March 03, 2016
Ripley Design, Inc.
419 Canyon Ste 200
Fort Collins, CO 80521
RE: Harmony Cottages( Affordable Housing), PDP150030, Round Number 2
Please see the following summary of comments from City staff and outside reviewing
agencies for your submittal of the above referenced project. If you have questions about
any comments, you may contact the individual commenter or direct your questions through
the Project Planner, Clay Frickey, at 970-224-6045 or cfrickey@fcgov.com.
Comment Summary:
Comment Responses: Ripley Design, Interwest Consulting Group, King Surveyors, Greg Fisher Architect
Department: Planning Services
Contact: Clay Frickey, 970-224-6045, cfrickey@fcgov.com
Topic: General
Comment Number: 10 Comment Originated: 12/30/2015
12/30/2015: Comment from GIS - Addresses will be assigned by the GIS
Department after the plans have met final approval through Development
Review and are recorded with the City.
Topic: Landscape Plans
Comment Number: 1 Comment Originated: 12/28/2015
02/02/2016: The updates to the landscape plan provide enough justification to
proceed with forward with the modification request to the 30' setback along both
Taft Hill and Harmony. With that being said, staff would like to see a planting of
evergreens around the detention area at the entrance to the site. This will
provide more year round color to the site.
Response: Evergreens have been added to detention areas
12/28/2015: Staff cannot justify the modification requested to the 30' setback
along Harmony and Taft Hill with the current landscape plan. While the
proposed picket fences will provide some screening and the generous amount
of trees will enhance the aesthetics of the site neither will provide ample
screening from these streets. Please either provide a small berm or a
significant increase in the amount of low shrubs between the back of the
sidewalk and proposed fence line.
Comment Number: 9 Comment Originated: 12/29/2015
12/29/2015: This project is eligible for a reduction in the minimum sizes for
various landscape elements outlined in section 3.2.1(D)(5) of the Land Use
Code.
Comment Number: 11 Comment Originated: 01/29/2016
01/29/2016: The plant material legend is cut off on sheet 3. Since this
information is repeated on sheet 4, you don't need to provide this information on
sheet 3.
Response: Noted.
Topic: Site Plan
Comment Number: 4 Comment Originated: 12/29/2015
01/29/2016: This comment has not been fully resolved. The parking table is still
incorrect. Please update the table to show 8 parking spaces required for the
single-family detached homes.
Response: Parking table has been updated for clarity.
12/29/2015: Will the single-family homes have garages? Since none of the
single-family lots has more than 40' of frontage on a street, each single-family
home must have two off-street parking spaces. Please update the parking
table to reflect the amount of required parking for the single-family detached
units and show how these units meet this standard.
Comment Number: 5 Comment Originated: 12/29/2015
12/29/2015: While there are not bicycle parking requirements for single-family
attached dwellings, staff recommends including some form of bike parking
on-site for residents and guests. Bike hooks in the garage could provide an
additional feature for residents that would provide secure bike storage. Fixed
racks on or near the green courts could provide a convenient location for guests
to store their bikes.
Comment Number: 8 Comment Originated: 12/29/2015
01/29/2016: While the updated landscape plan shows a shrub for parking lot
screening, it is unclear what shrubs will be planted in this area. Please provide
more specific information so staff can make a determination that this shrubbed
area will be sufficient.
Response: More detailed landscape plan is included.
12/29/2015: The headlights from the parked cars in the parking area in
southeast section will be shining directly onto the adjacent homes. Please
provide some low shrubs to provide screening of this parking area from the
adjacent neighborhood.
Department: Engineering Development Review
Contact: Katie Sexton, 970-221-6501, ksexton@fcgov.com
Topic: General
Comment Number: 3 Comment Originated: 12/29/2015
02/03/2016: Repayment amounts will be based on inflation rates for the month
in which the repayments are made. The repayments will be due at building
permit but can be paid sooner if desired.
Response:
12/29/2015: Repayments to the City will be due at the time of building permit
for construction of S Taft Hill Rd. and Harmoney Rd.
Department: Environmental Planning
Contact: Kelly Kimple, 970-416-2401, kkimple@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 12/29/2015
02/03/2016: Thank you for including the seed mixes. Although acceptable, a
mix that includes more forbs such as purple prairie clover (dalea purpurea),
annual sunflower (helianthus annuus), Mexican hat (ratibida columnierfa), and
black-eyed susan (rudbeckia hirta) would be preferred to create more habitat
for birds and pollinators.
Response: Noted.
12/29/2015: Please include the list of plant species for the the water quality
areas. Also, please consider a seed mix for the detention area that includes
native grasses and forbs instead of turf, as currently shown.
Department: Forestry
Contact: Tim Buchanan, 970-221-6361, tbuchanan@fcgov.com
Topic: Landscape Plans
Comment Number: 2 Comment Originated: 01/04/2016
02/02/2016:
It appears that at the project entry/exit along Harmony Road the street trees
closest to the curb-cut may cause site distance conflicts. Evaluate not planting
the two pear trees to the west of this intersection and the first honeylocust to the
east.
Response: Trees have been removed.
01/04/2016:
On final landscape plan adjust street trees away from entry drives to allow
greater site distance at these intersections.
Department: Internal Services
Contact: Sarah Carter, 970-416-2748, scarter@fcgov.com
Topic: Building Insp Plan Review
Comment Number: 1 Comment Originated: 02/02/2016
02/02/2016: Our records indicate that a presubmittal meeting has not been
scheduled for this project yet. Please schedule a presubmittal meeting as soon
as possible by calling 970-416-2748.
Response:
Comment Number: 2 Comment Originated: 02/02/2016
02/02/2016: Per the applicant's response: it is confirmed that State Statute
CRS 9-5 will not apply to this project due to the exception for single and paired
dwellings.
Department: Light And Power
Contact: Todd Vedder, 970-224-6152, tvedder@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 12/30/2015
12/30/2015: Contact Light and Power Engineering to coordinate the
transformer and electric meter locations, please show these locations on the
utility plans. Transformers need to have an 8’ frontal and 3’ side/rear clearance.
It also has to be 10’ within a drivable surface and cannot be located under the
drip zone of any trees.
Response: Acknowledged
Response: Yes, I will arrange the meeting.
Comment Number: 2 Comment Originated: 12/30/2015
12/30/2015: New development and system modification charges may apply. A
link to our online electric fee estimator is below.
http://www.fcgov.com/utilities/business/builders-and-developers/plant-investmen
t-development-fees/electric-development-fee-estimator?id=3
Comment Number: 3 Comment Originated: 12/30/2015
12/30/2015: Will each unit have gas or electric heat? Is single phase service
the only service needed for this project?
Comment Number: 4 Comment Originated: 12/30/2015
12/30/2015: Please identify electric meter locations on utility drawings. It is
recommended to have gained metering for the attached dwelling units and
these should be located on opposite side from gas meters (if applicable).
Comment Number: 5 Comment Originated: 12/30/2015
12/30/2015: Electric lines will need to maintain a 10' parallel separation
between any water lines and 3' parallel separation between any gas lines.
Comment Number: 6 Comment Originated: 12/30/2015
12/30/2015: In order for final design to be completed and construction to begin
the following will need to be submitted to Light & Power: Approved plat, site
plan, utility plan, landscape plan and AutoCAD drawings for the site plan and
utility plan. Invoice must be paid 100% before construction.
Comment Number: 7 Comment Originated: 12/30/2015
12/30/2015: Please contact Todd Vedder with Light & Power Engineering
Department if you have any questions at 970.224.6152. Please reference our
Electric Construction, Policies Practices & Procedures to ensure requirements
and policies are met.
http://www.fcgov.com/utilities/business/builders-and-developers
Comment Number: 8 Comment Originated: 02/02/2016
02/02/2016: Drawings show electric and gas meters together. Will electric
meters be banked on one side of duplex? Electric and gas needs to be
separated by 3' so it is preferred to have electric and gas meters separate on
each side of building. Also electric meter locations are not shown on single
family detached units.
Response: Electric and gas meters will be on the same side of the duplex unit but the meters will be
separated by a minimum of 3’.
Comment Number: 9 Comment Originated: 02/02/2016
02/02/2016: Electric needs to have a parallel separation of 3' from gas and 10'
frm water lines. This needs to be considered when having to design electric
lines utilizing easements. Pocket easements may need to be granted if
transformers have to be placed on lots outside of easement.
Response: Acknowledged.
Comment Number: 10 Comment Originated: 02/02/2016
02/02/2016: Will site be utilizing padmount or submersible transformers?
Response: The site will be utilizing padmount transformers.
Comment Number: 11 Comment Originated: 02/02/2016
02/02/2016: What size will be the main breaker for each unit? This is needed
for transformer sizing.
Response: Electrical Panels will be 150 amps
Comment Number: 12 Comment Originated: 02/02/2016
02/02/2016: Developer/electrician will be responsible for the installation of
secondary service for all non single family detached units. Light and Power will
provide the installation of electric lines up to the transformer and first secondary
box (if applicable) and secondary to single family detached homes.
Response: based on latest correspondence with Todd Vedder, L&P will provide the design and
installation of electric lines (both primary and secondary) for both single family and duplex units.
Department: PFA
Contact: Jim Lynxwiler, 970-416-2869, jlynxwiler@poudre-fire.org
Topic: General
Comment Number: 7 Comment Originated: 02/02/2016
02/02/2016: PRIOR PFA COMMENTS
The project team acknowledges that fire lane signage, gating and a plan for
route finding within the development will be resolved at time of final plans. All
other comments resolved.
Response: Noted. See sheet 6 of 7 for emergency access gate detail.
Response: Fire lane signage and gating is shown on the plans.
Department: Stormwater Engineering
Contact: Heather McDowell, 970-224-6065, hmcdowell@fcgov.com
Topic: General
Comment Number: 7 Comment Originated: 01/29/2016
01/29/2016: Stormwater department comments have been adequately
addressed and we are recommending approval for P&Z hearing.
Response:
Contact: Jesse Schlam, 970-218-2932, jschlam@fcgov.com
Topic: Erosion Control
Comment Number: 1 Comment Originated: 12/28/2015
12/28/2015: The site disturbs more than 10,000 sq-ft, therefore Erosion and
Sediment Control Materials need to be submitted for FDP. The erosion control
requirements are in the Stormwater Design Criteria under the Amendments of
Volume 3 Chapter 7 Section 1.3.3. Current Erosion Control Materials
Submitted do not meet requirements. Please submit; Erosion Control Plan,
Erosion Control Report, and an Escrow / Security Calculation. Also, based upon
the area of disturbance State permits for stormwater will be required since the
site is over an acre. If you need clarification concerning the erosion control
section, or if there are any questions please contact Jesse Schlam
970-218-2932 or email @ jschlam@fcgov.com
Acknowledged
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcounty@fcgov.com
Topic: Building Elevations
Comment Number: 1 Comment Originated: 12/29/2015
02/01/2016: No plans were provided for review. We will need to verify that this
plan was renumbered before plans are filed.
12/29/2015: No comments.
Response: Elevations will be routed for Final Plans
Topic: Landscape Plans
Comment Number: 18 Comment Originated: 02/01/2016
02/01/2016: There are line over text issues. See redlines.
Response: Noted.
Topic: Lighting Plan
Comment Number: 5 Comment Originated: 12/29/2015
02/01/2016: No comments.
12/29/2015: No comments.
Topic: Plat
Comment Number: 11 Comment Originated: 12/29/2015
02/01/2016: The Outlots still need more clarification. See redlines.
Response: THE ADDITION OF OUTLOT LABELS HAS BEEN ADDED AFTER COPIES WERE
SUBMITTED. ALSO THE 20’ EASEMENTS WITHIN OUTLOT B HAVE BEEN REVISED TO BE ONLY U,
D, & EAE. PLEASE SEE OUTLOT TABLE ON SHEET 1. RLE
12/29/2015: Are the 20' easements part of the Outlots? These are confusing.
See redlines.
Response: THE 20’ EASEMENTS ARE PART OF OUTLOTS B & C. THE EASEMENT ITSELF IS ALS
DEFINED BY LINE AND CURVE SEGMENTS AROUND THE BOUNDARY OF SAID EASEMENT. THE
ADDITION OF A CURVE LABEL ON THE EASTERLY MOST 20’ EASEMENT IN OUTLOT C HAS BEEN
ADDED AFTER COPIES WERE SUBMITTED.
Topic: Site Plan
Comment Number: 17 Comment Originated: 12/29/2015
02/01/2016: There are line over text issues. See redlines.
Response: Noted.
12/29/2015: There are line over text issues. See redlines.
Department: Transportation Planning
Contact: Emma Belmont, 970-224-6197, ebelmont@fcgov.com
Topic: General
Comment Number: 2 Comment Originated: 02/05/2016
02/05/2016: In addition to building the stop concrete surface, Transfort also
requires new development to upgrade the stop amenities. Please find the form
in the redlines describing what is required according to the Transfort Bus Stop
Design Standards. Please contact me with any questions.
Response:
Contact: Timothy Wilder, 970-416-2113, twilder@fcgov.com
Topic: Site Plan
Comment Number: 1 Comment Originated: 12/29/2015
02/05/2016: Thanks for relocating this stop per request.
12/29/2015: Transfort bus stop - Please move the bus stop shown on the site
plan to the west, at a location between the emergency access drive and the
Green Court pedestrian sidewalk connection.
Department: Water Conservation
Contact: Eric Olson, 970-221-6704, eolson@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 12/22/2015
12/22/2015: Irrigation plans are required no later than at the time of building
permit. The irrigation plans must comply with the provisions outlined in Section
3.2.1(J) of the Land Use Code. Direct questions concerning irrigation
requirements to Eric Olson, at 221-6704 or eolson@fcgov.com
Department: Water-Wastewater Engineering
Contact: Heather McDowell, 970-224-6065, hmcdowell@fcgov.com
Topic: General
Comment Number: 2 Comment Originated: 01/29/2016
01/29/2016: In regards to the proposed 1" water taps and water fee
calculations, please note the following:
Section 26-128 of the Municipal Code states the following: (1) Single Family
Residential Buildings...For each additional tap or meters larger than
three-fourths (3/4) inch, the nonresidential rate shall apply.
However, there have been recent discussions within the Utility Department
regarding this section of the code because of this project and a couple of others
in regards to determining if the non-residential rate is applicable when a
fire-suppression system in the homes is warranted. We are awaiting
clarification from the City attorney's office on this.
Response: Acknowledged.
Department: Zoning
Contact: Noah Beals, 970-416-2313, nbeals@fcgov.com
Topic: General
Comment Number: 3 Comment Originated: 02/03/2016
02/03/2016: The sidewalk connections on either side of the drive on W
Harmony Rd appear to connect into the ramp of the public sidewalk.
Response: Walk and ramp condition has been addressed.
Response: The sidewalk connection has been re-aligned to connect at the top of the public sidewalk ramp.