HomeMy WebLinkAboutWOODWARD TECHNOLOGY CENTER (FORMERLY LINK-N-GREENS) - PDP - PDP130001 - PLANS - PHOTOMETRIC PLAN (10)FORT COLLINS
PROJECT DEVELOPMENT PLAN SUBMITTAL
REVISIONS: DATE:
GHAFARI ASSOCIATES, LLC
122 S MICHIGAN AVE, SUITE 1500
CHICAGO, IL 60603 USA
TEL +1.312.984.2300
www.ghafari.com
ELECTRICAL
LIGHTING
SCHEDULES
AND DETAILS
14 January, 2013
EL5-00-01
PDP SUBMITTAL 01-14-13
1
EL5-00-01
ROADWAY / AREA LIGHTING POLE DETAIL
SCALE: NTS
6'-0" MIN.
2'-6" MIN TO 3'-0" MAX
6" MIN
REFER TO LIGHTING
FIXTURE SCHEDULE
GROUND LUG. BOND CU
GROUND WIRE TO INSIDE
OF POLE BASE
PVC
CONDUIT
ANCHOR
BOLTS
RIGID
STEEL
CONDUIT
COUPLING
CONCRETE
ENVELOPE
3/4"X10' COPPER
GROUND ROD
#2 BARE COPPER
GROUND WIRE BOND
TO POLE
FINISHED GRADE
STUB AND CAP CONDUIT
4'-0" FROM BASE WHERE
INDICATED
#3 @ 12" TIES
8-#7 VERT.
ARM LENGTH 4, 6, OR 8 FEET
MOUNTING HEIGHT 30'-0"
2'-0" IN PARKING LOTS, OTHERWISE 0'-6"
TAPERED SPUN ALUMINUM
MOUNTING ARM WITH
NATURAL ALUMINUM FINISH.
PHILIPS LUMEC BRACKET
TYPE AC4, AC6, OR AC8
TAPERED 8" TO 5" ROUND ALUMINUM POLE,
WELDED TOP AND BOTTOM TO A
CAST-ALUMINUM ANCHOR PLATE, 4"x8"
MAINTENANCE OPENING COMPLETE WITH
COVER AND COPPER GROUND LUG, CAST
ALUMINUM BOLT COVERS, NATURAL
ALUMINUM FINISH.
PHILIPS LUMEC POLE TYPE ATR85
1.6 fc 3.7 fc 0.8 fc 4.6:1 2.0:1
1.2 fc 3.6 fc 0.2 fc 18.0:1 6.0:1
1.0 fc 2.3 fc 0.3 fc 7.7:1 3.3:1
1.3 fc 3.5 fc 0.4 fc 8.8:1 3.3:1
1.2 fc 4.0 fc 0.3 fc 13.3:1 4.0:1
Parking Lot Ph.1 West
Parking Lot Ph.1 South
Parking Lot Ph.1 North
Parking Lot Ph.1 East
Main Street
Description Avg Max Min Max/Min Avg/Min
LIGHTING CALCULATION STATISTICS
NOTE: LIGHTING CALCULATIONS ASSUME 0.7 LIGHT LOSS FACTOR (LLF)
SINGLE ARM OR DOUBLE
ARM AS INDICATED ON
SITE LIGHTING PLANS
PDP RESUBMITTAL 01-30-13