans to reflect an existing drainage, utility and
access easement for the master developer's detention pond.
Comment Number: 2 Comment Originated: 02/28/2017
02/28/2017: Please make the discernment between infrastructure being installed by
the development vs. by others -- the sidewalk being constructed by this project that
ties into the walk built with the regional pond should be more clearly discerned from
the walk built with the regional pond by MAVD.
Comment Number: 3 Comment Originated: 02/28/2017
02/28/2017: It would appear that references to Harmony Technology Park LLC as
the owner should be updated.
Comment Number: 4 Comment Originated: 02/28/2017
02/28/2017: For what it's worth, I'm still of the belief that the northeast corner of
Technology Parkway and Precision Drive was built with curb and gutter for split
directional ramps and there wouldn't appear to be a need to depict the patching
around the curb return.
Comment Number: 5 Comment Originated: 02/28/2017
02/28/2017: The Master Improvement Plan sheet doesn't show the extension of a
storm line along the northern property line that is depicted on the other sheets.
Please clarify (perhaps this line is no longer intended with the identified "North Storm
Sewer Profile"?
Comment Number: 6 Comment Originated: 02/28/2017
Please see the following summary of comments from City staff and outside reviewing agencies for
your submittal of the above referenced project. If you have questions about any comments, you may
contact the individual commenter or direct your questions through the Project Planner, Pete Wray, at
970-221-6754 or pwray@fcgov.com.
Page 1 of 10
02/28/2017: The storm line along the property line referenced in the previous
comment isn't shown in a profile view. Verification of cover over the pipe along
Technology Parkway is needed.
Comment Number: 7 Comment Originated: 02/28/2017
02/28/2017: Might it be construed that the note shown within Lot 2 referencing note
5 on the cover sheet would apply only to Lot 2 since it's a defined boundary and the
note states "within the boundary of this property".
Comment Number: 8 Comment Originated: 02/28/2017
02/28/2017: The plat calls out an emergency access easement for the main drive
aisle internal to the project, however this does not appear to be labelled on the civil
plans.
Comment Number: 9 Comment Originated: 02/28/2017
03/02/2017: Please change references to work being done by others to work being
done by MAV Development (such as the regional sidewalk around the regional
pond). This is more for historical reference.
Comment Number: 10 Comment Originated: 03/02/2017
Department: Environmental Planning
Contact: Stephanie Blochowiak, 970-416-4290, sblochowiak@fcgov.com
Topic: Landscape Plans
02/24/2017: Still need to provide the scientific names along with the common
names for native /bioswale seed mix species. Common names for plants and in
particular grasses and sedges are not reliable for identification. Genus species
names must be included in addition to common names to ensure use of appropriate
species in the mix and that the correct mix is ordered from a native seed provider.
Comment Number: 1 Comment Originated: 02/24/2017
02/24/2017: Native seed mix seeding rates do not match from LP100-102. Minimum
drill seed rate of 15lbs/ac requested. Double that rate if broadcast seeding method
used.
Comment Number: 2 Comment Originated: 02/24/2017
02/24/2017: Call out in Native Seed Mix box the pounds/acre to be used for both a
drill seed application and a broadcast seed application.
Comment Number: 3 Comment Originated: 02/24/2017
Page 2 of 10
02/24/2017: Add Bioswale/Native Seed Mix notes to landscape plans.
a. ADHERE TO THE 5-PAGE SEEDING TECHNICAL SPECIFICATIONS
DOCUMENT PREPARED FOR WILMARC MEDICAL AND APPROVED THROUGH
DEVELOPMENT REVIEW PROCESS.
b. SEED MIX SHALL BE ORDERED AND APPLIED AS INDICATED ON
APPROVED PLANS AND THE GROUND CULTIVATED LIGHTLY THEN SEEDED
IN TWO DIRECTIONS TO DISTRIBUTE SEED EVENLY OVER ENTIRE AREA.
c. IF CHANGES ARE TO BE MADE TO SEED MIX BASED ON SITE CONDITIONS
APPROVAL MUST BE PROVIDED BY CITY ENVIRONMENTAL PLANNER.
d. PRIOR TO SEEDING SOIL WILL BE AERATED AND SOIL AMENDMENTS
ADDED IF NECESSARY. APPROPRIATE NATIVE SEEDING EQUIPMENT WILL
BE USED (STANDARD TURF SEEDING OR AGRICULTURE DRILL SEED
EQUIPMENT SHALL NOT BE USED).
e. DRILL SEED APPLICATION RECOMMENDED PER SPECIFIED APPLICATION
RATE TO ¼ - ½ INCH DEPTH. FOR BROADCAST SEEDING INSTEAD OF DRILL
SEEDING METHOD - DOUBLE SPECIFICIED APPLICATION RATE. REFER TO
NATIVE SEED MIX TABLE FOR SPECIES, PERCENTAGES AND APPLICATION
RATES.
f. TREAT NATIVE SEED MIX AREA PRIOR TO INSTALLATION OF SEED WITH
APPROPRIATE HERBICIDE TO HELP CONTROL HERBACEOUS WEED
SPECIES. ONLY AFTER APPROPRIATE TIME PERIOD THEN APPLY NATIVE
SEED AS CALLED FOR ON APPROVED PLANS.
g. CONTRACTOR SHALL MONITOR SEEDED AREA FOR PROPER
IRRIGATION, EROSION CONTROL AND GERMINATION. RESEEDING WILL
OCCUR AS NEEDED TO ESTABLISH COVER.
h. THE APPROVED SEED MIX AREA IS INTENDED TO BE MAINTAINED IN A
NATURAL-LIKE LANDSCAPE AESTHETIC. IF AND WHEN MOWING OCCURS IN
NATIVE GRASS SEED MIX AREAS DO NOT MOW LOWER THAN 6-8 INCHES IN
HEIGHT TO AVOID INHIBITING NATIVE PLANT GROWTH.
i. NATIVE SEED AREA WILL BE CONSIDERED ESTABLISHED WHEN
SEVENTY-PERCENT TOTAL COVER IS REACHED WITH NO LARGER THAN 6
INCH SQUARE BARE SPOTS AND/OR UNTIL DEEMED ESTABLISHED BY CITY
ENVIRONMENTAL PLANNER.
Comment Number: 4 Comment Originated: 02/24/2017
Topic: Lighting Plan
02/24/2017: Enlarge luminaire schedule on PH001 for easier reading and correct
ordering. Thank you for calling out 3000K or less LED fixtures to be used. This
supports efforts of the City of Fort Collins’ Night Sky team. Results of the team’s
work can currently be viewed on the City’s Public Records website in Resolution
2016-074, a summary of City of Fort Collins City Council Intent and General Policy
Regarding Night Sky Objectives. For further information regarding health effects of
blue light in the night sky see:
http://darksky.org/ama-report-affirms-human-health-impacts-from-leds/
Comment Number: 5 Comment Originated: 02/24/2017
Department: Light And Power
Page 3 of 10
Contact: Coy Althoff, 970-224-6150, CAlthoff@fcgov.com
Topic: General
02/28/2017: Light & Power will has electric facilities running along both Technology
Pkwy and Precision Dr. that can be utilized to serve this proposed building.
Comment Number: 1 Comment Originated: 02/28/2017
02/28/2017: Development charges, electric Capacity Fee, Building Site charges
and any system modification charges necessary will apply to this development.
Comment Number: 2 Comment Originated: 02/28/2017
02/28/2017: Streetlights will be placed along public streets. A 40 feet separation on
both sides of the light is required between canopy trees and streetlights. A 15 feet
separation on both sides of the light is required between ornamental trees and
streetlights.
Comment Number: 3 Comment Originated: 02/28/2017
02/28/2017: As your project begins to move forward please contact Light and
Power Engineering to coordinate the streetlight, transformer and electric meter
locations, please show the locations on the utility plans. Transformers shall be
within 10' of a paved surface and must have a minimum clearance of 8' from the
front and 3' around the sides and back.
Comment Number: 4 Comment Originated: 02/28/2017
02/28/2017: Please add one additional streetlight to your utility plan. It will need to
be added on the north side of Precision Dr. This streetlight will need to be offset no
more than 175' from the existing streetlight located on the S.E. side of the
intersection.
Comment Number: 5 Comment Originated: 02/28/2017
02/28/2017: Please provide a one line diagram and a C 1 form to Light and Power
Engineering. The C 1 form can be found at: http://zeus.fcgov.com/utils
procedures/files/EngWiki/WikiPdfs/C/C 1Form.pdf
Comment Number: 6 Comment Originated: 02/28/2017
02/28/2017: You may contact FCU Light & Power, project engineering if you have
questions. (970) 221-6700. You may reference Light & Power’s Electric Service
Standards at
http://www.fcgov.com/utilities/img/site_specific/uploads/ElectricServiceStandards_F
INAL_18November2016_Amendment.pdf
You may reference our policies, development charge processes, and use our fee
estimator at http://www.fcgov.com/utilities/business/builders-and-developers.
Comment Number: 7 Comment Originated: 02/28/2017
Department: Outside Agencies
Contact: Terry Ferrill, ,
Topic: General
Page 4 of 10
02/28/2017: FCLWD/SFCSD:
The South Fort Collins Sanitation District have reviewed the above mentioned
project and submit the following comments.
The existing sanitary sewer service located near the southeast corner of the
property is to be abandoned at the manhole in accordance with District
requirements.
The Fort Collins -Loveland Water District does not have any facilities in the area.
Please do not hesitate to contact me at 226-3104, ext. 104, if you have any
questions or require additional information.
Comment Number: Comment Originated: 02/28/2017
Department: PFA
Contact: Cal Sheesley, 970-416-2599, csheesley@poudre-fire.org
Topic: General
02/28/2017: AERIAL APPARATUS ACCESS
Aerial Fire Apparatus access is required for structures over 30' in height which is
measured to the top of parapet walls. The amended plans show the change in
height to 29' with a 2' parapet, dropping to the roof measured at 27'. This is an
acceptable amendment; however, the Site Cover Final Plan (Sheet LS001) shows a
maximum building height of 36' and the Elevations (Sheet EL002 - Panel Type 'A')
shows a height of 33'. The Poudre Fire Authority would like clarification on these
height measurements.
Comment Number: 1 Comment Originated: 02/28/2017
02/28/2017: FIRE LANE SIGNS
The limits of the fire lane shall be fully defined. The signage is noted; however,
please amend the plans to show the signs parallel to the Emergency Access
Easement (EAE) instead of 45 degrees to the EAE.
Please observe the current sign standards in LUCAS, specifically drawing #1418
and #1419. Let the future plans show the current LUCAS sign standards.
Comment Number: 2 Comment Originated: 02/28/2017
02/28/2017: WATER SUPPLY
Hydrant spacing and flow must meet minimum requirements based on type of
occupancy. The shown hydrant plans show a deficiency and an additional hydrant
will be required at the northwest corner of the site, at a distance of 600' from the
hydrant to the south, at the intersection of Technology Parkway and Precision Drive.
Specific code language follows:
> IFC 507.5 and PFA Policy: COMMERCIAL REQUIREMENTS: Hydrants to provide
1,500 gpm at 20 psi residual pressure, spaced not further than 300 feet to the
building, on 600-foot centers thereafter
CLEAR SPACE AROUND HYDRANTS
> IFC 507.5.5: A 3-foot clear space shall be maintained around the circumference of
fire hydrants except as otherwise required or approved.
Comment Number: 3 Comment Originated: 02/28/2017
Page 5 of 10
02/28/2017: LANDSCAPE
From the Landscape plans (specifically SHEET LP101 & LP102), several tree
footprints are shown within the Emergency Access Easement (EAE). The Poudre
Fire Authority would like verification that the mature footprint of these trees will not
interfere with the EAE and the 14' vertical and 24' wide will remain clear for
emergency access.
Comment Number: 4 Comment Originated: 02/28/2017
Department: Planning Services
Contact: Pete Wray, 970-221-6754, pwray@fcgov.com
Topic: General
02/28/2017: Utility Plan set. Revise vicinity map on cover page to include both
parcels in site.
Comment Number: 2 Comment Originated: 02/28/2017
Topic: Landscape Plans
03/01/2017: In reference to the full tree stocking requirement, and after reviewing
the interpretation plan, Noah and I think a few trees are still needed on southeast
building façade.
Comment Number: 4 Comment Originated: 03/01/2017
Topic: Lighting Plan
02/28/2017: Need other half of lighting sheet to show front side of building and street
area. Show property lines, street names for context and to confirm lighting levels
beyond property lines are correct. Lighting legend and table need to be much larger
to read. Need fixture details.
Comment Number: 3 Comment Originated: 02/28/2017
Topic: Site Plan
02/28/2017: Add Planning Approval Signature block to cover page.
Comment Number: 1 Comment Originated: 02/28/2017
Department: Stormwater Engineering
Contact: Jesse Schlam, 970-218-2932, jschlam@fcgov.com
Topic: Erosion Control
02/07/2017: Current Erosion Control Materials Submitted do not meet
requirements. Please submit; an Erosion Control Plan (Based upon redlines many
of the comments from last round were not addressed), an Erosion Control Report
(Based upon comments from PDP. I received the redlines not a revised copy please
send a revised copy for review), and an Escrow / Security Calculation (Recalculated
based upon redlines and comments, this too like the report were never provided
during this round of comments). Also, based upon the area of disturbance State
permits for stormwater will be required since the site is over an acre. If you need
clarification concerning the erosion control section, or if there are any questions
please contact Jesse Schlam 970-218-2932 or email @ jschlam@fcgov.com
Comment Number: 1 Comment Originated: 02/07/2017
Contact: Wes Lamarque, 970-416-2418, wlamarque@fcgov.com
Topic: General
03/01/2017: Stormwater did not receive a revised Drainage Report.
Comment Number: 2 Comment Originated: 03/01/2017
Page 6 of 10
03/01/2017: On the landscape plan, please add the roof drain piping. Some
conflicts with trees may exist.
Comment Number: 3 Comment Originated: 03/01/2017
03/01/2017: Please remove the forebay for the storm sewer entering the regional
pond. This may create a maintenance issue and is not needed.
Comment Number: 4 Comment Originated: 03/01/2017
03/01/2017: On the storm sewer plan and profile sheets, please label storm sewers
as private or public.
Comment Number: 5 Comment Originated: 03/01/2017
03/01/2017: Clarification is still needed if the existing inlet in Technology Parkway
has piping heading west into the main storm sewer trunk. If so, it will need to be
abandoned or plugged.
Comment Number: 6 Comment Originated: 03/01/2017
03/01/2017: The Grading Plan has a lot of information and may be best if it were
separated into two sheets similar to the Landscape Plan. If not, a blowup of the two
LID basins may be required to show in more detail the grading.
Comment Number: 7 Comment Originated: 03/01/2017
03/01/2017: Please provide hatching at the bottoms of the rain gardens to
document the area where soil media will be placed.
Comment Number: 8 Comment Originated: 03/01/2017
03/01/2017: Please label 4:1 max for all slopes including the rain gardens and
swales.
Comment Number: 9 Comment Originated: 03/01/2017
03/01/2017: Please replace all riprap with permanent erosion control matting.
Comment Number: 10 Comment Originated: 03/01/2017
03/01/2017: The minimum size for the rain garden underdrains are 6-inches.
Comment Number: 11 Comment Originated: 03/01/2017
03/01/2017: Please locate and show the weir for Rain Garden 1.
Comment Number: 12 Comment Originated: 03/01/2017
03/01/2017: The spot elevations can be removed from the Drainage Plan.
Comment Number: 13 Comment Originated: 03/01/2017
03/01/2017: Please remove the rain garden soil media specification and replace
with the City's soil media specification.
Comment Number: 14 Comment Originated: 03/01/2017
03/03/2017: Trees can not be located within the media-section of any rain gardens.
Comment Number: 15 Comment Originated: 03/03/2017
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcounty@fcgov.com
Topic: Construction Drawings
Page 7 of 10
03/01/2017: The datum has changed to NGVD29 Unadjusted. Please change it
back to NAVD88 and provide the following information for the Benchmark Statement
in the EXACT format shown below.
PROJECT DATUM: NAVD88
BENCHMARK # w/ DESCRIPTION
ELEVATION:
BENCHMARK # w/ DESCRIPTION
ELEVATION:
PLEASE NOTE: THIS PLAN SET IS USING NAVD88 FOR A VERTICAL DATUM.
SURROUNDING DEVELOPMENTS HAVE USED NGVD29 UNADJUSTED FOR
THEIR VERTICAL DATUMS.
IF NGVD29 UNADJUSTED DATUM IS REQUIRED FOR ANY PURPOSE, THE
FOLLOWING EQUATION SHOULD BE USED: NGVD29 UNADJUSTED = NAVD88
- X.XX’.
Comment Number: 9 Comment Originated: 03/01/2017
03/01/2017: Why did the Basis Of Bearings statement change. The plans still show
the original Basis Of Bearings. This should match the Subdivision Plat.
Comment Number: 10 Comment Originated: 03/01/2017
03/01/2017: Some of the easement descriptions shown are incorrect. If they are
going to stay on the plan, they should match what is shown on the Subdivision Plat.
Comment Number: 11 Comment Originated: 03/01/2017
03/01/2017: There are text over text issues. See redlines.
Comment Number: 12 Comment Originated: 03/01/2017
03/01/2017: There are line over text issues. See redlines.
Comment Number: 13 Comment Originated: 03/01/2017
03/01/2017: There is text that needs to be rotated 180°. See redlines.
Comment Number: 14 Comment Originated: 03/01/2017
03/01/2017: There is text that needs to be masked. Mask all text in hatched areas.
See redlines.
Comment Number: 15 Comment Originated: 03/01/2017
Topic: Landscape Plans
03/01/2017: There are match line issues. See redlines.
Comment Number: 6 Comment Originated: 03/01/2017
03/01/2017: Some of the easement descriptions shown are incorrect. If they are
going to stay on the plan, they should match what is shown on the Subdivision Plat.
Comment Number: 7 Comment Originated: 03/01/2017
03/01/2017: Please remove the "comma" from the title in the title blocks. See
redlines.
Comment Number: 8 Comment Originated: 03/01/2017
Topic: Plat
03/01/2017: Please add new title commitment information if available. You could be
potentially liable for any documents recorded since this date.
Comment Number: 1 Comment Originated: 03/01/2017
Page 8 of 10
Topic: Site Plan
03/01/2017: There are match line issues. See redlines.
Comment Number: 2 Comment Originated: 03/01/2017
03/01/2017: Some of the easement descriptions shown are incorrect. If they are
going to stay on the plan, they should match what is shown on the Subdivision Plat.
Comment Number: 3 Comment Originated: 03/01/2017
03/01/2017: Please remove the "comma" from the title in the title blocks. See
redlines.
Comment Number: 4 Comment Originated: 03/01/2017
03/01/2017: There are line over text issues. See redlines.
Comment Number: 5 Comment Originated: 03/01/2017
Department: Water Conservation
Contact: Eric Olson, 970-221-6704, eolson@fcgov.com
Topic: General
03/01/2017: Irrigation plans are required no later than at the time of building permit.
The irrigation plans must comply with the provisions outlined in Section 3.2.1(J) of
the Land Use Code. Direct questions concerning irrigation requirements to Eric
Olson, at 221-6704 or eolson@fcgov.com
Comment Number: 1 Comment Originated: 03/01/2017
Department: Water-Wastewater Engineering
Contact: Wes Lamarque, 970-416-2418, wlamarque@fcgov.com
Topic: General
03/01/2017: Please provide the water crossing on the storm sewer profiles.
Comment Number: 1 Comment Originated: 03/01/2017
03/01/2017: Please add a plug at the fire hydrant assembly on Note 4 on sheet 3.
Comment Number: 2 Comment Originated: 03/01/2017
03/01/2017: Please clarify if the irrigation tap is existing or proposed. Note 5 states
both.
Comment Number: 3 Comment Originated: 03/01/2017
03/01/2017: Is an 8-inch fire line required? A 6-inch is more typical.
Comment Number: 4 Comment Originated: 03/01/2017
03/01/2017: Please see redlines for other minor comments.
Comment Number: 5 Comment Originated: 03/01/2017
Department: Zoning
Contact: Noah Beals, 970-416-2313, nbeals@fcgov.com
Topic: General
02/28/2017: LS001 needs to include all sheets not a part of the plat and Utility plan
set in the sheet index.
Also needs to include CDNS director signature block.
Comment Number: 1 Comment Originated: 02/28/2017
Page 9 of 10
02/28/2017: Please reference the management plan for establishment of the seed
mix areas in a note on the landscape plan
Comment Number: 2 Comment Originated: 02/28/2017
02/28/2017: LUC 3.2.1(D)(1)(c) Requires full tree stocking to occur within all
landscape areas with 50ft of any building.
It appears there is room for some trees along the Southeast elevation in front of the
wall labeled PTE-05. The street trees in this area are more than 50ft away
Comment Number: 3 Comment Originated: 02/28/2017
02/28/2017: Where is the full lighting plan? The photometric plan should cover the
entire site plan. Where are the lighting fixtures?
Comment Number: 4 Comment Originated: 02/28/2017