www.maxsonengineering.com
June 27, 2016
Seth Lorson
Fort Collins Community Development and Neighborhood Services
281 N College Ave.
PO Box 580
Fort Collins, CO 80522
slorson@fcgov.com
Re: 221 E Mountain BDR Comments – Mechanical Equipment Roof Area Analysis
ME #: 15085
Dear Seth,
Per your request in our phone conversation dated 6/23/2016, this letter is a summary of the
required mechanical HVAC roof top equipment for the project referenced above. This letter
should also be considered our response to the Fort Collins BDR comment (BDR160011) we
received on 05/27/2016 for the project referenced above. Section 3.8.17 of the City of Fort
Collins Land Use Code, mechanical equipment exceeding the maximum building height is to be
limited to 5% of the total roof area.
Currently, we anticipate to provide the new four (4) story building with two (2) packaged rooftop
units (RTU) to provide the International Mechanical Code (IMC) required heating and ventilation
air to the space. In addition, a single restroom exhaust fan (EF) will provide the IMC required
ventilation to the core group of restrooms. At this time, it is expected that a future restaurant
tenant will occupy a portion of the first floor retail space, thus, as part of this analysis, we have
included the kitchen hood exhaust fan (KEF) and makeup air unit (MAU) that is expected to be
mounted on the roof. Lastly, per Poudre Fire Authority, a fire pump will be required for the space
which will need a backup generator. Due to space limitations, the generator is currently planned
to be placed on the roof.
Attached you will find a summary of each roof mounted piece of mechanical equipment and its
total percentage of roof area covered. Per your request, we have included both the area of the
fourth floor roof, and an analysis of the total roof area, which includes the lower third floor roof
area. The table provided in the attachment indicates roof area of all mechanical equipment
relative to the total roof area (including both roofs) is approximately 5.22%. The mechanical
rooftop units, RTU-1 and 2, are standard packaged equipment and they have been sized to
handle 30% outside air (relative to total airflow). The 30% outside air flow rate is the industry
standard recommendation for maximum amount of outside air a unit can adequately temper
during the design day conditions. Anything above that would generally require a larger air
handling unit.
We feel that the code required space heating and ventilation equipment has as small of a foot
print as allowed for standardized equipment and we request that the City of Fort Collins allow
the units as currently configured to be provided and placed on the roof. In addition to the
summary, cutsheets of each proposed piece of roof mounted mechanical equipment has been
provided for your reference.
Seth Lorson
June 27, 2016
Page 2 of 2
If you have any questions, please don’t hesitate to contact me for addition information or further
clarification.
Sincerely,
Maxson Engineering, LLC
Chris Geipel
Senior Mechanical Designer
Enclosed:
Mechanical Equipment Roof Area Analysis
2012 International Mechanical Code Ventilation Calculations
RTU-1 Manufacturer Cutsheets
RTU-2 Manufacturer Cutsheets
EF-1 Manufacturer Cutsheets
MAU-1 Manufacturer Cutsheets
KEF-1 Manufacturer Cutsheets
221 E Mountain
Mechanical Equipment Roof Area Analysis
6/26/2016
ME# 15085
Roof Area 1: SF (Level 4 Area)
Roof Area 2: SF (All Roof Areas)
L W H
RTU-1 529 143 104 525 4.46% 3.08%
RTU-2 394 93 104 254 2.16% 1.49%
Generator 180 53 70 66 0.56% 0.39%
EF-1 28 -- 28 4 0.04% 0.03% 2
MAU-1 84 60 6 35 0.30% 0.21% 1
KEF-1 28 -- 28 4 0.04% 0.03% 1, 2
890 7.56% 5.22%
Notes:
1. Future equipment.
2. Dimension represents round equipment diameter.
11,771
17,058
Notes
Totals
Dimensions [in] Percent of Total
Roof Area 1
Equipment Area [SF]
Percent of Total
Roof Area 2
221 E Mountain
RTU-1 Ventilation Calculation
6/26/2016
ME# 15085
RTU-2 Level 1 Sales SALES 10,000 7.5 0.12 15 150 2325 0.8 2,906 14,500 4,350 0.67
RTU-2 Level 1 Rest. DINING ROOMS 1,000 7.5 0.18 70 70 705 0.8 881 4,500 1,350 0.65
RTU-2 Level 1 Misc STORAGE ROOMS 1,000 0 0.12 0 0 120 0.8 150 1,000 300 0.50
ΣPz = 220 ΣVpz = 20,000 6,000 ---
2,820 Ps (#12) = 176 MAX. Zp = 0.67
5,852 D (#13) = 0.80 Ev (#11) = 0.48
6,000
20,000
30.0%
Y
NOTES:
1. "PEOPLE AND AREA OUTDOOR AIRFLOW RATE IN BREATHING ZONE"; PER TABLE 403.3, 2012 IMC.
2. "DEFAULT OCCUPANT DENSITY"; PER TABLE 403.3, 2012 IMC.
3. BREATHING ZONE OUTDOOR AIRFLOW Vbz = Rp*Pz + Ra*Az; PER EQUATION 4-1, SECTION 403.3.1.1, 2012 IMC.
4. ZONE AIR DISTRIBUTION EFFECTIVENESS; PER TABLE 403.3.1.2, SECTION 403.3.1.2, 2012 IMC.
5. ZONE OUTDOOR AIRFLOW Voz = Vbz/Ez; PER EQUATION 4-2, SECTION 403.3.1.3, 2012 IMC.
6. PRIMARY AIRFLOW SUPPLIED TO THE ZONE FROM THE AIR HANDLING UNIT; PER SECTION 403.3.2.3.1, 2012 IMC.
7. PRIMARY AIRFLOW SUPPLIED TO THE ZONE FROM THE AIR HANDLING UNIT. FOR DESIGN PURPOSES, Vpz SHALL BE THE ZONE DESIGN PRIMARY AIRFLOW RATE, EXCEPT FOR ZONES WITH VARIABLE AIR VOLUME
SUPPLY AND Vpz SHALL BE THE LOWEST EXPECT PRIMARY AIRFLOW RATE TO THE ZONE WHEN IT IS FULLY OCCUPIED. Vpz (MIN) = Vpz (MAX) * 30%.
8. PRIMARY OUTDOOR AIR FRACTION Zp = Voz/Vpz; PER EQUATION 4-5, SECTION 403.3.2.3.1, 2012 IMC.
9. UNCORRECTED OUTDOOR AIR INTAKE Vou = D*ΣRp*Pz+ΣRa*Az; PER EQUATION 4-6, SECTION 403.3.2.3.3, 2012 IMC.
10. OUTDOOR AIR INTAKE FLOW RATE Vot = Vou/Ev; PER EQUATION 4-8, SECTION 403.3.2.3.4, 2012 IMC.
11. SYSTEM VENTILATION EFFICIENCY; PER TABLE 403.3.2.3.2, 2012 IMC. Ev IS BASED ON MAXIMUM Zp CALCULATED USING EQUATION 4-5 AMONG ALL ZONES SERVED BY THE SYSTEM; PER SECTION 403.3.2.3.1,
OR NORMATIVE APPENDIX A OF ASHRAE 62.1-2007.
12. SYSTEM POPULATION: THE TOTAL NUMBER OF OCCUPANTS IN THE AREA SERVED BY THE SYSTEM; PER SECTION 403.3.2.3.3, 2012 IMC.
13. OCCUPANT DIVERSITY: THE RATIO OF THE SYSTEM POPULATION TO THE SUM OF ZONE POPULATIONS: PER EQUATION 4-7, 2012 IMC.
VENTILATION SCHEDULE (2012 IMC)
ZONE
SERVED
BY
ZONE IDENTIFICATION 2012 IMC VENTILATION RATE PROCEDURE - MULTI-ZONE RECIRCULATING SYSTEMS DESIGN CASE
FLOOR PLAN ROOM NAME & REMARKS
NUMBER
OCCUPANCY
CLASSIFICATION
PER TABLE 403.3 - 2012 IMC
ZONE NET
FLOOR
AREA
Az
[SQ.FT.]
OUTDOOR
AIRFLOW
REQUIRED
PER PERSON
Rp (#1)
[CFM /
PERSON]
SUPPLY
RATE TO
ZONE
Vpz (#7)
(MIN.)
[CFM]
PRIMARY
OUTDOOR
221 E Mountain
RTU-2 Ventilation Calculation
6/26/2016
ME# 15085
RTU-1 LV. 2A Office OFFICE SPACES 12,026 5 0.06 5 60 1022 0.8 1,278 14,500 4,350 0.29
RTU-1 Lv. 2A Conference CONFERENCE ROOMS 2,255 5 0.06 50 113 699 0.8 874 6,500 1,950 0.45
RTU-1 LV. 2A Misc. STORAGE ROOMS 752 0 0.12 0 0 90 0.8 113 750 225 0.50
RTU-1 LV. 3A Office OFFICE SPACES 12,026 5 0.06 5 60 1022 0.8 1,278 14,500 4,350 0.29
RTU-1 Lv. 3A Conference CONFERENCE ROOMS 2,255 5 0.06 50 113 699 0.8 874 6,500 1,950 0.45
RTU-1 LV. 3A Misc. STORAGE ROOMS 752 0 0.12 0 0 90 0.8 113 750 225 0.50
RTU-1 LV. 4A Office OFFICE SPACES 9,296 5 0.06 5 46 790 0.8 988 11,000 3,300 0.30
RTU-1 Lv. 4A Conference CONFERENCE ROOMS 1,743 5 0.06 50 87 540 0.8 675 5,000 1,500 0.45
RTU-1 LV. 4A Misc. STORAGE ROOMS 581 0 0.12 0 0 70 0.8 87 500 150 0.58
ΣPz = 479 ΣVpz = 60,000 18,000 ---
5,023 Ps (#12) = 479 MAX. Zp = 0.58
8,828 D (#13) = 1.00 Ev (#11) = 0.57
18,000
60,000
30.0%
Y
NOTES:
1. "PEOPLE AND AREA OUTDOOR AIRFLOW RATE IN BREATHING ZONE"; PER TABLE 403.3, 2012 IMC.
2. "DEFAULT OCCUPANT DENSITY"; PER TABLE 403.3, 2012 IMC.
3. BREATHING ZONE OUTDOOR AIRFLOW Vbz = Rp*Pz + Ra*Az; PER EQUATION 4-1, SECTION 403.3.1.1, 2012 IMC.
4. ZONE AIR DISTRIBUTION EFFECTIVENESS; PER TABLE 403.3.1.2, SECTION 403.3.1.2, 2012 IMC.
5. ZONE OUTDOOR AIRFLOW Voz = Vbz/Ez; PER EQUATION 4-2, SECTION 403.3.1.3, 2012 IMC.
6. PRIMARY AIRFLOW SUPPLIED TO THE ZONE FROM THE AIR HANDLING UNIT; PER SECTION 403.3.2.3.1, 2012 IMC.
7. PRIMARY AIRFLOW SUPPLIED TO THE ZONE FROM THE AIR HANDLING UNIT. FOR DESIGN PURPOSES, Vpz SHALL BE THE ZONE DESIGN PRIMARY AIRFLOW RATE, EXCEPT FOR ZONES WITH VARIABLE AIR VOLUME
SUPPLY AND Vpz SHALL BE THE LOWEST EXPECT PRIMARY AIRFLOW RATE TO THE ZONE WHEN IT IS FULLY OCCUPIED. Vpz (MIN) = Vpz (MAX) * 30%.
8. PRIMARY OUTDOOR AIR FRACTION Zp = Voz/Vpz; PER EQUATION 4-5, SECTION 403.3.2.3.1, 2012 IMC.
9. UNCORRECTED OUTDOOR AIR INTAKE Vou = D*ΣRp*Pz+ΣRa*Az; PER EQUATION 4-6, SECTION 403.3.2.3.3, 2012 IMC.
10. OUTDOOR AIR INTAKE FLOW RATE Vot = Vou/Ev; PER EQUATION 4-8, SECTION 403.3.2.3.4, 2012 IMC.
11. SYSTEM VENTILATION EFFICIENCY; PER TABLE 403.3.2.3.2, 2012 IMC. Ev IS BASED ON MAXIMUM Zp CALCULATED USING EQUATION 4-5 AMONG ALL ZONES SERVED BY THE SYSTEM; PER SECTION 403.3.2.3.1,
OR NORMATIVE APPENDIX A OF ASHRAE 62.1-2007.
12. SYSTEM POPULATION: THE TOTAL NUMBER OF OCCUPANTS IN THE AREA SERVED BY THE SYSTEM; PER SECTION 403.3.2.3.3, 2012 IMC.
13. OCCUPANT DIVERSITY: THE RATIO OF THE SYSTEM POPULATION TO THE SUM OF ZONE POPULATIONS: PER EQUATION 4-7, 2012 IMC.
PROVIDED OUTDOOR AIR INTAKE FLOW [CFM] =
TOTAL SUPPLY RATE ΣVpz (#6) [CFM] =
SYSTEM OUTDOOR AIR PERCENTAGE =
IN COMPLIANCE WITH STANDARD? [Y/N] =
SUPPLY
RATE TO
ZONE
Vpz (#6)
(MAX.)
[CFM]
SYSTEM SUMMARY:
UNCORRECTED OUTDOOR AIR INTAKE Vou (#9) [CFM] =
REQUIRED OUTDOOR AIR INTAKE Vot (#10) [CFM] =
OUTDOOR
AIRFLOW
RATE REQ.
PER UNIT
AREA
Ra (#1)
[CFM / SQ.FT.]
ZONE
OCCUPANT
DENSITY
(#2)
90-162 Ton Packaged Industrial Rooftop
Job Information
221 E Mountain
Denver Main Office
(S02) Gerry Boarman
Tag RTU-1 Model number SL--150
Nominal capacity 150 Ton air cooled Unit type DX cooling/hot water heat
Model Description
Voltage selection 460/60/3 XL Heat capacity High heat - 1.25" (32mm) valve
Supply fan airflow 58000 cfm Exhaust / Return airflow 54000 cfm
Damper Option Low leak
Unit configuration 1 piece unit - w/o blank section Miscellaneous options Belt guards
System control VAV (DTC) with VFD w/ bypass
Condenser coil selection Air-cooled aluminum
Supply / return airflow configuration Downflow supply / upflow return
Capacity, Efficiency, & drain pan Standard evap coil-stnls steel drain pan
Blank section application options None
Refrigeration system - A Replaceable core liquid filter driers
Fresh air option Econ w/ dry bulb
Power connection selection Ckt Brkr w/highfaultSCCR/pwrd conv outle
Pre evaporator coil filter selection 2 " high efficiency throw away
Energy recovery wheel module None
Reheat and hot gas bypass options Standard
Cooling
Cooling EDB 82.50 F Gross total capacity 1768.48 MBh
Cooling EWB 65.00 F Gross sensible capacity 1603.98 MBh
Ambient temp 95.00 F Latent capacity 75.85 MBh
Leaving coil dry bulb 55.52 F Net total capacity 1570.56 MBh
Leaving unit dry bulb 59.28 F Net sensible capacity 1406.06 MBh
Leaving unit wet bulb 56.25 F System power 205.70 kW
EER @ AHRI 9.9 EER IEER 14.8 EER
Fan motor heat 197.92 MBh Elevation 5000.00 ft
Reheat and hot gas bypass
options
Standard Reheat leaving dew point
100% Exhaust/Return fan
options
Std CFM Return w/ VFD w/
Bypass w/ Stat
Supply fan options Standard CFM w/
Internal Shaft Grounding
Power
Supply duct static pressure 1.750 in H2O Return duct static pressure 1.000 in H2O
Total supply static pressure 4.706 in H2O Component static pressure drop 2.956 in H2O
Supply fan RPM 1200 Exhaust/Return RPM 1100
Actual Supply fan RPM 1244 rpm Actual Exhaust / Return fan speed 1142 rpm
Supply fan motor 100 HP Exhaust/Return fan motor 50 HP
Actual supply motor power 76.54 bhp Actual Exhaust / Return motor power 36.79 bhp
4/11/2016 Product Version 1.1.0.0
Page 4 of 6
90-162 Ton Packaged Industrial Rooftop
Job Information
221 E Mountain
Denver Main Office
(S02) Gerry Boarman
Tag RTU-1 Model number SL--150
Nominal capacity 150 Ton air cooled Unit type DX cooling/hot water heat
Electrical
Minimum circuit ampacity 440.55 A Compressor 1 count 4.00 Each
Maximum overcurrent protection 500.00 A Compressor 1 RLA 52.10 A
Recommended dual element 500.00 A Compressor 2 count 0.00 Each
Minimum disconnect switch size 473.00 A Compressor 2 RLA 0.00 A
Supply fan motor FLA 115.00 A Exhaust / Return fan motor FLA 60.50 A
Electric heater FLA 0.00 A Condenser fan FLA 21.60 A
Crankcase heater FLA 1.00 A Other FLA 6.30 A
Heating
Heat capacity High heat - 1.25" (32mm) valve
Heating entering air temperature 44.60 F Output heating capacity 1322.97 MBh
Heating leaving air temperature 73.75 F Output heating capacity with fan 1529.86 MBh
Entering water temperature 160.00 F Hydronic Coil Flow Rate 60.00 gpm
Hydronic coil leaving water temp 113.42 F Fluid type Propylene glycol
Fluid percent 30.00 %
Heating delta T - air temp 29.15 F
Acoustical Performance
Octave Band 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
Supply duct 103 dB 100 dB 105 dB 99 dB 95 dB 96 dB 86 dB 78 dB
Return duct 101 dB 99 dB 105 dB 98 dB 94 dB 106 dB 86 dB 79 dB
Outdoor noise 105 dB 102 dB 102 dB 100 dB 97 dB 102 dB 93 dB 85 dB
Ducted Sound Power Rated in Accordance with ARI Standard 260.
Octave Band Sound Power in dB re 1 picoWatt.
"Discharge duct" is supply fan discharge sound power in the supply duct.
"Return duct" is supply fan inlet sound power in the return duct.
Weights
Total installed weight 24003.0 lb
Installed point loading 1 1970.5 lb Installed point loading 2 1440.9 lb
Installed point loading 3 1655.3 lb Installed point loading 4 1431.9 lb
Installed point loading 5 2054.8 lb Installed point loading 6 1937.2 lb
Installed point loading 7 3012.1 lb Installed point loading 8 2199.7 lb
Installed point loading 9 2000.8 lb Installed point loading 10 1885.2 lb
Installed point loading 11 2239.2 lb Installed point loading 12 2175.5 lb
First x dimension - installed 4.000 in Second x dimension - installed 97.800 in
4/11/2016 Product Version 1.1.0.0
Page 5 of 6
90-162 Ton Packaged Industrial Rooftop
Job Information
221 E Mountain
Denver Main Office
(S02) Gerry Boarman
Tag RTU-1 Model number SL--150
Nominal capacity 150 Ton air cooled Unit type DX cooling/hot water heat
Third x dimension - installed 191.600 in Fourth x dimension - installed 285.400 in
First y dimension - installed 2.875 in Second y dimension - installed 140.925 in
Installed center of gravity - x 260.022 in Installed center of gravity - y 64.384 in
Piece 1 Lifting
Piece One Type Complete Unit Piece 1 - Total weight 24003.0 lb
Piece 1-Lifting point loading 1 4707.1 lb Piece 1-Lifting point loading 2 3815.2 lb
Piece 1-Lifting point loading 3 4306.9 lb Piece 1-Lifting point loading 4 3507.5 lb
Piece 1-Lifting point loading 5 3918.8 lb Piece 1-Lifting point loading 6 3747.6 lb
Piece 1- First x dimension - loading 65.990 in Piece 1- Second x dimension - loading 269.380 in
Piece 1-Third x dimension - loading 466.180 in
Piece 1 - COG X 0.000 in Piece 1 - COG Y 0.000 in
Piece 3 - Lifting Point Load 3 0.0 lb
Installed point loads for multiple piece units are only applicable for continuous rail support. For other
installations contact your Trane representitive.
Information for LEED Projects
ASHRAE 90.1 compliance Yes IPLV @ AHRI
Refrig charge (HFC-410A) - ckt 1 105.0 lb Compressor total power
Refrig charge (HFC-410A) - ckt 2 105.0 lb Condenser fan total power
Rated capacity at AHRI 148.92 tons Actual supply motor power 76.54 bhp
EER @ AHRI 9.9 EER Actual Exhaust / Return 36.79 bhp
motor power
4/11/2016 Product Version 1.1.0.0
Page 6 of 6
20-75 Ton Packaged Industrial Rooftop
Job Information
221 E Mountain
Denver Main Office
(S02) Gerry Boarman
Tag RTU-2 Model number SLHLF50
Nominal Capacity 50 ton Air cooled Unit Function Hot Water Heat
Development Sequence R410A Development sequence
Unit airflow H: Single Zone
Model Description
Unit Function System Control VAV (DTC) SF &
EF/RF VFD w/ Bypass
Hot Water Heat
Nominal Capacity 50 ton Air cooled Outside Air Selection 0-100% Economizer with
TRAQ and DCV
Power Supply 460/60/3 Capacity/Efficiency Options Standard capacity unit
Heating Capacity High Heat, 1"[25mm]
Valve
Filter High-Efficiency Throwaway
Filters
Exhaust/Return fan options 100% Return 15 HP 1800 rpm - Return fan
w/Statitrac
Exhaust/Return fan drive
selection
Cooling
Gross total capacity 561.98 MBh Gross latent capacity 77.36 MBh
Gross sensible capacity 484.62 MBh Net total capacity 515.87 MBh
Net sensible capacity 438.50 MBh Net sensible heat ratio 85.00 %
Leaving coil DB 55.22 F Leaving coil WB 54.01 F
Leaving unit DB 58.02 F Leaving unit WB 55.01 F
Entering Conditions
Design airflow 18000 cfm Exhaust/Return Airflow 18000 cfm
Ambient DB 95.00 F Cooling EDB 84.00 F
Ent air relative humidity Cooling EWB 65.00 F
Elevation 5000.00 ft Heating EAT 40.10 F
Heating
Output htg capacity 489.69 MBh
Heating delta T 30.15 F Heating LAT 70.25 F
Output htg capacity w/fan 489.69 MBh Entering water temp 160.00 F
Leaving water temp 124.32 F
Water flow rate 30.00 gpm
Power
Supply Total Static Pressure 3.103 in H2O Supply duct static pressure 1.660 in H2O
Roof curb (for static pressure add) Roof Curb Return duct static pressure 0.830 in H2O
4/11/2016 Product Version 2004.05.24.1
Page 3 of 4
Electrical values provided are estimated only and are subject to change without notice and may differ from nameplate values.
20-75 Ton Packaged Industrial Rooftop
Job Information
221 E Mountain
Denver Main Office
(S02) Gerry Boarman
Tag RTU-2 Model number SLHLF50
Nominal Capacity 50 ton Air cooled Unit Function Hot Water Heat
Development Sequence R410A Development sequence
Supply Fan Hp 20 Hp FC Exhaust/Return fan options 100% Return 15 HP
w/Statitrac
Actual supply motor power 16.62 bhp Actual exhaust/return motor
power
11.38 bhp
Supply Fan Drive Selection 1100 rpm Exhaust/Return fan drive 1800 rpm - Return fan
selection
Actual supply fan speed 1082 rpm Actual exhaust/return fan 1785 rpm
speed
System power 57.36 kW EER @ AHRI 10.6 EER
IEER @ AHRI 14.3 EER
Electrical
Max overcurrent protection 150.00 A Min circuit ampacity 136.78 A
Min disconnect switch size 150.00 A Recommended dual element 150.00 A
Compressor 1 count 4.00 Each Compressor 1 RLA 19.10 A
1 Supply fan motor FLA 24.70 A
Supply motor count
Condenser fan FLA 10.80 A Exhaust/return fan motor FLA 17.70 A
Electric heater FLA Other FLA 1.00 A
Crankcase heater FLA Supply fan count 2.00 Each
Weights
Installed point load 1 682.3 lb Installed point load 2 771.5 lb
Installed point load 3 794.0 lb Installed point load 4 883.2 lb
Installed point load 5 893.0 lb Installed point load 6 982.2 lb
Installed point load 7 993.2 lb Installed point load 8 1082.3 lb
Installed point load 9 1103.7 lb Installed point load 10 1192.8 lb
COG - X dimension 17.27 ft COG - Y dimension 3.96 ft
Total installed weight 9378.3 lb
Coil Specification
Evaporator rows Evaporator face area 38.00 sq ft
Evaporator fin spacing
4/11/2016 Product Version 2004.05.24.1
Page 4 of 4
Electrical values provided are estimated only and are subject to change without notice and may differ from nameplate values.
*
*Overall height may be greater depending on motor
22
28.38
4
23.75
1.75
Model: G-143-VG
Direct Drive Centrifugal Roof Exhaust Fan
Dimensional
Quantity 1
Weight w/o Acc's (lb) 65
Weight w/ Acc's (lb) 91
Optional Damper (in.) 16 x 16
Roof Opening (in.) 18.5 x 18.5
Performance
Requested Volume (CFM) 2,700
Actual Volume (CFM) 2,700
External SP (in. wg) 0.5
Total SP (in. wg) 0.593
Fan RPM 1681
Operating Power (hp) 0.8
Elevation (ft) 5,663
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.061
Tip Speed (ft/min) 6,437
Static Eff. (%) 31
Motor
Motor Mounted Yes
Size (hp) 1
Voltage/Cycle/Phase 115/60/1
Enclosure TEFC
Motor RPM 1725
Windings 1
FLA (Amps) 12
External SP 0.5 in. wg
Damper 0.093 in. wg
Total SP 0.593 in. wg
Notes:
All dimensions shown are in units of in.
*NEC FLA - based on tables 430.248 or 430.250 of
National Electrical Code 2014. Actual motor FLA may vary,
for sizing thermal overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4
dBA - A weighted sound pressure level, based on 11.5 dB
attenuation per Octave band at 5 ft - dBA levels are not
licensed by AMCA International
Sones - calculated using AMCA 301 at 5 ft
Sound Power by Octave Band
Sound
Data
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 78 81 85 77 73 72 68 60 81 69 17.9
Printed Date: 6/22/2016
Job: 15085 - 221 E Mountain
Mark: EF-1
CAPS 4.20.1661 P:\2015\15085 -- 221 East Mountain\Mechanical\Equipment Selections\15085 - 221 E Mountain.gfcj Page 1 of 2
Model: G-143-VG
Direct Drive Centrifugal Roof Exhaust Fan
Standard Construction Features:
- Aluminum housing - Backward inclined wheel - Aluminum curb cap with
prepunched mounting holes - Birdscreen - Ball bearing motors (sizes 100-180),
sleeve bearing motors (sizes 60-95) - Motor isolated on shock mounts -
Corrosion resistant fasteners
Selected Options & Accessories:
Motor - Vari-Green EC motor w/Mounted Potentiometer Dial
Switch, NEMA-1, Toggle, Shipped with Unit
Junction Box Mounted & Wired
Roof Curb-Galv., GPI-22-G12, Under Sized 1.5 in. Total
Damper Shipped Loose, WD-100-PB-16X16, Gravity Operated, Not Coated
Unit Warranty: 1 Yr (Standard)
Printed Date: 6/22/2016
Job: 15085 - 221 E Mountain
Mark: EF-1
CAPS 4.20.1661 P:\2015\15085 -- 221 East Mountain\Mechanical\Equipment Selections\15085 - 221 E Mountain.gfcj Page 2 of 2
DG-112-H20
CONSTRUCTION FEATURES AND ACCESSORIES
Unit Overview
Model Airflow
(CFM)
Heating Cooling
Electrical
V/C/P
DG-112-H20 3,000 Direct Gas Evaporative 460/60/3
Features
• Exterior housing constructed of galvanized steel
• Removable access panels
• Painted or galvanized steel blower and bearing supports
• Forward curved steel blower and motor
• Fan assembly is mounted on neoprene vibration
isolators
• Motor pulleys are adjustable through 15 hp and fixed for
20 hp and greater
• Fan shaft is mounted in permanently lubricated ball
bearings (up through size 118) or ball bearing pillow
blocks (size 120 and greater)
• Static free belts
• Corrosion resistant fasteners are standard
• Disconnect mounted by factory
Options and Accessories
• Air Flow Arrangement: Outdoor Air Only
• With Louvered Intake and Aluminum Mesh Filters,
12x20x2 - (2), 12x25x2 - (1), 16x20x2 - (2), 16x25x2 -
(1)
• Damper: Inlet
•
•
•
•
•
Outdoor Air Intake Position: End
Discharge Position: Bottom
Coating: Galvanized
Insulation: Duct Liner - Heat Source On
Access Side: Right-Hand
•
•
•
•
•
Control Center
Freeze Protection
Dirty Filter Switch
Remote Panel: Kitchen (ships loose)
Service Receptacle (ships loose)
•
•
Mounting: GPI-32.5/82.5-G12
Curb Includes: 1 in. Insul.
• Unit Warranty: 1 Yr (Standard)
NOTES:
Integral unit disconnect is supplied as a standard.
Evaporative cooler section will ship loose and requires field installation.
Unit weight does NOT include skid/crating and may vary by 15% based on selected options.
Printed Date: 6/24/2016
DG-112-H20
PERFORMANCE AND SPECIFICATIONS
Description/Arrangement
Model Qty
Unit Weight (lb)
Discharge
Position
Air Flow
Arrangement
Unit
Arrangement
DG-112-H20 1 897 Downblast Outdoor Air Only Horizontal
Design Conditions
Elevation (ft) Summer DB (F) Summer WB (F) Winter DB (F)
5,663 93.0 64.1 -5.0
Air Performance
Type Volume
(CFM)
External SP
(in. wg)
Total SP
(in. wg)
RPM
Operating hp
(per motor)
Motor Quantity/HP
(per motor)
Supply Fan
Type/Quantity
Supply 3,000 0.5 1.308 1065 1.26 Qty 1/1-1/2 Forward Curve/Qty (1)
Unit Pressure Drop (in. wg)
Air Stream Weatherhood Damper Section Filter Section Cooling Section Heating Section
Supply 0 0.059 0 0.123 0.625
Sound Performance in Accordance with AMCA
Fan
Sound Power by Octave Band
Lwa dBA Sones
62.5 125 250 500 1000 2000 4000 8000
Supply 97 87 76 74 71 68 65 57 79 68 15.5
Electrical/Motor Specifications
V/C/P
Unit MCA
(amps)
Unit MOP
(amps)
Enclosure Supply Motor RPM Supply Efficiency
460/60/3 4.8 15 ODP 1725 Premium
Heating/Cooling Specifications
Heating Type Gas Type Input
(MBH)
Output
(MBH)
LAT (F) Temp. Rise (F)
Direct Gas Natural 214.2 197.1 70.0 75.0
Cooling Type
Evap Cooling
Media
Evap Filters
Evap Cooling
Control
DG-112-H20
FAN CURVES
Supply Fan Performance
Volume
(CFM)
External SP
(in. wg)
Total SP
(in. wg)
RPM
Operating hp
(per motor)
Motor hp
(per motor)
Supply Fan
Type
Supply Fan
Quantity
3,000 0.5 1.308 1065 1.26 1-1/2 Forward Curve 1
Printed Date: 6/24/2016
Job: 15085 - 221 E Mountain
Mark: MAU-1
CAPS 4.20.1661 P:\2015\15085 -- 221 East Mountain\Mechanical\Equipment Selections\15085 - 221 E Mountain.gfcj Page 3 of 8
DG-112-H20
HEATING PERFORMANCE
Direct Gas Heating
Heating Type Gas Type Input
(MBH)
Output
(MBH)
LAT (F) Temp. Rise (F)
Direct Gas Natural 214.2 197.1 70.0 75.0
Direct Gas Unit Details
This unit will come equipped with the following:
• 92% Efficiency
• Direct Spark Ignition
• High quality cast aluminum burners with stainless steel
mixing plates
• Burner capable of 30:1 turndown
• Maxitrol electronic modulation burner control
Heating Details
Agency Approval ETL and IRI
Building Gas Pressure 1/2 PSI
Temperature Control Discharge
Units Rated Gas Pressure 1/2 PSI
Ignition Control DirectSpark
Flame Sensing FlameRod
External Gas Regulator No
Min Gas Pressure For
Maximum Fire
8 in. wg
Printed Date: 6/24/2016
Job: 15085 - 221 E Mountain
Mark: MAU-1
CAPS 4.20.1661 P:\2015\15085 -- 221 East Mountain\Mechanical\Equipment Selections\15085 - 221 E Mountain.gfcj Page 4 of 8
DG-112-H20
86.192
33.676
ELEVATION VIEW
*Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.
*Note: Order of unit sections is from intake of unit to discharge of unit.
*Sections included on this unit: Cooling Section, Heating Section
*Insulation: Duct Liner, from Burner Section through end of unit.
EVAP COOLING
ACCESS SIDE
ACCESS SIDE
BURNER
ACCESS SIDE-
CONTROL CENTER
30.391
66.473
86.192
36.474
PLAN VIEW
* Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.
Printed Date: 6/24/2016
Job: 15085 - 221 E Mountain
Mark: MAU-1
CAPS 4.20.1661 P:\2015\15085 -- 221 East Mountain\Mechanical\Equipment Selections\15085 - 221 E Mountain.gfcj Page 5 of 8
36.474
END VIEW
66.473
0.846
34.772
1.174
31.656
31.681 31.681
1.096
INTAKE VIEW
Printed Date: 6/24/2016
Job: 15085 - 221 E Mountain
Mark: MAU-1
CAPS 4.20.1661 P:\2015\15085 -- 221 East Mountain\Mechanical\Equipment Selections\15085 - 221 E Mountain.gfcj Page 6 of 8
NOTE: Roof Opening Requirements:
Minimum Roof Opening: The minimum roof opening size is the illustrated duct diameter plus 0.25 in. on all sides.
For example: If the duct size is 14 x 14 in. square, the minimum roof opening size is 14.5 x 14.5 in. square.
Maximum Roof Opening: There must be a minimum perimeter of 1.75 in. between the roof opening and the roof curb.
For example: If the roof curb is 75 x 30 in. square, the maximum roof opening is 71.5 x 26.5 in. inches square.
NOTE: The weatherhood and filter sections of the make-up air unit are not supported by the curb.
This is by design, in order to help alleviate water infiltration issues. MUA Unit supports are shipped loose with unit.
Supply
Duct
5.846
7.250
7.250
82.500
CURB LENGTH ACTUAL
32.500
CURB WIDTH
ACTUAL
15.500
16.000
18.000
FOOTPRINT VIEW
UNIT BASE
INSULATION
CURB
1.00
1.63
0.82
1.15
INSIDE OF RAILS 34.15
CURB VIEW
Notes: All dimensions shown are in in.'s.
Curb Dimenision: Length = 82.5 in. Width = 32.5 in. Height = 12 in.
Printed Date: 6/24/2016
Job: 15085 - 221 E Mountain
Mark: MAU-1
CAPS 4.20.1661 P:\2015\15085 -- 221 East Mountain\Mechanical\Equipment Selections\15085 - 221 E Mountain.gfcj Page 7 of 8
Recommended Minimum Combustible Clearances
Floor Top Sides Ends
Insulated/Units 0 in. 0 in. 0 in. 0 in.
Non-Insulated/Units 0 in. 6 in. 6 in. 6 in.
Clearance to combustibles is defined as the minimum distance required between the heating source and the
adjacent combustible surfaces to ensure the adjacent surface's temperature does not exceed 90 F above the
ambient temperature.
Recommended Minimum Service Clearances
Housing 32 and less 42 in. on the controls side of the unit
Housing 35 and higher 48 in. on the controls side of the unit
To ensure ample space for component removal (evaporative cooling media, coils, filters, etc.), service clearances
should be 6 in. wider than the width of the module itself.
Printed Date: 6/24/2016
Job: 15085 - 221 E Mountain
Mark: MAU-1
CAPS 4.20.1661 P:\2015\15085 -- 221 East Mountain\Mechanical\Equipment Selections\15085 - 221 E Mountain.gfcj Page 8 of 8
Dia.
*Overall height may be greater depending on motor
22
28.88
1.75
19.39
29.75
Model: CUE-161-VG
Direct Drive Upblast Centrifugal Roof Exhaust
Fan
Dimensional
Quantity 1
Weight w/o Acc's (lb) 82
Weight w/ Acc's (lb) 140
Roof Opening (in.) 18.5 x 18.5
Performance
Requested Volume (CFM) 3,000
Actual Volume (CFM) 3,000
External SP (in. wg) 0.5
Total SP (in. wg) 0.5
Fan RPM 1252
Operating Power (hp) 0.62
Elevation (ft) 5,663
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.061
Tip Speed (ft/min) 5,449
Static Eff. (%) 38
Motor
Motor Mounted Yes
Size (hp) 1
Voltage/Cycle/Phase 115/60/1
Enclosure ODP
Motor RPM 1300
Windings 1
FLA (Amps) 12.4
Notes:
All dimensions shown are in units of in.
*Please consult factory for actual motor amp draw
LwA - A weighted sound power level, based on ANSI S1.4
dBA - A weighted sound pressure level, based on 11.5 dB
attenuation per Octave band at 5 ft - dBA levels are not
licensed by AMCA International
Sones - calculated using AMCA 301 at 5 ft
Sound Power by Octave Band
Sound
Data
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 75 81 82 78 71 70 66 63 80 68 16.2
Printed Date: 6/24/2016
Job: 15085 - 221 E Mountain
Mark: KEF-1
CAPS 4.20.1661 P:\2015\15085 -- 221 East Mountain\Mechanical\Equipment Selections\15085 - 221 E Mountain.gfcj Page 1 of 2
Model: CUE-161-VG
Direct Drive Upblast Centrifugal Roof Exhaust Fan
Standard Construction Features:
- Aluminum housing - Backward inclined aluminum wheel - Aluminum curb cap
with prepunched mounting holes - Drain trough - Ball bearing motors (sizes
98-160), sleeve bearing motors (sizes 60-95) - Motor isolated on shock mounts -
Corrosion resistant fasteners
Selected Options & Accessories:
Motor - Vari-Green EC motor w/Mounted Potentiometer Dial
Standard curb cap size - 22 in. square
UL/cUL 762 Listed - "Power Ventilators for Rest. Exh. Appliances"
Switch, NEMA-1, Toggle, Shipped with Unit
Junction Box Mounted & Wired
Roof Curb-Galv., GPI-22-G16, Under Sized 1.5 in. Total
Curb Extension-Galv., VCE-22-G15.25
Hinged Bracket Kit (PN 877581) (Shipped Loose)
Grease Trap (PN 475538)
Clean-out Port
Unit Warranty: 1 Yr (Standard)
Printed Date: 6/24/2016
Job: 15085 - 221 E Mountain
Mark: KEF-1
CAPS 4.20.1661 P:\2015\15085 -- 221 East Mountain\Mechanical\Equipment Selections\15085 - 221 E Mountain.gfcj Page 2 of 2
Evap LDB (F) Evap LWB (F)
Required
Flow
Evaporative CELdek 2 in. Alum. Mesh Auto Drain 66.1 64.1 0.29
Printed Date: 6/24/2016
Job: 15085 - 221 E Mountain
Mark: MAU-1
CAPS 4.20.1661 P:\2015\15085 -- 221 East Mountain\Mechanical\Equipment Selections\15085 - 221 E Mountain.gfcj Page 2 of 8
Job: 15085 - 221 E Mountain
Mark: MAU-1
CAPS 4.20.1661 P:\2015\15085 -- 221 East Mountain\Mechanical\Equipment Selections\15085 - 221 E Mountain.gfcj Page 1 of 8
[PEOPLE /
1000 SQ.FT.]
VENTILATION SCHEDULE (2012 IMC)
ZONE
SERVED
BY
ZONE IDENTIFICATION 2012 IMC VENTILATION RATE PROCEDURE - MULTI-ZONE RECIRCULATING SYSTEMS DESIGN CASE
FLOOR PLAN ROOM NAME & REMARKS
NUMBER
OCCUPANCY
CLASSIFICATION
PER TABLE 403.3 - 2012 IMC
ZONE NET
FLOOR
AREA
Az
[SQ.FT.]
OUTDOOR
AIRFLOW
REQUIRED
PER PERSON
Rp (#1)
[CFM /
PERSON]
SUPPLY
RATE TO
ZONE
Vpz (#7)
(MIN.)
[CFM]
PRIMARY
OUTDOOR
AIR
FRACTION
Zp (#8)
ZONE
POPULATION
Pz
[PEOPLE]
BREATHING
OUTDOOR
AIR FLOW
Vbz (#3)
[CFM]
ZONE AIR
DISTRIB.
EFFECT.
Ez (#4)
REQUIRED
ZONE
OUTDOOR
AIR FLOW
Voz (#5)
[CFM]
AIR
FRACTION
Zp (#8)
ZONE
POPULATION
Pz
[PEOPLE]
BREATHING
OUTDOOR
AIR FLOW
Vbz (#3)
[CFM]
ZONE AIR
DISTRIB.
EFFECT.
Ez (#4)
REQUIRED
ZONE
OUTDOOR
AIR FLOW
Voz (#5)
[CFM]
PROVIDED OUTDOOR AIR INTAKE FLOW [CFM] =
TOTAL SUPPLY RATE ΣVpz (#6) [CFM] =
SYSTEM OUTDOOR AIR PERCENTAGE =
IN COMPLIANCE WITH STANDARD? [Y/N] =
SUPPLY
RATE TO
ZONE
Vpz (#6)
(MAX.)
[CFM]
SYSTEM SUMMARY:
UNCORRECTED OUTDOOR AIR INTAKE Vou (#9) [CFM] =
REQUIRED OUTDOOR AIR INTAKE Vot (#10) [CFM] =
OUTDOOR
AIRFLOW
RATE REQ.
PER UNIT
AREA
Ra (#1)
[CFM / SQ.FT.]
ZONE
OCCUPANT
DENSITY
(#2)
[PEOPLE /
1000 SQ.FT.]