May 23, 2014
Cathy Mathis
TB Group
444 Mountain Ave
Fort Collins, CO 80525
Comment Summary:
Department: Current Planning
Contact: Jason Holland, 970-224-6126, jholland@fcgov.com
Topic: General
Note: Rooftop and ground mounted mechanical equipment shall be completely screened from view
from adjacent properties and public streets. In cases where parapets do not accomplish sufficient
rooftop screening, then free-standing screen walls matching the predominant color of the building shall
be constructed. To satisfy this screening requirement, other visible equipment such as conduit,
meters, and plumbing vents attached to the building face or protruding from the roof may be painted to
match surrounding building surfaces.
Comment Number: 1 Comment Originated: 05/19/2014
SE corner of the site, I would like to see the landscape transition to the concrete drain pan be softer
and more integrated into a shrub bed for some of the drain pan, especially since this feature is
prominent at the intersection. Please refer to redlines for suggested alignment.
Comment Number: 2 Comment Originated: 05/19/2014
The plan uses a lot of blue fescue, which is fine, but on its own in the front it seems like it will likely not
have a lot of visual impact given the spacing shown and its growth habit. I would suggest moving the
plants a bit closer to the parking edge, tightening up the spacing and adding a consistent performing
flowering perennial such as a salvia or lavender around and behind the fescue so that the fescue has
some backup, and it would help the plan overall to have some color and be less grass dominant.
Also please consider adding some yellow flowering perennials.
Comment Number: 3 Comment Originated: 05/19/2014
Rock mulch appears to go to the top of the berm so that the berm is half mulch and half rock. Would
suggest less rock so that it is only a 2-3' edge along the parking bays.
Comment Number: 4 Comment Originated: 05/19/2014
Please see the following summary of comments from City staff and outside reviewing agencies for your submittal of
the above referenced project. If you have questions about any comments, you may contact the individual
commenter or direct your questions through the Project Planner, Jason Holland, at 970-224-6126 or
jholland@fcgov.com.
RE: Geico Office Building, FDP140013, Round Number 1
Page 1 of 5
Need a bigger size than 5 gallon for the Plums and Tatarian Maples. Also, the maples are planted on
top of the the storm drain west of the building. Would suggest moving the storm drain under the
sidewalk with manhole access or reconfiguring the parking lot so that there's more room for the
sidewalk and landscape area.
Comment Number: 5 Comment Originated: 05/19/2014
In the planting table, please break out and show which trees are being used to satisfy tree mitigation.
Comment Number: 6 Comment Originated: 05/19/2014
Is the 6% parking lot interior landscape requirement being satisfied? Demonstrate this graphically on
the plan and document quantity.
Comment Number: 7 Comment Originated: 05/19/2014
Please refer to redlines for format comments.
Comment Number: 8 Comment Originated: 05/19/2014
Department: Engineering Development Review
Contact: Tyler Siegmund, 970-221-6501, tsiegmund@fcgov.com
Topic: Construction Drawings
05/20/2014: Please add the Dixon Canyon Lateral signature block to the Utility Plan (sheet C3).
Comment Number: 3 Comment Originated: 05/20/2014
05/20/2014: Please update note #1 under the E. Utility Notes (sheet C0.01) to read City of Fort Collins
Utility and Fort Collins- Loveland Water District Standards. See redlines.
Comment Number: 4 Comment Originated: 05/20/2014
05/20/2014: Please add LCUASS sidewalk detail 1601 to the details sheet.
Comment Number: 6 Comment Originated: 05/20/2014
Topic: General
05/20/2014: Please submit the project quantities and cost estimate sheet to determine if a DCP will be
required for this project. Contact me for additional information or visit the Engineering Development
Review Website: http://www.fcgov.com/engineering/devrev.php
Comment Number: 5 Comment Originated: 05/20/2014
Topic: Plat
05/20/2014: Please extend the emergency access easement to the west property line. See redlines.
Comment Number: 1 Comment Originated: 05/20/2014
Department: Forestry
Contact: Tim Buchanan, 970-221-6361, tbuchanan@fcgov.com
Topic: Landscape Plans
05/21/2014:
Provide 5 upsized mitigation trees in one or more of the following categories.
Shade trees 3.0 inch caliper
Ornamental Trees 2.5 inch caliper
Evergreen Trees 8 feet height
Comment Number: 1 Comment Originated: 05/21/2014
Page 2 of 5
05/21/2014:
Will existing tree number 13 and 14 be impacted from construction? If so note on plan and provide
mitigation.
Comment Number: 2 Comment Originated: 05/21/2014
05/21/2014:
Tatarian Maple is listed as a shrub but should be placed in the tree category and specified at the
minimum size of 1.5 inch caliper.
Comment Number: 3 Comment Originated: 05/21/2014
05/21/2014:
At the SW corner of the Bosnian Pine shown is not very shade tolerant from the future growth of the
English Oak to the south. Fastigate Blue Spruce or Fastigate Norway Spruce would be more shade
tolerant.
Comment Number: 4 Comment Originated: 05/21/2014
05/21/2014:
Please add information in Landscape note number 14 that says in effect that cultivation should not
occur within the drip line of existing trees to retain.
Comment Number: 5 Comment Originated: 05/21/2014
05/21/2014:
Please add a landscape note that describes how the landscape plants including turf will be irrigated.
Comment Number: 6 Comment Originated: 05/21/2014
05/21/2014:
Please edit Prospect Street from Tree Protection Note number 10.
Comment Number: 7 Comment Originated: 05/21/2014
Department: Light And Power
Contact: Rob Irish, 970-224-6167, rirish@fcgov.com
Topic: General
05/16/2014: If the existing electric line along Harmony is under the proposed park strip, Light & Power
can intercept this line and trench north to the proposed transformer location. If the electric line is under
the existing asphalt this could be problematic. Have this line field located to verify the line is within the
parkway and not under the asphalt.
Comment Number: 1 Comment Originated: 05/16/2014
05/16/2014: A C-1 form and a One-line diagram with power requirements will need to be submitted to
Light & Power Engineering.
Comment Number: 2 Comment Originated: 05/16/2014
05/16/2014: Please send an APPROVED Autocad drawing (no later than version 2008) of the site plan
& utility plan to tcox@fcgov.com
Comment Number: 3 Comment Originated: 05/16/2014
Department: PFA
Contact: Jim Lynxwiler, 970-416-2869, jlynxwiler@poudre-fire.org
Topic: General
Page 3 of 5
05/21/2014: Plat - The limits of the EAE should be modified and extended to the property line to the
west to coincide with the public access easement at that end of the site. This will also serve the site by
increasing the dimensions of the hammerhead turnaround at that portion of the property which is
currently undersized per code.
Comment Number: 1 Comment Originated: 05/23/2014
Department: Stormwater Engineering
Contact: Wes Lamarque, 970-416-2418, wlamarque@fcgov.com
Topic: General
05/20/2014: There are some trees planned right on top of a storm sewer along the west face of the
building.
Comment Number: 1 Comment Originated: 05/20/2014
05/23/2014: Please add in the drainage report the existing total flows that enter the irrigation ditch and
the proposed total flows that enter the ditch.
Comment Number: 2 Comment Originated: 05/23/2014
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcounty@fcgov.com
Topic: Building Elevations
05/19/2014: No comments.
Comment Number: 1 Comment Originated: 05/19/2014
Topic: Construction Drawings
05/19/2014: There are line over text issues. See redlines.
Comment Number: 2 Comment Originated: 05/19/2014
Topic: Landscape Plans
05/19/2014: The text in the plant list needs to be sharpened up. It is very fuzzy & pixelated. See
redlines.
Comment Number: 3 Comment Originated: 05/19/2014
Topic: Plat
05/20/2014: Please update the title commitment information if available.
Comment Number: 4 Comment Originated: 05/20/2014
05/20/2014: Please label the easement along Timberline Road. See redlines.
Comment Number: 5 Comment Originated: 05/20/2014
05/20/2014: There is text that needs to be masked. See redlines.
Comment Number: 6 Comment Originated: 05/20/2014
Topic: Site Plan
05/20/2014: Put "Geico Office Building" back into the legal description. See redlines.
Comment Number: 7 Comment Originated: 05/20/2014
Department: Traffic Operation
Contact: Martina Wilkinson, 970-221-6887, mwilkinson@fcgov.com
Page 4 of 5
Topic: Site Plan
05/20/2014: Please include a stop sign (R1-1) at the exit of the parking lot.
Comment Number: 1 Comment Originated: 05/20/2014
Department: Water-Wastewater Engineering
Contact: Roger Buffington, 970-221-6854, rbuffington@fcgov.com
Topic: Construction Drawings
05/20/2014: Minimum grade on a 4" sewer service is 2%.
Comment Number: 1 Comment Originated: 05/20/2014
05/20/2014: Is the 4" FCLWD water main in service or abandoned?
Comment Number: 2 Comment Originated: 05/20/2014
05/20/2014: Is there a conflict where the sewer service crosses the 16" water main or the FCLWD main
in Timberline?
Comment Number: 3 Comment Originated: 05/20/2014
05/20/2014: Is there a conflict where the sewer service crosses the irrigation ditch on the east side of
Timberline?
Comment Number: 4 Comment Originated: 05/20/2014
05/20/2014: Add thrust block detail.
Comment Number: 5 Comment Originated: 05/20/2014
Page 5 of 5