HomeMy WebLinkAboutCOLORADO EARLY COLLEGES - SITE PLAN ADVISORY REVIEW - SPA160003 - SUBMITTAL DOCUMENTS - ROUND 1 - FIRE AUTHORITY REQUIREMENTSTriple C Communications, Inc. 114 Inverness Circle East Englewood, CO 80112 (303) 850-9000 1 September 23, 2016 Diversified Consulting Solutions, Inc. Attn: Michelle Fisher 8778 Wolff Ct, Suite 204 Westminster, CO 80031 Prepared by: Robin Crout/Estimator Re: Colorado Early Colleges - Fort Collins Scope: Radio Frequency Signal Level Testing Per the requirements of Poudre Fire Authority and the City of Fort Collins, we were onsite to perform RF signal level testing of the above referenced building. Code requirements are under IFC 2012 and NFPA 72 and state that the building must exceed -95 dBm in 95% of each area of each floor and 100% in areas considered critical. We used our Harris two-way radios, set to the frequencies used by Poudre Fire for this testing. Our signal level readings ranged from -68 dBm to -93 dBm. Based on code requirements it is our opinion that this building does meet minimum code requirements and will not need a signal enhancement system. It is ultimately up to the fire department, based on our signal level readings, and their over the air testing if they choose, as to whether they would pass or fail this building. Copies of our results are being sent to them as well. Thank you for this opportunity. Please feel free to contact me with any questions at the above number or at robin@tripleccom.com. We look forward to working with you again in the near future. Sincerely, Robin Crout Robin Crout Estimator/Project Manager 1/25/2016 Plan name Design plan Project name Revision history 1/25/2016 Plan name Level 1 Project name Revision history