Loading...
HomeMy WebLinkAboutWOODWARD TECHNOLOGY CENTER (FORMERLY LINK-N-GREENS) - PDP - PDP130001 - PLANS - PHOTOMETRIC PLAN (10)FORT COLLINS PROJECT DEVELOPMENT PLAN SUBMITTAL REVISIONS: DATE: GHAFARI ASSOCIATES, LLC 122 S MICHIGAN AVE, SUITE 1500 CHICAGO, IL 60603 USA TEL +1.312.984.2300 www.ghafari.com ELECTRICAL LIGHTING SCHEDULES AND DETAILS 14 January, 2013 EL5-00-01 PDP SUBMITTAL 01-14-13 1 EL5-00-01 ROADWAY / AREA LIGHTING POLE DETAIL SCALE: NTS  ‘ 6'-0" MIN. 2'-6" MIN TO 3'-0" MAX 6" MIN REFER TO LIGHTING FIXTURE SCHEDULE GROUND LUG. BOND CU GROUND WIRE TO INSIDE OF POLE BASE PVC CONDUIT ANCHOR BOLTS RIGID STEEL CONDUIT COUPLING CONCRETE ENVELOPE 3/4"X10' COPPER GROUND ROD #2 BARE COPPER GROUND WIRE BOND TO POLE FINISHED GRADE STUB AND CAP CONDUIT 4'-0" FROM BASE WHERE INDICATED #3 @ 12" TIES 8-#7 VERT. ARM LENGTH 4, 6, OR 8 FEET MOUNTING HEIGHT 30'-0" 2'-0" IN PARKING LOTS, OTHERWISE 0'-6" TAPERED SPUN ALUMINUM MOUNTING ARM WITH NATURAL ALUMINUM FINISH. PHILIPS LUMEC BRACKET TYPE AC4, AC6, OR AC8 TAPERED 8" TO 5" ROUND ALUMINUM POLE, WELDED TOP AND BOTTOM TO A CAST-ALUMINUM ANCHOR PLATE, 4"x8" MAINTENANCE OPENING COMPLETE WITH COVER AND COPPER GROUND LUG, CAST ALUMINUM BOLT COVERS, NATURAL ALUMINUM FINISH. PHILIPS LUMEC POLE TYPE ATR85 1.6 fc 3.7 fc 0.8 fc 4.6:1 2.0:1 1.2 fc 3.6 fc 0.2 fc 18.0:1 6.0:1 1.0 fc 2.3 fc 0.3 fc 7.7:1 3.3:1 1.3 fc 3.5 fc 0.4 fc 8.8:1 3.3:1 1.2 fc 4.0 fc 0.3 fc 13.3:1 4.0:1 Parking Lot Ph.1 West Parking Lot Ph.1 South Parking Lot Ph.1 North Parking Lot Ph.1 East Main Street Description Avg Max Min Max/Min Avg/Min LIGHTING CALCULATION STATISTICS NOTE: LIGHTING CALCULATIONS ASSUME 0.7 LIGHT LOSS FACTOR (LLF) SINGLE ARM OR DOUBLE ARM AS INDICATED ON SITE LIGHTING PLANS PDP RESUBMITTAL 01-30-13