March 20, 2015
Kathy Mathis
TB Group
444 Mountain Ave
Berthoud, CO 80513
RE: Centre for Advanced Technology 23rd Lot 2 Office Building, FDP150007, Round Number 1
Comment Summary:
Department: Planning Services
Contact: Clay Frickey, 970-224-6045, cfrickey@fcgov.com
Topic: Building Elevations
03/16/2015: Make sure to use materials that are consistent with the materials used
at Sunshine House. This material choice will ensure the area has a unified look and
feel.
Comment Number: 6 Comment Originated: 03/16/2015
03/16/2015: Since you are breaking up the mass of the building horizontally as
opposed to vertically, please provide a diagram that shows the scale and
dimensions of the changes in plane of the building.
Comment Number: 7 Comment Originated: 03/16/2015
03/16/2015: A rendering of the building showing the changes in plane and material
choice would be useful in determining how the building meets section 3.5.3 of the
Land Use Code.
Comment Number: 8 Comment Originated: 03/16/2015
03/16/2015: Please provide elevations of the trash/recycle enclosure and the
covered bike parking.
Comment Number: 9 Comment Originated: 03/16/2015
03/16/2015: The site plan shows a fixed bike rack for 4 bike parking spaces. The
building elevations show a fixed bike rack on the West elevation that provides
capacity beyond what the site plan calls for. Please update either the building
elevations or the site plan so that the two elements are consistent.
Comment Number: 10 Comment Originated: 03/16/2015
Topic: Landscape Plans
03/16/2015: The plant list table, hydrozone table and landscape legend are all
incomplete. Please complete these tables with the appropriate numbers.
Comment Number: 4 Comment Originated: 03/16/2015
Please see the following summary of comments from City staff and outside reviewing agencies for
your submittal of the above referenced project. If you have questions about any comments, you may
contact the individual commenter or direct your questions through the Project Planner, Clay Frickey, at
970-224-6045 or cfrickey@fcgov.com.
Page 1 of 9
03/16/2015: Ensure that the street trees along Centre are located within 15 feet of
light poles to ensure there is not an 80 foot gap between street trees.
Comment Number: 5 Comment Originated: 03/16/2015
Topic: Site Plan
03/16/2015: Please recalculate the FAR. A FAR of 7:1 on this site would mean
575,000+ gross square feet of floor area.
Comment Number: 1 Comment Originated: 03/16/2015
03/16/2015: Please correct the sheet number for the site plan or remove since
there is only one sheet.
Comment Number: 2 Comment Originated: 03/16/2015
03/16/2015: Please fix the parking table calculations. The site plan shows 96
parking spaces with 91 regular spaces and 5 handicapped accessible spaces. The
parking table double counts the handicapped spaces, resulting in 101 spots.
Comment Number: 3 Comment Originated: 03/16/2015
Department: Engineering Development Review
Contact: Marc Ragasa, 970.221.6603, mragasa@fcgov.com
Topic: Easements
03/18/2015: Please see the following link for the Easement Dedication process for
the Emergency Asscess and Drainage Easement:
http://www.fcgov.com/engineering/pdf/Easrowdedications2010.pdf
Please see link for a sample deed of dedication of easement:
http://www.fcgov.com/engineering/pdf/ESMwithAdminAcceptance9111.doc
Comment Number: 7 Comment Originated: 03/18/2015
03/19/2015: An easement vacation will need to be done for the existing access,
slope & utility easement (Rec 20000043055) along Centre Avenue. Please vacate a
portion of easement so that the retaining walls are not in the easment. Please see
the following link for the Easement Vacation process:
http://www.fcgov.com/engineering/pdf/Vacationofeaseinfo2010.pdf
Comment Number: 8 Comment Originated: 03/18/2015
Topic: General
03/18/2015: Adjust Sheet Index on the Cover Sheet to match individual sheets of
the Utility Plan. Sheet C3.01 should read, "Storm Sewer Plan". See Redlines.
Comment Number: 1 Comment Originated: 03/18/2015
03/18/2015: With the installation of the sanitary sewer service off Perennial Lane,
new curb and gutter will need to be replaced in the ROW. Please include the
standard LCUASS drawing to the details in the Utility Plan
Comment Number: 2 Comment Originated: 03/18/2015
03/18/2015: There appears to be conflicting sidewalk widths along Perennial Lane.
The minimum sidewalk width for commercial local streets is 5'.
Comment Number: 3 Comment Originated: 03/18/2015
03/18/2015: Please use updated LCUASS drawings 1606 and 1607 for the
Pedestrian Ramp and Truncated Dome details. New changes became effective on
February 17, 2015.
Comment Number: 4 Comment Originated: 03/18/2015
Page 2 of 9
03/18/2015: Please label details not in the public ROW as on site only. Please see
redlines.
Comment Number: 5 Comment Originated: 03/18/2015
03/18/2015: The Erosion Control Plan should read, "C6.01"
Comment Number: 6 Comment Originated: 03/18/2015
Contact: Sheri Langenberger, 970-221-6573, slangenberger@fcgov.com
Topic: General
03/20/2015: The project owes an additional $779.75 for PDP fees. The building
square footage on the appplication form is less than that identified on the submitted
site plan.
Comment Number: 9 Comment Originated: 03/20/2015
Department: Environmental Planning
Contact: Stephanie Blochowiak, 970-416-2401, sblochowiak@fcgov.com
Topic: General
03/03/2015: Thank you for providing an Ecological Characterization Study (ECS)for
this site. Based upon results from the ECS, no development timing restrictions or
mitigation measures will be necessary. No natural habitat buffer zone will be
required on-site either, as the Larimer Canal #2 is located further than fifty feet (50
ft) from this parcel, as are the four large eastern cottonwoods along the canal; these
features are separated from the site by Rolland Moore Dr. There are no wetlands
on-site, and nearby wetlands are separated from this parcel by Perennial Ln.
Comment Number: 1 Comment Originated: 03/03/2015
Department: Forestry
Contact: Tim Buchanan, 970-221-6361, tbuchanan@fcgov.com
Topic: Landscape Plans
03/17/2015:
Provide the following notes under a separate heading labeled Street Tree Notes:
1. A permit must be obtained from the City Forester before any trees or shrubs as
noted on this plan are planted, pruned or removed on the public right-of-way. This
includes zones between the sidewalk and curb, medians and other City property.
This permit shall approve the location and species to be planted. Failure to obtain
this permit may result in replacing or relocating trees and a hold on certificate of
occupancy.
2. Contact the City Forester to inspect all street tree plantings at the completion of
each phase of the development. All trees need to have been installed as shown on
the landscape plan. Approval of street tree planting is required before final approval
of each phase.
3. Street tree shall be supplied and planted by the developer using a qualified
landscape contractor.
4. The developer shall replace all dead and dying street trees after planting until final
maintenance inspection and acceptance by the City of Fort Collins Forestry
Division. All street trees in the project must be established of an approved species
and of acceptable le condition prior to acceptance.
5. Street tree locations and numbers may be adjusted to accommodate driveway
locations, utility standards, separation between trees, street signs and street lights.
Street trees shall be centered in the middle of the parkway. Quantities shown on
plan must be installed unless a reduction occurs to meet separation standards.
Comment Number: 1 Comment Originated: 03/17/2015
Page 3 of 9
03/17/2015:
Provide the following note in large print with a bold border on all landscape sheets.
A free permit must be obtained from the City Forester before any street trees are
planted in parkways between the sidewalk and Curb. Street tree locations and
numbers may change to meet actual utility/tree separation standards. Landscape
contractor must obtain approval of street tree location after utility locates. Street
trees must be inspected and approved before planting. Failure to obtain this permit
is a violation of the Code of the City of Fort Collins.
Comment Number: 2 Comment Originated: 03/17/2015
03/17/2015:
If this note is currently not on the plan then please add:
Landscaping including street trees in each phase shall be or secured with a letter of
credit, escrow, or performance bond for 125% of the value of the landscaping and
installation prior to the issuance of certificate of occupancy for any building. All City
street trees must be installed established, of an approved species and of acceptable
condition prior to final release of financial security.
Comment Number: 3 Comment Originated: 03/17/2015
03/17/2015:
Show location of any streetlights and stop signs and provide separation between
trees and fixtures to LUC standards.
Comment Number: 4 Comment Originated: 03/17/2015
03/17/2015:
Chanticleer Pear used as street trees in the narrow parkway along Centre should be
upsized to 2.0 inch caliper because they are being used as street trees and will
need to have a higher canopy.
Comment Number: 5 Comment Originated: 03/17/2015
Comment Number: Comment Originated: 03/17/2015
03/17/2015:
Evaluate the first Chanticleer Pear tree north of Rolland Moore Drive for possible
deletion for improved site visibility from this intersection.
Comment Number: 6 Comment Originated: 03/17/2015
Department: Light And Power
Contact: Todd Vedder, 970-224-6152, tvedder@fcgov.com
Topic: General
03/05/2015: New development charges and any system modification charges will
apply. A link to the online fee estimator is below.
http://www.fcgov.com/utilities/business/builders-and-developers/plant-investment-de
velopment-fees/electric-development-fee-estimator?id=3
Comment Number: 1 Comment Originated: 03/05/2015
03/05/2015: A one-line diagram as well as a Commercial Form (C-1) will need to be
provided to Light & Power in order to properly size the transformer. Please contact
Light & Power to obtain this form or it can be retrieved using the link below.
http://www.fcgov.com/utilities/business/builders-and-developers/development-forms
-guidelines-regulations
Comment Number: 2 Comment Originated: 03/05/2015
Page 4 of 9
03/05/2015: The existing conditions and utility drawing shows the location of an
existing vault in the wrong location. There is an existing vault in the Right-Of-Way
off of Centre in between the Advanced Technology and Day Care Center property.
Please update drawings to reflect this vault. Contact Light & Power with any
questions.
Comment Number: 3 Comment Originated: 03/05/2015
03/05/2015: The Utility Plan shows the proposed transformer being tapped off the
existing transformer located at the day care center. If this is the case, then an
easement will need to be granted to utilize this property. It is advised to use the
existing vault located on the east corner of the property in the Right-Of-Way.
Comment Number: 4 Comment Originated: 03/05/2015
03/05/2015: For transformer location, ensure the transformer is within 10 ft of a
paved surface for the utility vehicles to install and do maintenance. Also ensure
there is an 8 ft frontal and 3 ft side/back clearance from the transformer.
Comment Number: 5 Comment Originated: 03/05/2015
Department: PFA
Contact: Jim Lynxwiler, 970-416-2869, jlynxwiler@poudre-fire.org
Topic: General
03/17/2015: BUILDINGS OVER 30' IN HEIGHT
The 30' wide fire lane which is currently positioned on the north side of the building
exceeds the maximum, allowable separation distance from the building. The fire
lane shall be no closer than 15' from the building but no further than 30' from the
building. Code language is provided below. Refer to Appendix D of the 2012 IFC for
additional information.
AERIAL FIRE APPARATUS ACCESS ROADS - PROXIMITY TO BUILDING
> 2012 IFC D105.3: At least one of the required access routes meeting this
condition shall be located within a minimum of 15 feet and a maximum of 30 feet
from the building, and shall be positioned parallel to one entire side of the building.
The side of the building on which the aerial fire apparatus access road is positioned
shall be approved by the fire code official.
Comment Number: 1 Comment Originated: 03/17/2015
03/17/2015: FIRE LANE SPECIFICATIONS
The proposed fire lane plan needs to be designed so as to support 40 tons, be
marked appropriately by painting and/or signage, and maintained unobstructed at all
times.
Comment Number: 2 Comment Originated: 03/17/2015
Department: Stormwater Engineering
Contact: Dan Mogen, , dmogen@fcgov.com
Topic: General
03/17/2015: Please see redlined plans and drainage report.
Comment Number: 2 Comment Originated: 03/17/2015
03/17/2015: Please provide LID table to verify LID requirements are met. Please
email me at dmogen@fcgov.com for a sample table.
Comment Number: 3 Comment Originated: 03/17/2015
03/17/2015: Please provide information on existing underdrain running along
Perennial.
Comment Number: 4 Comment Originated: 03/17/2015
Page 5 of 9
Contact: Jesse Schlam, 970-218-2932, jschlam@fcgov.com
Topic: Erosion Control
03/17/2015: The erosion control requirements are in the Stormwater Design Criteria
under the Amendments of Volume 3 Chapter 7 Section 1.3.3. The current Erosion
Control Materials Submitted do not meet requirements. See redlines for corrections
in the Erosion Control Plan. The Erosion Control Report (Stormwater Management
Control) was not submitted. The Site will also have to supply new Erosion Control
Escrow Calculations. If you need clarification concerning this section, or if there are
any questions please contact Jesse Schlam 970-218-2932 or email @
jschlam@fcgov.com
Comment Number: 1 Comment Originated: 03/17/2015
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcounty@fcgov.com
Topic: Building Elevations
03/17/2015: The title does not match the subdivision name. The subdivision plat
name is "Centre For Advanced Technology 23rd Filing", not "CAT 23rd". The title
needs to match the rest of the plans. See redlines.
Comment Number: 1 Comment Originated: 03/17/2015
03/17/2015: There are line over text issues. See redlines.
Comment Number: 2 Comment Originated: 03/17/2015
Topic: Construction Drawings
03/17/2015: Please remove the marked text in the sub-title. It is duplication of the
title. See redlines.
Comment Number: 3 Comment Originated: 03/17/2015
Page 6 of 9
03/17/2015: The City has moved to the NAVD88 vertical datum. Please provide the
following information in the EXACT format shown below.
If your project is started on NAVD88 datum:
1) PROJECT DATUM: NAVD88
BENCHMARK # w/ DESCRIPTION
ELEVATION:
BENCHMARK # w/ DESCRIPTION
ELEVATION:
OR, if project has already been surveyed in NAVD29 Unadjusted datum:
2) PROJECT DATUM: NGVD29 UNADJUSTED (OLD CITY OF FORT COLLINS
DATUM)
BENCHMARK # w/ DESCRIPTION
ELEVATION:
BENCHMARK # w/ DESCRIPTION
ELEVATION:
If using NGVD29 UNADJUSTED the following equation statement will be needed.
NOTE: IF NAVD 88 DATUM IS REQUIRED FOR ANY PURPOSE, THE
FOLLOWING EQUATION SHOULD BE USED: NAVD88 = NGVD29 UNADJUSTED
+ X.XX’
Comment Number: 4 Comment Originated: 03/17/2015
03/17/2015: The Basis Of Bearings needs to be corrected. There is no Tract A on
the Centre For Advnaced Technology 23rd Filing plat. If it is meant to match the
Basis Of Bearings from the Centre For Advnaced Technology 23rd Filing plat, it is
missing information.
Comment Number: 5 Comment Originated: 03/17/2015
03/17/2015: The titles in the sheet index do not match the titles on the marked
sheets. See redlines.
Comment Number: 6 Comment Originated: 03/17/2015
03/17/2015: Please tie the coordinate values shown for utilities to the project
boundary. We would prefer that this be done by adding property corner values to
each sheet, or showing the property corner values on the horizontal control plans
and adding a note to each sheet with coordinate values.
Comment Number: 7 Comment Originated: 03/17/2015
03/17/2015: There are line over text issues. See redlines.
Comment Number: 8 Comment Originated: 03/17/2015
03/17/2015: All benchmark statements need to match on all sheets.
Comment Number: 9 Comment Originated: 03/17/2015
03/17/2015: All Basis Of Bearings statements need to match on all sheets.
Comment Number: 10 Comment Originated: 03/17/2015
03/17/2015: Please correct the sheet number on sheet C6.01.
Comment Number: 11 Comment Originated: 03/17/2015
Page 7 of 9
Topic: Landscape Plans
03/17/2015: No comments.
Comment Number: 12 Comment Originated: 03/17/2015
Topic: Lighting Plan
03/17/2015: The title does not match the subdivision name. The subdivision plat
name is "Centre For Advanced Technology 23rd Filing", not "CAT 23rd". The title
needs to match the rest of the plans. See redlines.
Comment Number: 13 Comment Originated: 03/17/2015
Topic: Site Plan
03/17/2015: Please correct the typo in Note #12. See redlines.
Comment Number: 14 Comment Originated: 03/17/2015
03/17/2015: There are line over text issues. See redlines.
Comment Number: 15 Comment Originated: 03/17/2015
03/17/2015: Please check the sheet numbering. If there are 3 sheets, we did not
receive sheets 2 & 3, and will need to review them next round. See redlines.
Comment Number: 16 Comment Originated: 03/17/2015
Department: Traffic Operation
Contact: Martina Wilkinson, 970-221-6887, mwilkinson@fcgov.com
Topic: General
03/17/2015: There have been concerns raised about WB approach striping at
Rolland Moore / Centre, but that is CSU property and that concern has been
forwarded to them.
Comment Number: 2 Comment Originated: 03/17/2015
03/17/2015: There have been concerns raised about a pedestrian connection to the
east to get to the MAX station, but this is not an obligation of this development.
Comment Number: 3 Comment Originated: 03/17/2015
Topic: Traffic Impact Study
03/17/2015: The submitted TIS has been reviewed and the conclusions accepted.
Comment Number: 1 Comment Originated: 03/17/2015
Department: Water Conservation
Contact: Eric Olson, 970-221-6704, eolson@fcgov.com
Topic: General
03/11/2015: A landscape plan shall contain accurate and identifiable hydrozones,
including a water budget chart that shows the total annual water use, which shall not
exceed fifteen (15) gallons per square foot over the site. If you have questions
contact Eric Olson at eolson@fcgov.com or 970-221-6704.
Comment Number: 1 Comment Originated: 03/11/2015
Department: Water-Wastewater Engineering
Contact: Dan Mogen, , dmogen@fcgov.com
Topic: General
Page 8 of 9
03/17/2015: Please add note to core drill new sanitary service into existing
manhole.
Comment Number: 1 Comment Originated: 03/17/2015
03/18/2015: Please allow 5' separation between bend and fire line and 3' separation
between fire line and 1" water service.
Comment Number: 2 Comment Originated: 03/17/2015